Three-phase inverters for grid- connected .... High power density due to a compact design. ⢠Isolation ... medium-voltage switchgear and transformers or.
Three-phase inverters for gridconnected photovoltaic systems SINVERT 60 M – SINVERT 1700 MS
Grid-connected photovoltaic systems with maximum yields and a long service life – for 25 years and more! With SINVERT, you are on the sunny side. Because our inverters are based on reliable standard Siemens components, such as SIMATIC S7 controllers or MASTERDRIVES and SINAMICS converters.
Their reliability and long service life have been sucessfully proven a hundred thousand times over in industrial applications. We place particular importance on a high standard of quality and longterm availability, also where spare parts are concerned. In short: Best quality for an excellent yield of your PV system.
SINVERT PV Inverter Answers for energy.
Technical Data SINVERT PV Inverter Inverter type *
60 M
80 LV M
100 M
160 LV MS
200 MS
240 LV MS
Input DC MPP-Voltage Range
V
450 – 750 (350 – 750 for SINVERT 80, 160, 240)
Max. Operating Voltage
V
820
Max. System Voltage
V
900 (must not be exceeded)
Rated input power
kW
68
80
Rated input current
A
149 2
Number of DC-inputs Maximum Current per Input
A
111
160
176
243
3
1 or 3 250 / 80
80
222
240
352
486
528
6
2 or 6
9
80
250 / 80
80
Output AC Grid Interface
3 ~ 230/400 V; 50 Hz
Optional 60 Hz operation
x
x
Rated output power
kW
65
77
105
154
210
231
Rated output current
A
94
111
153
222
306
333
Efficiency eta EU
%
94.1
92.4
94.9
93.2
95.6
93.3
Max. efficiency
%
95.7
96.2
96.2
96.2
96.2
96.2
Number of single units
Pcs.
1 x 60
1 x 80
1 x 100
2 x 80
2 x 100
3 x 80
Dimensions (H x W x D) for each single unit
mm
Further data
1902 x 918 x 834
Weight of each single unit
kg
690
830
850
830
850
2540
Ambient Temperature
°C
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
Installation
Up to 1000 m above sea level
Maximum Humidity Rating
%
* M = Master MS = Master-Slave system
Efficiency characteristic SINVERT 100
85 (non condensing)
300 MS
350 M
400 MS
420 M
700 MS
850 MS
1000 MS
1300 MS
1400 MS
1700 MS
450 – 750 820 900 (must not be exceeded) 333
373
444
465
746
930
1119
1395
1492
1860
729
820
972
1022
1640
2044
2460
3066
3280
4088
3 or 9
4
4 or 12
4
8
8
12
12
16
16
250 / 80
250
250 / 80
250
250
250
250
250
250
250
x
x
x
x
x
x
x
x
x
x
315
357
420
435
714
870
1071
1305
1428
1740
459
518
612
630
1036
1260
1554
1890
2072
2520
95.7
95.5
95.8
95.7
96
96.2
96.1
96.2
96.1
96.3
96.2
96.5
96.2
96.5
96.5
96.5
96.5
96.5
96.5
96.5
3 x 100
1 x 350
4 x 100
1 x 420
2 x 350
2 x 420
3 x 350
3 x 420
4 x 350
4 x 420
2000 x 2700 x 800
1902 x 918 x 834
3 ~ 230/400 V; 50 Hz
2000 x 2700 x 800
850
2025
850
2540
2025
2540
2025
2540
2025
2540
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
0 – 50
Up to 1000 m above sea level 85 (non condensing)
Efficiency characteristic SINVERT 420
Connecting inverters in parallel makes it easy to realize PV plants without any restrictions in size.
Advantages at a glance • Best performance ratio due to optimized energy availability • Optimized for reliability and long lifespan • Little cost of installation and operation • High power density due to a compact design • Isolation surveillance of the PV array • Integrated protection against overcurrent and overvoltage • Galvanic separation protects against feeding DC into the grid • Ethernet communication interface standard
Siemens AG Industry Sector Systems Engineering P.O. Box 23 55 90713 FÜRTH GERMANY www.siemens.com/sinvert
Options • Communication, remote monitoring and diagnostics – Data logger with archive and analysis via Internet portal – Remote monitoring by WinCC with alarming functions (Fax, e-mail or SMS) – Weather station • Cabinet heating • Auxiliary power connection • Plant-specific grounding of the PV array • Containers available in different sizes for the inverters, medium-voltage switchgear and transformers or medium-voltage measurement (control of reactive power) • Warranty – Extension possible – Customer-specific service contracts
The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.
2008 Product Data 1 ..... Customers will have to purchase the products considering the energy label to meet ..... Note : O : Applie, X : Not applied, â : No relation.
Complementary MOS (CMOS) inverter. ⢠Static analysis of CMOS inverter ... Circuit and load-line diagram of inverter with PMOS current source pull-up: V. OUT.
BATTERIES IS AS FOLLOWS: 3 Remove the Battery by sliding it out and then lift up. ⢠When the DC Power Cable (supplied) is connected to the AC Adaptor, the ...
is not always operating. A component can be failed and ... Photovoltaic modules are connected in series-parallel to .... point tracker (MPPT) and a transformer DC-to-AC. The ... a three-phase connection and 2 for a single-phased connection).
Entrée. 4.06 m². CH 2 & Pl. 10.30 m². Rgt. 1.43 m². Balcon. 11.39 m². Bains. 6.01 m². 17 Mar. 16.3/31.8. 17 Mar. 16.3/30.7. 321.87. S.S.. Séjour & Cuisine. Entrée.
CMOS power budget: â Dynamic power consumption: ⢠Charging and discharging of capacitors. â Short circuit currents: ⢠Short circuit path between power rails ...