EEDE06-9
technical data
Altherma
ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300
Altherma ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com
EEDE0 6 - 9
EEDE06-9 - 07/2006 Printed in Belgium by Goekint Graphics
“ The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”
EEDE06-9
technical data Altherma
ERYQ005-007A EKHBH007A / EKHBX007A EKSWW150-300
• Chillers • R-410A • ALTHERMA
erA el0 hl1 t4i l-h RAC
Cooling only
Heating only
Heat pump 4
• Altherma • Chillers
• Outdoor units • R-410A • ERYQ
TABLE OF CONTENTS ERYQ
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cooling/Heating capacity tables
4
7 7 9
10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 11 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 12
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 8
14 15
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
• Altherma • Outdoor units
5
• Outdoor units • R-410A • ERYQ
1 i n u a r m o rA o e0 dh1Q t4Y uRl- EA•OR
1
•
Features Cost effective alternative to a fossil fuel boiler
•
Easy to install
Low energy bills and low CO2 emissions
•
Total solution for year round comfort
1
6
• Altherma • Outdoor units
• Outdoor units • R-410A • ERYQ
2
Specifications
2-1 NOMINAL CAPACITY AND NOMINAL INPUT
EKHBH*
Indoor Units Condition 1
Heating capacity
ERYQ007A
ERYQ005A
ERYQ006A
ERYQ007A
EKHBH007A*
EKHBH007A*
EKHBH007A*
EKHBX007A*
EKHBX007A*
EKHBX007A*
4.36
4.36
4.36
4.36
4.36
4.36
kW
Nominal
kW
5.75
6.84
8.43
5.75
6.84
8.43
Maximum kW
7.45
8.79
9.58
7.45
8.79
9.58
Cooling capacity
Minimum
kW
-
-
-
3.67
3.67
3.67
Nominal
kW
-
-
-
5.12
5.86
6.08
-
-
-
5.12
6.13
7.10
Heating PI
Nominal
kW
1.26
1.58
2.08
1.26
1.58
2.08
Cooling PI
Nominal
kW
-
-
-
2.16
2.59
2.75
COP
Nominal
-
4.56
4.34
4.05
4.56
4.34
4.05
EER
Nominal
-
Heating
Minimum
kW
Nominal
kW
5.03
6.10
7.64
5.03
6.10
7.64
Maximum kW
6.68
7.98
8.76
6.68
7.98
8.76
Cooling
-
-
-
2.37
2.26
2.21
3.87
3.87
3.87
3.87
3.87
3.87
Minimum
kW
-
-
-
4.82
4.82
4.82
Nominal
kW
-
-
-
7.20
8.16
8.37
Maximum kW
-
-
-
7.20
8.50
8.91 2.54
Heating PI
Nominal
kW
1.58
1.95
2.54
1.58
1.95
Cooling PI
Nominal
kW
-
-
-
2.16
2.59
2.75
COP
Nominal
-
3.18
3.13
3.00
3.18
3.13
3.00
EER
Nominal
-
-
-
-
3.33
3.15
3.04
ERYQ005A (+ EKHBX)
ERYQ006A (+ EKHBX)
ERYQ007A (+ EKHBX)
Notes
2-2
ERYQ006A
Minimum
Maximum kW
Condition 2
EKHBX*
ERYQ005A
1 2
*Condition 1 - cooling Ta 35°C - LWE 7°C - heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C) * Condition 2 - cooling Ta 35°C - LWE 18°C (DT = 5°C) - heating Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C)
TECHNICAL SPECIFICATIONS
Casing Dimensions
Packing
ERYQ006A (+ EKHBH)
ERYQ007A (+ EKHBH)
Colour
Ivory white
Material
Polyester painted galvanised steel
Unit
Packing
Weight
ERYQ005A (+ EKHBH)
Height
mm
797
Width
mm
960
Depth
mm
390
Height
mm
735
Width
mm
825
Depth
mm
300
Unit
kg
56
Packed Unit
kg
61
Material
EPS Carton
Weight Heat Exchanger
Dimensions
Length
kg
5
mm
845
mm
1.8
Nr of Rows Fin Pitch
2
Nr of Stages Tube type Fin
Type
WF fin
Treatment Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity Motor
1 Quantity Output
Compressor
1 W
Quantity Motor
32 Hi-Xa(8)
53 1
Model
2YC63BXD#C
Type Motor Output
Hermetically sealed swing compressor W
• Altherma • Outdoor units
1920
7
• Outdoor units • R-410A • ERYQ
2
1 2
2-2
Specifications TECHNICAL SPECIFICATIONS
Operation Range
Heating Cooling Sanitary water
Sound Level (nominal)
Heating
Cooling
Refrigerant
ERYQ005A (+ EKHBH)
-20
°CWB
25
Min
°CDB
7
Max
°CDB
20
Min
°CDB °CDB
-20
Sound Power
dBA
64
64
66
64
64
66
Sound Pressure
dBA
48
48
52
48
48
52
Sound Power
dBA
63
64
66
Sound Pressure
dBA
47
47
53
43
R-410A kg
1 FVC50K
Charged Volume
l Type mm
Type mm
Quantity
15,9 1
Type
Socket
Diameter (OD)
mm
Minimum
m
3
Maximum m
30
Additional Refrigerant Charge
kg/m
Maximum m
Max. internunit level difference
m
18
0.02 IF > 10m 15
20
Defrost Method
Reverse cycle
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Standard Accessories
Installation manual
Item Quantity
1
Item
Drain plug
Quantity
8
6,35 Flare connection
Diameter (OD)
Installation height difference
0.75 Flare connection
Diameter (OD)
Piping Length
1.7 Expansion valve(electronic type)
Type
Drain
ERYQ007A (+ EKHBX)
Max
Nr of Circuits
Gas
ERYQ006A (+ EKHBX)
°CWB
Type
Liquid (OD)
ERYQ005A (+ EKHBX)
Min
Control
Piping connections
ERYQ007A (+ EKHBH)
Max
Charge
Refrigerant Oil
ERYQ006A (+ EKHBH)
1
• Altherma • Outdoor units
• Outdoor units • R-410A • ERYQ
2 2-3
Specifications ELECTRICAL SPECIFICATIONS
Power Supply
ERYQ007A (+ EKHBH)
ERYQ005A (+ EKHBX)
ERYQ006A (+ EKHBX)
ERYQ007A (+ EKHBX)
V1
1
Phase
1˜
2
Voltage
Hz
50
V
220-440
Voltage range
Maximum V
Maximum running Current
Cooling
A
Heating
A
Cooling
A
Heating
A
18
A
20
Recomended fuses Wiring connections
ERYQ006A (+ EKHBH)
Name Frequency
Current
ERYQ005A (+ EKHBH)
For Power Supply
Quantity
For connection Quantity with indoor Remark
• Altherma • Outdoor units
+10% 11 11 16.25
3 4 Included earth wiring
9
• Outdoor units • R-410A • ERYQ
1
3
Capacity tables
3-1
Cooling/Heating capacity tables
COOLING
Model
3 005
006
007
Tamb (°C) LWE (°C) 7 11 13 16 20 7 11 13 16 20 7 11 13 16 20
20 CC 6.01 6.81 7.23 7.88 8.80 7.15 8.09 8.57 9.33 10.4 8.24 9.26 9.79 10.6 11.7
25 PI 1.56 1.57 1.57 1.56 1.55 2.05 2.09 2.11 2.13 2.16 2.43 2.49 2.52 2.57 2.63
CC 5.73 6.50 6.90 7.54 8.42 6.84 7.73 8.20 8.92 9.9 7.90 8.87 9.38 10.17 11.3
PI 1.48 1.52 1.54 1.57 1.57 1.57 1.82 1.88 1.91 1.95 1.97 1.98 2.06 2.13 2.17 2.22 2.26 2.28
HC 3.67 4.32 4.77 5.62 6.38 7.45 4.62 5.34 5.83 6.77 7.61 8.79 5.16 5.93 6.46 7.45 8.35 9.58
30 PI 1.75 1.77 1.78 1.78 1.79 2.28 2.34 2.36 2.40 2.44 2.68 2.76 2.80 2.86 2.94
CC 5.43 6.17 6.56 7.17 8.03 6.50 7.34 7.79 8.49 9.48 7.52 8.45 8.93 9.69 10.75
PI 1.59 1.65 1.68 1.72 1.74 1.75 1.94 2.02 2.07 2.13 2.16 2.19 2.19 2.29 2.34 2.41 2.46 2.51
HC 3.47 4.07 4.49 5.28 6.00 7.00 4.43 5.09 5.55 6.42 7.21 8.32 4.97 5.68 6.17 7.10 7.93 9.10
35 PI 1.95 1.98 2.00 2.01 2.03 2.52 2.59 2.63 2.68 2.73 2.94 3.05 3.10 3.17 3.26
CC 5.12 5.83 6.20 6.79 7.63 6.13 6.94 7.36 8.03 8.99 7.10 7.79 8.14 8.68 9.39
PI 1.71 1.79 1.83 1.88 1.91 1.94 2.08 2.18 2.24 2.32 2.37 2.42 2.34 2.46 2.53 2.62 2.69 2.76
HC 3.33 3.89 4.28 5.03 5.72 6.68 4.30 4.92 5.35 6.17 6.92 7.98 4.86 5.51 5.97 6.85 7.65 8.76
40 PI 2.16 2.21 2.23 2.26 2.29 2.77 2.87 2.91 2.97 3.04 3.23 3.31 3.36 3.41 3.48
CC 4.80 5.30 5.56 5.95 6.48 5.35 5.84 6.09 6.46 6.96 5.68 6.12 6.34 6.67 7.09
PI 1.84 1.94 1.99 2.06 2.11 2.15 2.23 2.36 2.42 2.52 2.59 2.66 2.51 2.65 2.73 2.85 2.93 3.02
HC 3.25 3.78 4.15 4.87 5.53 6.47 4.24 4.82 5.23 6.02 6.74 7.78 4.80 5.42 5.86 6.70 7.47 8.56
43 PI 2.39 2.32 2.28 2.22 2.13 2.68 2.62 2.59 2.53 2.44 2.86 2.80 2.77 2.71 2.61
CC 4.59 4.98 5.18 5.46 5.82 4.89 5.21 5.36 5.57 5.82 4.87 5.18 5.33 5.55 5.80
PI 2.53 2.38 2.30 2.18 1.99 2.59 2.43 2.34 2.20 1.99 2.59 2.43 2.35 2.20 1.99
HEATING (Peak values)
Model
005
006
007
LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7
30 HC 3.93 4.65 5.14 6.06 6.89 8.03 4.87 5.67 6.21 7.23 8.14 9.40 5.42 6.27 6.84 7.92 8.9 10.2
35
40
45
50 PI 1.99 2.10 2.16 2.25 2.31 2.37 2.40 2.55 2.63 2.75 2.83 2.92 2.70 2.86 2.95 3.10 3.20 3.31
HEATING (integrated values*)
Model
005
006
007
LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7
30 HC 3.50 4.14 4.52 5.27 5.92 8.03 4.34 5.04 5.46 6.29 7.00 9.40 4.82 5.58 6.02 6.89 7.6 10.2
35 PI 1.40 1.45 1.45 1.46 1.45 1.57 1.73 1.79 1.80 1.81 1.81 1.98 1.96 2.03 2.04 2.07 2.08 2.28
HC 3.27 3.85 4.20 4.89 5.49 7.45 4.11 4.75 5.13 5.89 6.55 8.79 4.59 5.28 5.69 6.48 7.18 9.58
40 PI 1.51 1.56 1.58 1.60 1.60 1.75 1.85 1.92 1.94 1.98 1.99 2.19 2.08 2.17 2.20 2.25 2.27 2.51
HC 3.09 3.62 3.95 4.59 5.16 7.00 3.94 4.53 4.88 5.59 6.20 8.32 4.43 5.06 5.43 6.17 6.82 9.10
45 PI 1.62 1.70 1.72 1.75 1.76 1.94 1.98 2.07 2.10 2.15 2.18 2.42 2.23 2.34 2.37 2.44 2.47 2.76
HC 2.97 3.46 3.77 4.38 4.92 6.68 3.83 4.38 4.71 5.37 5.96 7.98 4.32 4.91 5.26 5.96 6.58 8.76
SYMBOLS CC HC PI LWE LWC Tamb
10
50 PI 1.75 1.84 1.87 1.92 1.94 2.15 2.12 2.24 2.28 2.35 2.38 2.66 2.39 2.52 2.57 2.65 2.70 3.02
HC 2.89 3.36 3.65 4.24 4.76 6.47 3.77 4.29 4.60 5.23 5.80 7.78 4.27 4.82 5.15 5.83 6.43 8.56
PI 1.89 2.00 2.03 2.10 2.13 2.37 2.28 2.42 2.47 2.56 2.61 2.92 2.56 2.72 2.78 2.88 2.94 3.31
* The integrated heating capacity and power input, is the average heating capacity and power input during 1 cycle. (from end of defrost till end of the next defrost).
4TW56712-1A
NOTES
: Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85%
• Altherma • Outdoor units
1
2
3
Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total input according to Eurovent rating standard 6/C/003-2006
• Outdoor units • R-410A • ERYQ
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing unit (mm)
ERYQ Drain outlet (I.D. J 15.9 hose for connection)
Minimum space for air passage
Wall height on air outlet side = less than 1200
1 4
In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10)
Name plate Wiring inlet
Brand name label
Outdoor air thermistor
Terminal strip with earth terminal
Liquid stop valve (J6.4 CuT) Service port
Gas stop valve (J15.9 CuT)
3D051658B
• Altherma • Outdoor units
11
• Outdoor units • R-410A • ERYQ
1
4
Dimensional drawing & centre of gravity
4-2
Centre of gravity
ERYQ
4
The position of foundation bolt 4D042258G
12
• Altherma • Outdoor units
• Outdoor units • R-410A • ERYQ
5
Piping diagram
ERYQ
1
Outdoor unit Heat exchanger
5
Outdoor temperature thermistor
Capillary tube 1
Capillary tube 2 Capillary tube 3
Heat exchanger thermistor
Muffler with filter
Refrigerant flow Cooling Heating
Capillary tube 4
Filter Motor operated valve
Propeller fan
Filter Four way valve on : heating
Muffler with filter
Field piping
Muffler Liquid stop valve Muffler
Field piping Discharge pipe thermistor
Compressor
Accumulator
Gas stop valve with service port
3D052750A
• Altherma • Outdoor units
13
• Outdoor units • R-410A • ERYQ
1
6
Wiring diagram
6-1
Wiring diagram
ERYQ
6 Power supply
To indoor unit
Sheet metal
Indoor
g Field wiring
(discharge) (outdoor) (Condenser) Outdoor Z1C∼Z7C X1M, X2M Y1E V2, V3, V5, V9, V100 SA2 FU1, FU2, FU3: AC1, AC2 U, V, W, X11A, X12A E1, E2 HR1, HR2
14
: Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Surge arrester : Fuse
: Connector
MRM10, MRM20 MRC/W R1T∼R3T S2∼S102 LEDA L N SW1 SW4 M1C M1F L1R
: Magnetic relay : Thermistor : Connector : Pilot lamp : Live : Neutral : Forced operation on/off switch SW (SW1) : Local setting SW (SW4) : Compressor motor : Fan motor : Reactor
• Altherma • Outdoor units
Q1L PM1 PCB1,2 Y1R Sheet metal
: Overload protector : Power module : Printed circuit board : Reversing solenoide valve coil : Terminal strip fixed plate
3D052296B
• Outdoor units • R-410A • ERYQ
6
Wiring diagram
6-2
External connection diagram
EKHB-A
1
Standard parts Power supply For more details please check unit wiring diagram
Outdoor unit
6
3 core
Unit power supply: 230V + earth
X1M:L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
Optional power supply
X2M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
3 or 4 core
3 core
Optional parts
4 core
Field supply X1M:9-10-11-Earth
Sanitary tank Room thermostat Power supply booster heater
Q2L - Clixon booster heater
R5T - Thermistor water temperature
4 core 5 core
230V or 400V
A3P (optional)
X1M:7-8-Earth
NO valve:
2 core
NC valve:
2 core
2 core Signal Thermistor cable Note: min. distance to power cable = 3cm
2 way valve M2S (EKHBX Units) for cooling mode
3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating
Indoor unit User interface
3TW56719-6
• Altherma • Outdoor units
15
• Outdoor units • R-410A • ERYQ
7-1
Sound pressure spectrum
ERYQ005ABV3 Cooling
ERYQ006ABV3 Cooling Sound pressure level (dB)
7
Sound data
Sound pressure level (dB)
1
7
3TW56717-1
Octave band center frequency (Hz)
3TW56717-1
NOTES 1 2 3 4
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
1 Coil Microphone
2 3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil Microphone
Location of microphone
Location of microphone
ERYQ007ABV3 Cooling Sound pressure level (dB)
Sound pressure level (dB)
ERYQ005ABV3 Heating
3TW56717-1
Octave band center frequency (Hz)
3TW56717-2
NOTES 1 2 3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
1
Coil Microphone
2 3 4
Location of microphone
16
Octave band center frequency (Hz)
NOTES
• Altherma • Outdoor units
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil Microphone
Location of microphone
• Outdoor units • R-410A • ERYQ
7
Sound data
7-1
Sound pressure spectrum ERYQ007ABV3 Heating
3TW56717-2
Octave band center frequency (Hz)
2 3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
7
3TW56717-2
NOTES 1
1
Sound pressure level (dB)
Sound pressure level (dB)
ERYQ006ABV3 Heating
Octave band center frequency (Hz)
NOTES 1
Coil Microphone
2 3 4
Location of microphone
• Altherma • Outdoor units
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil Microphone
Location of microphone
17
• Outdoor units • R-410A • ERYQ
8
Operation range
1
Outdoor temp. (°CDB)
Cooling mode
8
Leaving evaporator water temperature (°C)
Heating mode
Outdoor temp. (°CDB)
Leaving condenser water temperature (°C)
Sanitary mode
Outdoor temp. (°CDB)
: Booster heater operation only
Leaving condenser water temperature (°C)
4TW56713-1A
18
• Altherma • Outdoor units
• Indoor units • R-410A • EKHBH / EKHBX
TABLE OF CONTENTS EKHBH / EKHBX
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 23
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 25 Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
27 29
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Static pressure drop unit
• Altherma • Indoor units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
19
• Indoor units • R-410A • EKHBH / EKHBX
1 H t K i E n u a/ m r rA Ho e0 Bo h1 Hd t4 nKl- E•IAR •
Features Cost effective alternative to a fossil fuel boiler
•
Easy to install
Low energy bills and low CO2 emissions
•
Total solution for year round comfort
2 1
20
• Altherma • Indoor units
• Indoor units • R-410A • EKHBH / EKHBX
2 2-1
Specifications TECHNICAL SPECIFICATIONS
Outdoor units Nominal input (Indoor only) Casing Dimensions
Packing
EKHBH007A (+ERYQ006A)
EKHBH007A (+ERYQ007A)
ERYQ005A
ERYQ006A
ERYQ007A
W
EKHBX007A (+ERYQ005A)
EKHBX007A (+ERYQ006A)
EKHBX007A (+ERYQ007A)
ERYQ005A
ERYQ006A
ERYQ007A
230
Colour
RAL9010
Material
Polyester painted galvanised steel
Packing
Unit
Weight
EKHBH007A (+ERYQ005A)
Height
mm
2 2
1225
Width
mm
660
Depth
mm
595
Height
mm
895
936
Width
mm
487
487
Depth
mm
361
461
Unit
kg
55
65
Packed Unit
kg
65
75
Material
EPS Wood Carton PS(straps)
Weight
kg
Main components
Pump
Type
Pump
Nominal ESP unit
Cooling Heating
kPa
Main components
Pump
Power input
W
Water side Heat exchanger
Type
10 Water cooled
Nr. of speed
3
kPa 46.5
40.1
29.0
46.5
40.1
29.0
1
Water volume
l
Water flow rate Min.
l/min
0.67 12
Cooling
l/min
Heating
l/min
Main components
Water side Heat exchanger
Insulation material
Expansion vessel
Volume
l
10
Max. water pressure
bar
3
Pre pressure
bar
1
Diameter perforations
mm
1
inch
1"MBSP
Piping
inch
1"MBSP
Safety valve
bar
3
16.5
Material Piping connections diameter
44.4
Brazed plate
Qty
Water flow rate Nom.
Water circuit
46.5
130
Water side Heat exchanger
Water filter
49.9
19.6
24.2
14.7
16.5
17.6
16.5
19.6
24.2
Polyurethane foam
Brass
Manometer
Yes
Drain valve / Fill valve
Yes
Shut off valve
Yes
Air purge valve
Yes
• Altherma • Indoor units
21
• Indoor units • R-410A • EKHBH / EKHBX
2 2-1
2 2
Specifications TECHNICAL SPECIFICATIONS
EKHBH007A (+ERYQ005A)
EKHBH007A (+ERYQ006A)
EKHBH007A (+ERYQ007A)
EKHBX007A (+ERYQ005A)
Refrigerant Circuit
Gas side diameter
mm
15,9
Liquid side diameter
mm
(2)
Sound Level
Sound Pressure
Operation range
Waterside
Notes
dBA
27
Cooling
°C
7 ˜ 20
Heating
°C
EKHBX007A (+ERYQ007A)
30 ˜ 55 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment. ERYQ = 6.35 mm EKHB = 9.52 mm (flare connection)
22
EKHBX007A (+ERYQ006A)
• Altherma • Indoor units
• Indoor units • R-410A • EKHBH / EKHBX
2 2-2 Electric heater
Specifications ELECTRICAL SPECIFICATIONS Type Power Supply
Current Electric heater
Power Supply
Current Electric heater
Current Electric heater
Power Supply
Current
EKHBX007A (+ERYQ006A)
EKHBX007A (+ERYQ007A)
1 50
2
Voltage
V
230
2
Running Current
A
13 6V3
Phase
1
Frequency
Hz
50
Voltage
V
230
Running Current
A
26 6W1
Phase
3N
Frequency
Hz
50
Voltage
V
400
Running Current
A
8.6 6T1
Phase
3
Frequency
Hz
50
Voltage
V
230
Running Current
A
15 9W1
Phase
3N
Frequency
Hz
50
Voltage
V
400
Running Current
A
13
Type Power Supply
EKHBX007A (+ERYQ005A)
Hz
Type
Current Electric heater
Phase
Type Power Supply
EKHBH007A (+ERYQ007A)
Frequency
Type Power Supply
EKHBH007A (+ERYQ006A)
3V3
Type
Current Electric heater
EKHBH007A (+ERYQ005A)
9T1 Phase
3
Frequency
Hz
50
Voltage
V
230
Running Current
A
23
• Altherma • Indoor units
23
24
Back up heater 6kW 1∼230 V
Back up heater 6kW 3∼400 V + N
Back up heater 6kW 3∼230 V
Back up heater 9kW 3∼400 V + N
Back up heater 9kW 3∼230 V
6V3
6W1
6T1
9W1
9T1
Sanitary warm water tank 150 l 230 V
Sanitary warm water tank 200 l 230 V
Sanitary warm water tank 300 l 230 V
Sanitary warm water tank 200 l 400 V
Sanitary warm water tank 300 l 400 V
Wall bracket for EKSWW150V3
EKSWW150V3
EKSWW200V3
EKSWW300V3
EKSWW200Z2
EKSWW300Z2
EKWBSWW150
Available kits
Back up heater 3kW 1∼230 V
3V3
⎯ ⎯ ⎯ ⎯
⎯ ⎯ ⎯ ⎯
• Altherma • Indoor units V ⎯ ⎯
⎯ ⎯
V
V
V
V
V
⎯
V
⎯
V
EKHBH007A6V3 EKHBX007A6V3
V
V
V
V
V
⎯
⎯
⎯
V
⎯
⎯
EKHBH007A6W1 EKHBX007A6W1
⎯
⎯
V
V
V
⎯
⎯
V
⎯
⎯
⎯
EKHBH007A6T1 EKHBX007A6T1
V
V
V
V
V
⎯
V
⎯
⎯
⎯
⎯
EKHBH007A9W1 EKHBX007A9W1
⎯
⎯
V
V
V
V
⎯
⎯
⎯
⎯
⎯
EKHBH007A9T1 EKHBX007A9T1
3
Available options
EKHBH007A3V3 EKHBX007A3V3
Number
3TW56719-5
Kit
Kit
Kit
Kit
Kit
Kit
Factory mounted
Factory mounted
Factory mounted
Factory mounted
Factory mounted
Factory mounted
Availability
3
Heating only model Reversible model
Description
2
Reference
Optional equipment for EKHB(H/X)007*
• Indoor units • R-410A • EKHBH / EKHBX
Options
• Indoor units • R-410A • EKHBH / EKHBX
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKHBH-A
2 4
Service door
Setup 1 Setup 2
A ≥ 200 ≥ 350
B ≥ 400 ≥ 200
1’’ female BSP
(Closed) 361 (Open) 553
1’’ male BSP
Min. 400
Min. 200
Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN conection 1’’ M BSP j 4 Water OUT connection 1’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Drain / fill valve j 7 Air purge j 8 Expansion vessel + nipple j 9 Blow off valve j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J9.52 flare connection j 14 Shut off valves (delivered with unit) j 15 Thermistor connection (+ sanitary warm water tank) j 16 Holes for fixation j 17 Blow off drain j 18 Switchbox connection terminals j 19 Wallbracket
Min. 100
Minimum space for service & ventilation
3TW56714-1A
EKHBX-A
Minimum space for service & ventilation
1’’ female BSP
(Closed) 461 (Open) 653
1’’ male BSP
Dimensions wallbracket
Min. 400
Min. 200
Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN conection 1’’ M BSP j 4 Water OUT connection 1’’ M BSP j 5 Power supply intake (+ sanitary warm water tank) j 6 Drain / fill valve j 7 Air purge j 8 Expansion vessel + nipple j 9 Blow off valve j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J9.52 flare connection j 14 Shut off valves (delivered with unit) j 15 Thermistor connection (+ sanitary warm water tank) j 16 Holes for fixation j 17 Blow off drain / drain of drainpan j 18 Switchbox connection terminals j 19 Wallbracket
Min. 125
Service door
Setup 1 Setup 2
A ≥ 200 ≥ 350
B ≥ 400 ≥ 200
• Altherma • Indoor units
3TW56724-1A
25
• Indoor units • R-410A • EKHBH / EKHBX
5
Piping diagram
EKHB-A
Water side
R4T R3T R2T R1T
2
Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat-exchanger thermistor
Field installation Filter Inlet Shut off valve
5 Refrigerant side
Safety valve Drain valve
Pressure gauge
Drain
Expansion vessel Cooling (EKHBX) Heating (EKHBX + EKHBH)
Option backup heater Drain valve
Field installation
Air purge
Flowswitch
Pump
Outlet Shut off valve
Overview Electric heater body Evaporator Condensor
Outdoor unit
Refr. out Refr. in
Water inlet Refrigerant side
Water side
Refr. in Water outlet Refr. out
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe
26
• Altherma • Indoor units
3TW56715-1
• Indoor units • R-410A • EKHBH / EKHBX
6
Wiring diagram
6-1
Wiring diagram
EKHBH/X-A3V3 Power supply
Outdoor unit
Sanitary tank
>> See note 2 > See note 2 > See note 2
See note 2 typcial 2-persons usage pattern. Medium Daily demand up to 325 l -> typical 3 to 4 persons usage pattern. High Daily demand up to 550 l -> 4 to 6 persons usage pattern.
(2) Heat-up time: Definition: Heat-up time The time required to reheat the sanitary tank to 55°C after tapping a certain volume of hot water at 40°C. note: changing the field settings (see installation manual) can influence the heat-up time. Tank 150L 200L 300L
Setpoint temp. (°C) 55 55 55
Heat-up time for Heat-up time for 50 150 L (bath) L (shower) 60 45 60 40 50 30
Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERYQ007
(3) Efficiency of sanitary hot water production: In the ALTHERMA by Daikin system both the heat-pump and the electric booster heater supply the energy to produce sanitary hot water. The higher the portion of energy supplied by the heat-pump, the more energy efficient the system is. Lowering the setpoint temperature increases the portion of energy supplied by the heat-pump and thus the efficiency of the system.
Heat-pump portion
Definition: Heat-pump portion Percentage of energy supplied by the heat-pump in the total energy need for sanitary hot water.
Setpoint temp. (°C) Conditions:
Real life condition Outdoor temperature Room temperature Outdoor unit type Tank type Field settings
Simulation of a daily usage based upon ′medium′ usage pattern. 7°CDB / 6°CWB 20°CDB ERYQ007 200l Default field settings (see installation manual).
4TW56719-3
34
• Altherma • Sanitary Hot Water
• Sanitary Hot Water • R-410A • EKSWW
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKSWW j 1 Water mains in female 3/4’’ BSP j 2 Water mains out female 3/4’’ BSP j 3 Thermistor connection female 1/2’’ BSP j 4 Flow (from hydrobox) female 3/4’’ BSP j 5 Return (to hydrobox) female 3/4’’ BSP j 6 Switchbox j 7 Clixon j 8 Connection female 3/4’’ BSP
3 4
3TW56714-4
• Altherma • Sanitary Hot Water
35
• Sanitary Hot Water • R-410A • EKSWW
5
Wiring diagram
5-1
External connection diagram
EKHB-A Standard parts Power supply For more details please check unit wiring diagram
Outdoor unit 3 core
Unit power supply: 230V + earth
X1M:L-N-Earth
Backup heater power supply (3/6/9kW): 400V or 230V + earth
3 5
Optional power supply
X2M:1-2-3-Earth
Booster heater power supply (3kW): 400V or 230V + earth
3 or 4 core
3 core
Optional parts
4 core
Field supply X1M:9-10-11-Earth
Sanitary tank Room thermostat Power supply booster heater
Q2L - Clixon booster heater
R5T - Thermistor water temperature
4 core 5 core
A3P (optional)
X1M:7-8-Earth
230V or 400V
NO valve:
2 core
NC valve:
2 core
2 core Signal Thermistor cable Note: min. distance to power cable = 3cm
2 way valve M2S (EKHBX Units) for cooling mode
3 way valve M3S (when EKSWW is installed) selection sanitary-floorheating
Indoor unit User interface
3TW56719-6
36
• Altherma • Sanitary Hot Water