Inverter Single (50Hz/R410A) 5RMA2-01A
Inverter Single-50Hz(R410A) Contents
Page
1. Models line up.........................................................................................4 2. Nomenclature..........................................................................................6 3. Features & Benefits................................................................................8 4. Specifications .......................................................................................19 5. Dimensions ...........................................................................................31 6. Wiring diagrams ...................................................................................43 7. Refrigerant cycle diagram....................................................................57 8. Capacity tables .....................................................................................62 9. Capacity coefficient factor...................................................................76 10. Operation range..................................................................................78 11. Air flow and temperature distributions(reference data)..................79 12. Sound level..........................................................................................82 12. Remote controller ...............................................................................88 14. Installation...........................................................................................91
2008 Product Data
1
Test condition of international standard
CLASSIFICATION
Indoor Cooling Capacity
Outdoor
Indoor Heating Capacity
Maximum
Outdoor
Indoor
Cooling Operating
Outdoor
Maximum
Indoor
Heating Operating Enclosure
Outdoor
Indoor
Sweat / Condensate
Outdoor
Disposal Freeze-up/
Indoor
Low Temperature Outdoor
KSC 9306
ISO 5151
ARI 210/240
AHAM
AS 1861.1
SSA 385
DB°C(°F)
27.0
27.0
26.7(80)
26.7(80)
27.0
29.0
WB°C(°F)
19.5
19.0
19.4(67)
19.4(67)
19.0
19.0
DB°C(°F)
35.0
35.0
35.0(95)
35.0(95)
35.0
46.0
WB°C(°F)
24.0
24.0
23.9(75)
23.9(75)
24.0
24.0
DB°C(°F)
20.0
20.0
21.1(70)
21.1(70)
20.0
21.0
WB°C(°F)
15.0
15.0
15.6(60)
15.6(60)
15.0
15.5
DB°C(°F)
7.0
7.0
8.3(47)
8.3(47)
7.0
7.0
WB°C(°F))
6.0
6.0
6.1(43)
6.1(43)
6.0
6.0
DB°C(°F)
32.0
32.0
26.7(80)
32.2(90)
32.0
29.0
WB°C(°F)
23.0
23.0
19.4(67)
22.8(73)
23.0
19.0
DB°C(°F)
43.0
43.0
46.1(115)
43.3(110)
43.0
54.0
WB°C(°F)
26.0
26.0
23.9(75)
25.6(78)
26.0
24.0
DB°C(°F)
27.0
27.0
26.7(80)
26.7(80)
-
-
WB°C(°F)
19.0
19.0
19.4(67)
22.8(73)
-
-
DB°C(°F)
21.0
24.0
23.9(75)
23.9(75)
-
-
WB°C(°F)
15.0
18.0
18.3(65)
18.3(65)
-
-
DB°C(°F)
27.0
27.0
26.7(80)
26.7(80)
27.0
27.0
WB°C(°F)
24.0
24.0
23.9(75)
23.9(75)
24.0
24.0
DB°C(°F)
27.0
27.0
26.7(80)
26.7(80)
27.0
27.0
WB°C(°F)
24.0
24.0
23.9(75)
23.9(75)
24.0
24.0
DB°C(°F)
21.0
21.0
19.4(67)
21.1(70)
21.0
21.0
WB°C(°F)
15.0
15.0
13.9(57)
15.6(60)
16.0
16.0
DB°C(°F)
21.0
21.0
19.4(67)
21.1(70)
21.0
21.0
WB°C(°F)
15.0
15.0
13.9(57)
15.6(60)
16.0
16.0
KS : Korea Standard ISO : International Standard Organization ARI : Airconditioning and Refrigeration Institute AHAM : Association of Home Appliance Manufacturers
2
2008 Product Data
AS : Australia Standard SSA : Saudi Arabian Standard
General Description
Split type of Air conditioners are known by the category name of Wall Mounted Type of units.These units can be easily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,it ensures a pleasant air conditioned environment. LG Offers various types of units to its customers to suit for the best application and requirement.The following are the important categories offered by LG : 1) General Wall Mounted Type Units : Units with Simplicity in design. 2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning. 3) Inverter Units : These units are capable of minimising the Power consumption with the unique inverter technology. Some of the Important Features of these units are listed below : 1) Providing Health to the Customers : By having the Filters such as Plasma Filter which is capable of removing the Micro Organisms up to 0.1 microns. 2) Long Term Money Saving : By providing Features such as Gold Fin, Auto Clean etc. to maintain the same performance for the years. 3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc. The Units are available with many standard and optional features which gives our Customers the free choice to select the unit of their own desire.For details refer to the Detailed specification followed after this description.
LG Electronics Inc. Air Conditioning Division
2008 Product Data
3
1. Models Line up 1.1 Indoor Unit kW (kBtu/h) Indoor Type
2.63(9)
3.51(12)
5.28(18)
7.03(24)
AS-W096E*H2 [C09AW* NE2]
AS-W126E*H2 [C12AW* NE2]
AS-W1868*H1 [C18AW* N81]
AS-W2468*H1 [C24AW* N81]
AS-W096U*H1 [C09AW* NU1]
AS-W126U*H1 [C12AW* NU1]
AS-W1863*H3 [C18AW* N33]
AS-W2463*H3 [C24AW* N33]
AS-W096F1G2 [A09AW1 NF2]
AS-W126F1G2 [A12AW1 NF2]
AS-W096F*G2 [A09AW* NF2]
AS-W126F*G2 [A12AW* NF2]
AS-W1865DH2 [S18AW N52]
AS-W2465DH2 [S24AW N52]
8.79(30)
10.55(36)
ART COOL Mirror *Mirror
*Silver
*Blue
ART COOL Mirror *Blue *Metal *White Wood *Mirror
ART COOL
ART COOL
Red
Gold
Silver
Wall Mounted Type
AS-W096ADR0 AS-W126ADR0 [S09AA NA0] [S12AA NA0] Wall Mounted Type
AS-W096E1G0 [S09AW1 NE0]
AS-W126E1G0 [S12AW1 NE0]
Wall Mounted Type
AS-W0964GG1 AS-W1264GG1 AS-W1865GG1 [S09AM N41G] [S12AM N41G] [S18AM N51G]
AS-W306DGM0 AS-W366DGM0 [S30AW ND0] [S36AW ND0]
* denotes the color or the picture used on the front grille of the unit (refer to the Nomenclature section)
4
2008 Product Data
1. Models Line up 1.2 Outdoor Unit AS-W0964GG1[S09AM N41G] AS-W096ADR0 [S09AA NA0] AS-W096E*H2[C09AW* NE2] AS-W096E1G0[S09AW1 NE0] AS-W096F1G2[A09AW1 NF2] AS-W096F*G2 [A09AW* NF2] AS-W096U*H1[C09AW* NU1]
Heat pump
No. of connectable indoor units Total capacity index of connectable indoor units Power supply
AS-W1264GG1[S12AM N41G] AS-W126ADR0 [S12AA NA0] AS-W126E1G0[S12AW1 NE0] AS-W126E*H2 [C12AW*NE2] AS-W126F1G2 [A12AW1 NF2] AS-W126F*G2 [A12AW* NF2] AS-W126U*H1[C12AW* NU1] Max.1
kW kBtu/h
2.64 9
3.52 12 1ø, 220-240V, 50Hz
Chassis
AS-W1865DH2[S18AW N52] AS-W1863*H3[C18AW* N33] AS-W1868*H1 [C18AW* N81] AS-W1865GG1[S18AM N51G] AS-W2463*H3[C24AW* N33]
Heat pump
No. of connectable indoor units Total capacity index of connectable indoor units Power supply
AS-W366DGM0[S36AW ND0]
Max.1 kW kBtu/h
5.28 18
10.55 36 1ø, 220-240V, 50Hz
Chassis
AS-W2465DH2[S24AW N52] AS-W2468*H1 [C24AW* N81]
Heat pump No. of connectable indoor units Total capacity index of connectable indoor units Power supply
AS-W306DGM0[S30AW ND0] Max.1
kW kBtu/h
7.03 24
8.79 30 1ø, 220-240V, 50Hz
Chassis
2008 Product Data
5
2. Nomenclature
Code
A
S
1
2
-
W
0
9
6
4
G
G
1
3
4
5
6
7
8
9
10
Type
Code of Model
Meaning
1
Production Center, Refrigerant
A~Z
L: Chang-won R22 A: Chang-won R410A
2 3
Product Type Cooling/Heating/Inverter
A~Z A~Z
4, 5
Capacity
0~9
S: Split Type Air Conditioner C: Cooling only H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P Cooling/Heating Capacity Ex. "09" → 9,000 Btu/h
6
Electric Range
1~9 A~Z
1: 115V/60Hz, 2: 220V/60Hz 3: 208-230V/60Hz 5: 200-220V/50Hz 6: 220-240V/50Hz 7: 110V, 50/60Hz
7
Chassis
A~Z
Name of Chassis
8
Look
A~Z
ART COOL models B : Blue C : Cherry W: White D : Wood M: Metal Q : Quran
K : Mecca R : Mirror
1 : The Kiss(SF chassis) 2 : The Sunset(SF chassis) 3 : London Bridge(SG chassis)
General Wall Mounted models D – Look ( Panel Type) G – Look ( Grille Type) Glory Look :- (a) F – Look (Blue color) (b) H – Look (Gold) (c) J – Look (Silver)
6
9, 10
Function
A~Z
11
Serial No.
1~9
2008 Product Data
A B C D E F G H I J K L M N P Q R S T U V W Y
Basic Basic+4Way Plasma Filter Plasma Filter+4 Way Tele+LCD Tele+LCD+Nano plasma+4Way NBF F+(A/changeove)+A/clean+Low A NBF F+(A/changeove)+A/clean+4way+Low A Tele+LED+4way Internet Plasma F+4Way+Oxygen generator NBF F+(A/changeove)+A/clean NBF F+(A/changeove)+A/clean+4way NBF F+(A/changeove)+A/clean+PTC NBF F+(A/changeove)+Autoclean+4way+PTC NBF F+(A/changeove)+A/clean+4way+Low A+PTC Negative ion+A/Clean (Nano)Plasma+Negative ion+A/Clean 4way+(Nano)Plasma F+Negative ion+A/Clean Nano Plasma F+4Way+(A/changeove)+A/clean+Oxygen generator 4way+(Nano)Plasma F+Negative ion+A/Clean+Oxygen generator Dry contact Basic + Low A
LG Model Development Serial No.
2. Nomenclature • Europe Model Number C
0
9
A
W
M
N
N
1 Development sequence Chassis For ART COOL type E : SE chassis F : SF chassis U : SU chassis 8 : S8 chassis For Wall mounted type D : SD chassis 4 : S4 chassis 5 : S5 chassis Indicator for unit type N : Indoor Color of the Panel (only ART COOL Models) M : Metal (Silver) R : Mirror (Black) B : Blue D : Wood W : White Type of Operation W : DC inverter Deluxe N : DC inverter Normal Type of Refrigerant A : R410A Cooling / Heating Capacity (kBtu/h) Model Type A : ART COOL Panel type C : ART COOL Mirror type S : Wall mounted type
2008 Product Data
7
3. Features & Benefits LG Air Conditioners are environment-friendly and future-oriented. LG air conditioners are environment-friendly and future-oriented. To reduce freon gas, a prime ozone destroyer, we adopted an alternative refrigerant R-410A, and neo plasma air-purifying system for powerful sterilization for health-conscious customers. Also, ARTCOOL series with outstanding designs have received International Forum Design Award and Reddot Design Award. These air-conditioners have improved air flow innovatively to realize world’s lowest noise, and provide a more pleasant and convenient indoor environment.
Environmental concern 2008 As the concern for environment increases day by day, EC Directive made it a regulation to put an indication on all air conditioning products. With the information regarding energy-saving, customers will easily understand products considering the environment. Customers will have to purchase the products considering the energy label to meet their needs. Energy label shows the energy consumption of the unit classified with 7 different colors.
Energy Efficiency Class of The Unit In Cooling Mode :
Energy Efficiency Class of The Unit In Heating Mode :
8
2008 Product Data
3. Features & Benefits
DC Inverter? You may have heard the excitement about Inverter technology, LG Inverters are the pinnacle of energy efficiency due to the innovative operation. Rather than using a constant speed compressor, the LG Inverter system uses a variable speed compressor, which means the Cooling or Heating capacity of the Air Conditioning can be varied to suit Indoor conditions. This makes the LG Inverter Units more economical & efficient to operate, produce less noise than standard counterparts and contain most superior features on the market. All LG Inverter units have the major benefits including premium features like
Economical
■ Energy Saving
■ Recouping the Initial Investment Cost
Unlike ordinary Conventional air conditioners, inverter air conditioners can control the speed of compressors to adjust cooling and heating.
Though the initial purchase price is a little higher, in case you use an inverter air conditioner in the long term, you can reduce electricity cost to save on the whole investment and management costs.
When indoor temperatures reach your desired levels, inverter air conditioners can operate their compressors at low speeds and maintain desired temperatures, thus saving you electricity cost by about 44% compared to conventional.
Money
Inverter
Energy Saving
Conventional
Save 44% 1Year Year
Conventional Inverter
Energy Saving! Low Noise! Powerful Cooling & Heating!
2008 Product Data
9
3. Features & Benefits Strong
Capable
■ Powerful Cooling & Heating
■ Powerful Heating Capacity (Chilly Area Available)
You can change the power by changing the compressor frequency. Operational power with a greater scope - When you return home from outside, in case you start the air conditioner to heat or cool the room, you can speed up the compressor, enhance the power and then operate it. Also, when indoor temperature reach your desired levels, you can reduce the speed of the compressor and lower the power. Thus, the product's operational power has a greater range from low to high levels.
Energy Saving Low Noise
Powerful Cooling & Heating
High Efficiency Low Cost Light Weight
Provides the greatest heating performance in cold areas - When outdoor temperatures fall to as low as -10°, you can faster increase the speed of the compressor, and simultaneously raise the quantity of refrigerant using the electronic expansion valve, thus further increasing the heating performance compared to ordinary conventional model. You can heat the room even in cold areas using the air conditioner.
Outdoor Temp.(˚C) Max
138%(H)
Energy Saving
138%(H) 40°C (Outlet)
100%
100%
Conventional
12%
12% Inverter (min)
Min
T1
T1 : 35% up Inverter (max) -20
■ Quick Cooling & Heating Compared to conventional air conditioners, inverter air conditioners can operate their compressors faster, thus giving them powerful performance. Therefore, on returning home from outside during hot summer days, you can speed up the compressor to enhance the performance and cool the room. In case outdoor temperatures are low in winter, inverters operate more powerfully than conventional, thus heating the room faster.
Temp.
Conventional Target Temp.
Inverter
50% Time of Convention
10
2008 Product Data
Time
-15
-10
-5
0
5
7
15
Conventional Inverter
3. Features & Benefits
NEO-Plasma Air Purifying System LG Electronics’ unique neo-plasma air purifying system, equipped with 12-level bio-enzyme filters, has further enhanced its sterilization power. While air passes each level of filters, the system can more powerfully eliminate household's fine dust and molds, ordinary odor, food smell, and cigar smoke, as well as can destroy bacteria's cell walls to completely kill them. It has a strong sterilization power.
Have you ever experienced these symptoms? Though the industrial development has enhanced people's quality of life and their satisfaction in living, it is increasingly creating various kinds of pollution, hazardous substances and viruses. In particular, substances (household tick dust, molds, etc.) that create allergies give rise to respiratory diseases and atopic diseases. Harmful gases, the prime cause of 'new house syndromes,’ create chronic headache.
Whenever seasons change, You have runny nose
Asthma, and Continuous coughs.
The skin is itchy without knowing reasons,
Frequent headache, and chronic fatigue...
You scratch it again
1
First antibiotic
Allergy
2
Fishy smell
Foot stink
3
Animal smell
Odor of food garbage
Chemical substance
4
Influenza
Virus
Mite
5
Micro dust
Deodorize
Mold Smoke
Allergy Mold
Mite
Big dust
Odor of construction ingredient
Blanket dust Odor of food garbage
Chemical substance
Pollutant
2008 Product Data
11
3. Features & Benefits Plasma Filter
Nano Bio Fusion Filter Nano bio fusion filters allow their nano-size bio enzymes to directly penetrate through cell walls of bacteria and allergen to decompose
The PLASMA Air Purifying System developed uniquely by LG not only removes microscopic contaminants and dust, but also removes house mites, pollen, and pet fur to prevent allergic diseases like asthma.
its cell nuclei and kill them.While conventional methods merely inactivate bacteria or destroy external cell walls, this innovative sterilization method can completely decompose bacteria's cell nuclei and kill them.
5
Bacteria, Virus Bio Active Site Nano Particle
Nano Particle
Nano Particle
Active State
Bacteria Selective Capture
Bacteriolysis
Nano Particle
Polluted Air Regeneration (Active State)
Distinctions from Conventional Filters Conventional
4 Simply inactivate bacteria
Destroy bacteria but allow part of them to survive
Nano Bio Fusion Filter
The bio enzyme destroys cell walls and nuclei of bacteria and allergens, thus completely kills bacteria
3
Nano-size carbon filters catch fine odorous particles again, and doubly and completely remove odors from the household, thus offering a pleasant environment.
What is Nano Carbon Ball?
2
Nano Carbon Filter
Nano(1/1Bil) ball structure,consisted of Nano carbon, is adopted as deodorizing material first in the world
200~500nm
Kitasato Research Center of Environmental Sciences - Inactivating Germs Test Result 99.9% Performance (No. 16_0113_1,2,3)
Clean Air
Japan Food Research Laboratories - Inactivating Germs Test Result 99.9% Performance (No. 104093863-001,2,3,4,5) - Killing Virus (No. 204031236-001,2,3) Japan Spinners Inspecting Foundation (No. 624217, 019355-13) - NCB Deodorizing 4 Type Test Result 78%~98% Security
Pre Filter The antibacterial prefilters primarily remove large dusts, molds, and quilt dusts.
12
2008 Product Data
Triple Filter
FITI Korea Consumer Science Center (No. 513104-195-A-01) - Killing bacteria, fungi Test Result 99.9% Security ITS(International Technical Standard Center) (No. IL26937-A,B) - Inactivating bacteria Test Result 99.9% Security
The triple filters consist of a various organic-compound filter to eliminate displeasure and pain in the eyes and necks with various organic compounds. It also has a formaldehyde filter to cut off formaldehyde, a prime cause of new-house syndromes, and prevents symptoms such as dermatitis, vomiting and pneumonia. And lastly, it has a filter to remove ordinary odors that are causes of migraine and chronic fatigues.
3. Features & Benefits Healthy Dehumidification LG Wall Mounted Split models feature a Dehumidification mode to remove uncomfortable humidity from the room without over cooling.
Indoor Temperature Distribution Chart
Conventional Since the surrounding temperature is measured after the air from the unit is widely distributed, an accurate assessment of the air is not possible.
Healthy Dehumidification By increasing the Vane Angle, a better assessment of the actual temperature is possible to prevent over cooling.
Auto Clean The main cause of air conditioner's odor is molds that breed in the heatexchanger. If you turn off the air conditioner as it is, molds and bacteria will breed in the wet heat exchanger. The automatic cleaning function will dry the wet heat exchanger to prevent molds and bacteria from breeding. It will eliminate air conditioner's odor and save you from frequent cleaning efforts.
When you press "Auto Clean”, Auto clean starts after cooling operation.
In 30 minutes, Auto clean" dries the inner part of Air conditioner.
1STEP : Dries the evaporator with super-weak, lownoise air blowing, and removes remaining moisture.
2STEP : Fundamentally removes the sources of molds once again through the neo plasma system.
2008 Product Data
13
3. Features & Benefit Low Level Noise & Vibration In the case of the inverter air conditioner’s outdoor equipment, when indoor temperatures reach your desired levels, you can lower the speed of the compressor operating inside the outdoor equipment, thus further reducing noise compared to ordinary conventional air conditioners. Also, the indoor equipment, which adopts a BLDC motor, can achieve even quieter and industry’s lowest-level noise, compared to existing conventional air conditioner. Since even the outdoor equipment is quiet, though the air conditioner is hung on the wall, it has subdued noise, thus not disturbing your neighbors. It is perfect for sleeping, studying, and a quiet indoor ambience.
Indoor
Outdoor
20dB
45dB
Low Noise Compressor [Indoor equipment] 1. Uses low-noise BLDC motor and fan 2. Shuts off noise with an all-side panel design
[Outdoor equipment] 1. Low-noise inverter compressor and low-noise fan 2. Designed for optimizing compressor vibration
Anti Corrosion Gold Fin™ LG ’s Outdoor Heat Exchanger is coated with a golden anticorrosive epoxy treatment on the aluminum coil to minimized corrosion. This maintains heat transfer properties of the coil for an extended time where as non-Gold Fin coils progressively lose efficiency due to surface corrosion. Standard on every LG air conditioner, this assists in areas suffering from pollution or near the ocean where the unit may subjected to higher levels of salt. Salt Spray Test for 15 Days
After 15 Days
LG Gold Fin™ Anti Corrosion
Gold Coated Aluminum
After 15 Days
Uncoated Aluminum
• Gold Fin is long lasting, durable and makes the Outdoor Unit look prestigious.
14
2008 Product Data
Conventional Starting to corrode
3. Features & Benefits Optimized Cooling & Heating Air Flow LG Electronics' air conditioner, which adopts the twin air vanes, blows winds horizontally far away in the cooling mode to prevent direct blowing. And, in the heating mode, the air conditioner pushes winds downwards to provide warm air evenly, thus offering pleasant air. Heating mode
Cooling mode
New Chaos Swing
Cooling mode
0.5hr
1hr
2hr
The most comfortable airflow for the human body can be found in nature. After analysis,LG has applied the scientific Chaos theory to its air conditioners to effectively reproduce a natural breeze. The Chaos technology recreates the flow of natural air by controlling the angle speed and movement of the air vane. It also minimizes the temperature difference between high and low areas in the room,creating a more comfortably conditioned environment.
Heating mode
0.5hr
1hr
2hr
LG
Co., A
Co., B
Even & Fast Air flow
It swings with random angle speed (0ms~12ms) to reproduce a natural breeze
LG Electronics' air conditioner improves the difference between high and low indoor temperatures . It allows you to reach your desired temperatures even faster.
2008 Product Data
15
3. Features & Benefits Indoor Temperature Distribution Chart
4 Way Auto Swing LG Air Conditioning units can now automatically distribute the air 4-ways.
This effectively eliminates hot and cold patches, keeping the room at a more stable temperature. Chaos Swing
Auto Swing
Chaos Swing Effect
Jet Cool TM
ARTCOOL_MIRROR TYPE
The Jet cool function allows quick cooling. In this mode, strong, cool air is blown at high speed for 30 minutes, until the room temperature reaches 18˚C.
A little interior accent for the modern you. The romantic pastel colors, subdued luster,modern texture and the super slim design of LG ARTCOOL Mirror are the answers to your unique mood and personality.
ARTCOOL_PANEL TYPE LG's unique frame-style of ARTCOOL panel type. Its super-slim and sensory design satisfies your sense.
10m It can cool the spot ten meters away in 3 minutes.
16
2008 Product Data
3. Features & Benefits Auto Changeover
Low Ambient
With heat pump model,cooling and heating operation is changed automatically on the base of setting temp.
Cools the room as is necessary, even in winter. - In case you hold a party indoors in winter, you need to operate equipment in the computer server room for long hours, or you cannot open windows for the security's sake, you can cool the room using the Inverter air conditioner. Under such circumstances, ordinary conventional air conditioners may have heat exchangers in indoor equipment frozen, thus not properly functioning to cool the room. However, in the case of inverter air conditioners, you can adjust the speed of compressors and outdoor equipment's fans to prevent heat exchangers in indoor equipment from being frozen, thus cooling the room more easily.
• Initial Setting Temp:18˚C Memorize final setting temp.
Auto Restart Function
Hot Start Function
In case of a sudden power failure, It automatically sets the A/C to settings before the power failure when power returns.
During starting of the unit in the heating mode it prevents cold air blowing from the unit. It starts the indoor fan only after indoor unit pipe temperature reaches a preset value (28˚C).
Sleep Mode Auto Control
When indoor unit pipe temperature reaches 28˚C, then for initial 1 minute the indoor fan runs at a low speed and after that at the setting speed.
it automatically programs the Air Conditioning Unit to turn off, controls the fan speed and adjusts the set temperature for a more comfortable sleep.
With one touch of the Sleep mode button,
2008 Product Data
17
3. Features & Benefits Modern & Luxury Design
Gallery In My Room
Its premium designs match well with any part of the household.
Your room will shine chicly with a famous painting or a beautiful photo (showcased in the product). LG ARTCOOL will convert your room into a gallery. Do you like Western paintings, Oriental paintings, or photos? The product features your desired style of famous paintings.
Klumt, Gustav(1862-1918) The Kiss-Der Kuss EX)LS-H126F1L0
Courbet, Gustav(1817-1877) Lake Geneva at Sunset EX)LS-H126F2L0
Ez-Replaceable Color Panel
Digital Air Flow Control
The ARTCOOL chameleon panel enables you to change the air conditioner color according to background colors, the first of its kind in the world. When you want to change interior designs (wallpaper colors, furniture, etc.) or you want to change the air conditioner designs after you are bored with them. You can only change the panel.
You feel more comfortable and convenient by controlling air flow.
Normal
Jet Cool
Sleep Mode
Fast & Even Widely
Speedy & Powerful
Indirectly & Softly
3 Dimensional Air Flow Designed like a work of art, and the new concept of 3 dimensional air flow. It gives even cooling as well as quick cooling from front and bothsides making the space evenly cool.
Ultra Thin Technology mixed with sense of art result in the super slim design which is of 129mm depth.
The slimmest in the world!!!
129mm 18
2008 Product Data
4. Specifications
Inverter single
Inverter Single, ART COOL Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
AS-W096ADR0 [S09AA NA0] 0.89~2.64~3.69 3,070~9,000~12,620 0.89~3.60~5.00 3,070~12,300~17,060 650 / 870 3/4 3/4 4.04 13.8 4.1 1/220-240/50 98.7 8.5(300) 29(1,024) 1.2 31 / 27 / 22 45 R410A,1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 925*295*189 36.4*11.6*7.4 770*545*245 30.3*21.5*9.6 11.6(25.6) 34(74.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SA+UL Thermistor O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24hr, On/Off O O 2 O O O O Smart Clean
AS-W096E*H2[C09AW* NE2] 0.89~2.64~3.69 3,070~9,000~12,620 0.89~3.60~5.00 3,070~12,300~17,060 650 / 870 3/4 3/4 4.1 13.9 4.1 1 / 220-240 / 50 94.2 10.5(371) 27.0(954) 1.2 31 / 27 / 22 45 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 915*282*165 36.0*11.1*6.5 770*545*245 30.3*21.5*9.6 10(22.1) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SE + UL Thermistor Neo O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
2008 Product Data
19
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) 3 m /min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W096F1G2[A09AW1 NF2] 1.30~2.70~3.50 4,436~9,210~11,942 1.30~3.50~4.20 4,436~11,940~14,330 830 / 960 3.8 / 4.4 4.5 / 5.2 3.3 11.1 3.7 1 / 220-240 / 50 95.0 8(283) 26(918) 1.2 35 / 29 / 25 / 22 48 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Tubo Fan 24 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 770*545*245 30.3*21.5*9.6 770*540*245 30.3*21.3*9.6 15(33) 34(74.9) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SF + UL Thermistor Nano O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
20
2008 Product Data
AS-W096F*G2 [A09AW* NF2] 1.30~2.70~3.50 4,436~9,210~11,942 1.30~3.50~4.20 4,436~11,940~14,330 830 / 960 3.8 / 4.4 4.5 / 5.2 3.3 11.1 3.7 1 / 220-240 / 50 95.0 8(283) 26(918) 1.2 35 / 29 / 25 / 22 48 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Tubo Fan 24 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 770*545*245 30.3*21.5*9.6 770*540*245 30.3*21.3*9.6 15(33) 34(74.9) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SF + UL Thermistor Nano O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) 3 m /min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W096U*H1[C09AW* NU1] 0.65 ~ 2.64 ~ 3.25 2,200 ~ 9,000 ~ 11,080 0.90 ~ 3.17 ~ 3.87 1,800 ~ 10,800 ~ 13,950 750 / 870 3.5 / 4.0 3.5 / 4.0 3.52 12 3.64 1 / 220 ~ 240 / 50 93.17 9(318) 26(918) 1.5 34/32/28 48 R410A, 720(25.4) 20(0.22) Rotary 5RS102XAA Brushless DC motor RB68A 320 CS-7L 115 Cross Flow Fan 9.5 Propeller AC Induction 43 15 3*1.0 4*1.5(Including Earth) 6.35(1/4) 9.52(3/8) 21.5 /16(0.85 / 0.63) 1,030*290*153 40.6*11.4*6.0 770*545*245 30.3*21.5*9.6 9.5(20.9) 31(68.3) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SU + UL Thermistor Nano O O O 3/4/3 Auto Manual Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
AS-W126ADR0 [S12AA NA0] 0.89~3.51~4.04 3,070~12,000~13,800 0.89~4,57~5,49 3,070~15,600~18,720 1,090 / 1,260 4.8 / 5.7 4.8 / 5.7 3.22 11.01 3.63 1 / 220-240 / 50 98.7 9.5(335) 29(1,024) 1.3 36 / 27 / 22 45 R410A, 1000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 BLDC 20.0 BLDC BLDC 43 15 3*1.0 4*1.5(Including Earth) 6.35(1/4) 9.52(3/8) 21.5 /16(0.85 / 0.63) 925*295*189 36.4*11.6*7.4 770*545*245 30.3*21.5*9.6 11.6(25.6) 34(74.9) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SA+UL Thermistor O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24hr, On/Off O O 2 O O O O Smart Clean
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
2008 Product Data
21
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W126E*H2 [C12AW*NE2] 0.89~3.51~4.04 3,070~12,000~13,800 0.89~4.57~5.48 3,070~15,600~18,720 1,090 / 1,260 4.8 / 5.7 4.8 / 5.7 3.2 11.0 3.6 1/220-240/50 98.7 10.5(371) 27(954) 1.3 37 / 27 / 22 / 20 45 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 915*282*165 36.0*11.1*6.5 770*545*245 30.3*21.5*9.6 10(22.1) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SE + UL Thermistor Nano O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
22
2008 Product Data
AS-W126F1G2 [A12AW1 NF2] 1.30~3.50~4.00 4,436~11,940~13,648 1.30~4.20~5.00 4,436~14,330~17,060 1,090 / 1,160 4.9 / 5.2 5.7 / 6.9 3.2 11.0 3.6 1 / 220-240 / 50 96.7 9.5(336) 34(1,200) 1.5 39 / 32 / 25 / 23 48 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Tubo Fan 24 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 600*600*145 23.6*23.6*5.7 770*545*245 30.3*21.5*9.6 15(33) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SF + UL Thermistor Nano O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W126F*G2 [A12AW* NF2] 1.30~3.50~4.00 4,436~11,940~13,648 1.30~4.20~5.00 4,436~14,330~17,060 1,090 / 1,160 4.9 / 5.2 5.7 / 6.9 3.2 11.00 3.60 1 / 220-240 / 50 96.7 9.5(336) 34(1,200) 1.5 39 / 32 / 25 / 23 48 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Tubo Fan 24 Propeller BLDC 43 15 3*1.0 4*1.5 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 600*600*145 23.6*23.6*5.7 770*545*245 30.3*21.5*9.6 15(33.1) 32(70.5) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SF + UL Thermistor Nano O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
AS-W126U*H1[C12AW* NU1] 0.82 ~ 3.52 ~ 3.87 2,800 ~ 12,000 ~ 13,200 1.29 ~ 3.96 ~ 4.35 4,400 ~ 13,500 ~ 14,850 1,090 / 1,410 5.0 / 6.2 5.0 / 6.2 3.23 11.01 2.81 1 / 220 ~ 240 / 50 94.78 9.5(335) 26(918) 1.5 35/33/28 48 R410A, 810(28.6) 20(0.22) Rotary 5RS102XAA Brushless DC motor RB68A 320 CS-7L 115 Cross Flow Fan 9.5 Propeller AC Induction 43 15 3*1.5 4*1.5(Including Earth) 6.35(1/4) 12.7(1/2) 21.5 /16(0.85 / 0.63) 1,030*290*153 40.6*11.4*6.0 770*545*245 30.3*21.5*9.6 9.5(20.9) 31(68.3) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SU + UL Thermistor Nano O O O 3/4/3 Auto Manual Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
2008 Product Data
23
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W1863*H3[C18AW* N33] 1.61~5.28~5.83 5,500~18,000~19,900 1.67~6.07~6.73 5,700~20,700~23,000 1,630 / 1,890 7.5 / 8.5 7.5 / 8.5 3.2 11.0 3.2 1,220-240,50 94.5 14.15(499) 42(1,483) 5.2 43 / - /3 7 57 R410A, 1,200(42.3) 20(0.22) E-SCROLL 5CS130XCA03 Brushless DC Motor RB68A 480 CS-7L N120 Cross Flow Fan 25.6 Propeller AC Induction 61 20 3*2.5 4*2.5(Including Earth) 6.35(1/4) 12.7(1/2) 21.5 /16(0.85 / 0.63) 1,170*315*173 46*12.4*6.8 870*655*320 34.3*25.8*12.6 13(28.7) 64(141.1) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) S3 + UE Thermistor Neo O O O 3/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
24
2008 Product Data
AS-W1868*H1 [C18AW* N81] 1.76 ~ 5.28 ~ 5.80 6,000 ~ 18,000 ~ 19,800 1.40 ~ 6.07 ~ 6.65 4,800 ~ 20,700 ~ 22,700 1,640 / 1,770 7.3 / 8.3 7.3 / 8.3 3.2 11.0 3.43 1 / 220~240 / 50 98.3 16(565) 42(1,483) 2.1 42 / 39 / 36 54 R410A, 1,200(42.3) 20(0.22) E-SCROLL 5CS130XCC03 BLDC RB68A 480 CS-7L N120 Cross Flow Fan 20 Propeller AC Induction 65 20 3*1.5 4*1.5(Including Earth) 6.35(1/4) 12.7(1/2) 21.5 / 16.0(0.85 / 0.63) 1,107*299*200 43.6*11.8*7.9 870*655*320 34.3*25.8*12.6 14.1(31.1) 46(101.4) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) S8 + UE Thermistor O O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O -
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W2463*H3[C24AW* N33] 4.43~7.03~7.73 15120~24000~26400 4.19~7.95~8.35 14,300~27,100~28,500 2,600 / 2,800 11.5 / 12.5 11.5 / 12.5 2.7 9.23 2.84 1,220-240,50 98.3 16.64(587) 45(1,587) 5.2 45 / - / 37 / 36 57 R410A, 1,490(52) 30(0.32) Rotary TNB220FLBM1 Brushless DC Motor MEL 56 670 Cross Flow Fan 20 Propeller BLDC 85.3 30 3*2.5 4*2.5 (Including Earth) 9.52(3/8) 15.88(5/8) 21.5 / 16.0(0.85 / 0.63) 1,170*315*173 46*12.4*6.8 870*655*320 34.3*25.8*12.6 13(28.7) 64(141.1) -5~43(23~109.4) -10~24(14.0~75.2) 30(98) 15(49) S3 + UE Thermistor nano O O 3/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
AS-W2468*H1 [C24AW* N81] 3.87 ~ 7.03 ~ 7.74 13,200 ~ 24,000 ~ 26,400 3.37 ~ 8.44 ~ 8.88 11,500 ~ 28,800 ~ 30,300 2,450 / 2,900 11.0 / 13.0 11.0 / 13.0 2.9 9.8 2.9 1 / 220~240 / 50 96.8 20.3(717) 58(2,048) 2.7 43 / 40 / 36 / 34 55 R410/1,800(63) 30(0.32) Rotary(Non Tropical) 5KD240XCA21 BLDC FV50S 900 CS-7L N115 Cross Flow Fan 24 Propeller AC Induction 76.5 30 3*2.5 4*2.5 (Including Earth) 9.52(3/8) 15.88(5/8) 21.5 / 16.0(0.85 / 0.63) 1,107*299*200 43.6*11.8*7.9 870*808*320 34.3*31.8*12.6 14.1(31.1) 60(132) -5~43(23~109.4) -10~24(14.0~75.2) 30(98) 15(49) S8 + UE1 Thermistor O O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
2008 Product Data
25
4. Specifications
Inverter single
Inverter Single, General Wall Mounted Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
AS-W096E1G0[S09AW NE0] 0.89~2.64~3.69 3,070~9,000~12,620 0.89~3.60~5.00 3,070~12,300~17,060 650 / 870 3/4 3/4 4.1 13.9 4.1 1,220-240,50 94.2 8.5(300) 29(1,024) 0.6 31 / 27 / 22 / 20 45 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller BLDC 43 15 3*1.0 4*1.5(Including Earth) 6.35(1/4) 9.52(3/8) 21.5 /16(0.85 / 0.63) 915*282*165 36.0*11.1*6.5 770*545*245 30.3*21.5*9.6 8(17.6) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SE + UL Thermistor Neo O O O 3/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
26
2008 Product Data
AS-W0964GG1[S09AM N41G] 0.90 ~ 2.64 ~ 3.46 3,070 ~ 9,000 ~ 11,800 0.90 ~ 3.17 ~ 3.87 3,070 ~ 10,800 ~ 13,200 820 / 930 3.8 / 4.3 3.8 / 4.3 3.2 11.0 3.4 1 / 220 ~ 240 / 50 93.8 9.5(335) 26(918) 1.3 32 / 28 / 25 45 R410A, 630(22.2) 20(0.22) Rotary 5RS102XAA21 Brushless DC motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller AC Induction 29 15 3*1.0 4*1.0 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 840*270*153 33.1*10.6*6.0 770*545*245 30.3*21.3*9.7 7.5(16.5) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) S4 + UL Thermistor Neo O O O 3/4/4 Auto Manual Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O -
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W126E1G0[S12AW* NE0] 0.89~3.52~4.04 3,070~12,000~13,800 0.89~4.57~5.48 3,070~15,600~18,720 1,090 / 1,260 4.8 / 5.7 4.8 / 5.7 3.2 11.0 3.63 1 / 220 ~ 240 / 50 98.7 9.5(335) 29(1,024) 1.3 37 / 27 / 22 / 20 45 R410A, 1,000(35.3) 20(0.22) Rotary 5RS102XAA21 Brushless DC Motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller BLDC 43 15 3*1.0 4*1.5(Including Earth) 6.35(1/4) 9.52(3/8) 21.5 /16(0.85 / 0.63) 915*282*165 36.0*11.1*6.5 770*545*245 30.3*21.5*9.6 8(17.64) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) SE + UL Thermistor Nano O O O 3/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O(Logic) -
AS-W1264GG1[S12AM N41G] 0.90 ~ 3.52 ~4.04 3,070 ~ 12,000 ~ 13,800 0.90 ~ 4.00 ~ 4.86 3,070 ~ 13,650 ~ 16,600 1,090 / 1,170 5.0 / 5.3 5.0 / 5.3 3.2 11.0 3.4 1 / 220 ~ 240 / 50 94.8 10.8(381) 26(918) 1.5 38 / 30 / 25 45 R410A, 940(33.2) 20(0.22) Rotary 5RS102XAA21 Brushless DC motor FV50S 320 CS-7L 115 Cross Flow Fan 20 Propeller AC Induction 29 15 3*1.0 4*1.0 (Including Earth) 6.35(1/4) 9.52(3/8) 21.5 / 16.0(0.85 / 0.63) 840*270*153 33.1*10.6*6.0 770*545*245 30.3*21.3*9.7 7.5(16.5) 32(70.6) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) S4 + UL Thermistor Neo O O O 3/4/4 Auto Manual Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
2008 Product Data
27
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W1865DH2[S18AW N52] 1.76~5.28~5.80 6,000~18,000~19,800 1.41~6.07~6.65 4,800~20,700~22,700 1,640 / 1,770 7.3 / 8.3 7.3 / 8.3 3.2 11.0 3.4 1 / 220-240 / 50 98.8 16(565) 42(1,483) 2.1 42 / 39 / 36 55 R410A, 1,200(40.8) 20(0.22) E-SCROLL 5CS130XCC03 Brushless DC Motor RB68A 480 CS-7L N120 Cross Flow Fan 20 Propeller AC Induction 65 15 3*1.5 4*1.5 (Including Earth) 6.35(1/4) 12.7(1/2) 21.5 / 16.0(0.85 / 0.63) 1,090*300*180 42.9*11.8*7.1 870*655*320 34.3*25.8*12.6 13(28.7) 46(101.4) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) S5 + UE Thermistor Nano O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24hr, On/Off O O 2 O O O O(Logic) -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
28
2008 Product Data
AS-W1865GG1[S18AM N51G] 1.78~5.28 ~ 5.80 6,000 ~ 18,000 ~ 19,800 1.40 ~5.80 ~ 6.65 4,800 ~ 19,790 ~ 22,700 1,730 / 1,800 8.0 / 8.3 8.0 / 8.3 3.1 10.4 3.2 1 / 220 ~ 240 / 50 94.0 13.0(459) 42(1,483) 2.1 43 / 40 / 37 56 R410A 1,200(40.8) 20(0.22) E-SCROLL 5CS130XCA Brushless DC motor RB68A 480 CS-7L N120 Cross Flow Fan 24 Propeller AC Induction 85.3 15 3*1.5 4*1.5(Including Earth) 6.35(1/4) 12.7(1/2) 21.5 / 16.0(0.85 / 0.63) 1,090*300*180 42.9*11.8*7.1 870*655*320 34.3*25.8*12.6 13(28.7) 46(101.4) -5~43(23~109.4) -10~24(14.0~75.2) 15(49) 7(23) S5 + UE Thermistor Neo O O O 3/ 4 / 4 Auto Manual Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 2 O O O O -
4. Specifications Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge g/m(oz/ft) Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose(O.D/ I.D.) Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) m3/min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Inverter single
AS-W2465DH2[S24AW N52] 3.87~7.03~7.74 13,200~24,000~26,400 3.37~8.08~8.88 11,500~27,570~30,300 2,500 / 2,880 11.0 / 13.0 11.0 / 13.0 2.8 9.6 2.8 1 / 220-240 / 50 96.8 18.0(636) 58(2,048) 3.2 44 / 41 / 37 56 R410A, 1,800(63.5) 30(0.32) Rotary 5KD240XCA21 Brushless DC Motor FV50S 900 CS-7LN115 Cross Flow Fan 20 Propeller AC Induction 76.5 30 3*2.5 4*2.5(Including Earth) 9.52(3/8) 15.88(5/8) 21.5 / 16.0 (0.85 / 0.63) 1,090*300*178 42.9*11.8*7.1 870*808*320 34.25*31.5*12.6 13(28.7) 60(132.3) -5~43(23~109.4) -10~24(14.0~75.2) 30(98) 15(49) S5 + UE1 Thermistor O O O O 3/4/4 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24hr, On/Off O O 2 O O O O(Logic) -
AS-W306DGM0[S30AW SD0] 3.6 ~ 8.0 ~ 8.8 12,283 ~ 27,296 ~ 30,026 5.3 ~ 9.6 ~ 10.2 18,084 ~ 32,775 ~ 34,802 2,650 / 3,180 12.0 / 14.5 12.0 / 14.5 3.0 10.3 3.0 1 / 220 ~ 240 / 50 97 21(350) 58(2,048) 3.5 46 / 43 / 39 54 R410A, 1,800(63.3)(at 10m) 30(0.32) Rotary 5KD240XAE21 Brushless DC motor FV50S 900 CS-7L 115 Cross Flow Fan 70 Propeller Brushless DC motor 80 25 3*2.5 4*0.75 (Including Earth) 6.35(1/4) 15.88(5/8) 21.5 / 16.0(0.85 / 0.63) 1,209*346*205 47.6*13.6*8.1 870*808*320 34.3*31.8*12.6 18(39.7) 60(132.3) -5~43(23~109.4) -10~24(14.0~75.2) 50(164) 30(98.4) SD + UE1 Thermistor Neo O O O 3/4/3 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 3 O O O O -
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
2008 Product Data
29
4. Specifications
Models Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER COP Power Supply Power Factor Air Flow Rate
Cooling/Heating Cooling/Heating Cooling/Heating
Indoor,Max Outdoor,Max
Moisture Removal Sound Level
Indoor,H/M/L Outdoor,Max Refrigerant & Charge (at 7.5 m) Additional Refrigerant charge Compressor Type Model Motor Type Oil Type Oil Charge O.L.P. name Fan(Indoor) Type Motor Output Fan(Outdoor) Type Motor Type Motor Output Circuit Breaker* Power Supply Cable Power and Transmission Cable No.*mm2 Piping Connections Liquid Side Gas Side Drain Hose O.D / I.D Dimensions Indoor (W*H*D) Outdoor (W*H*D) Net Weight Operation Range Max. Piping Length Max. Elevation Difference Tool Code(Chassis) Functions
Indoor Outdoor Cooling(Outdoor) Heating(Outdoor)
Unit kW Btu/h. kW Btu/h. W A A W/W Btu/h.W W/W Ø / V / Hz % m3/min(CFM) 3 m /min(CFM) l/h. dB(A)±3 dB(A)±3 g(oz) g/m(oz/ft)
cc
W
W A No.*mm2 No.*mm2 mm(in) mm(in) mm(in) mm inch mm inch kg(lbs) kg(lbs) °C(°F) °C(°F) m(ft) m(ft)
Indoor + Outdoor Temperature Control Plasma Filter Prefilter(washable/anti-fungus) Auto Clean CHAOS Wind(Auto Wind) Steps, Fan/Cool/Heat Airflow Direction Control(up & Down) Airflow Direction Control(left & right) Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation (Micom Control) Auto Changeover (Micom Control) Self Diagnosis Timer Sleep Operation Soft Dry Operation Restart Delay(minute) Deice Control(Defrost) Hot Start Jet Cool Low Ambient Operation Special Function
Note : O : Applie, X : Not applied, – : No relation • Filters are optional in some specific areas. • For Circuit Breaker Rating, please conform to local standards whenever necessary.
30
2008 Product Data
Inverter single
AS-W366DGM0[S36AW SD0] 4.0 ~ 9.0 ~ 9.8 13,648 ~ 30,708 ~ 33,438 5.6 ~ 10.4 ~ 11.0 19,107 ~ 35,485 ~ 37,532 2,980 / 3,450 13.6 / 16.5 13.6 / 16.5 3.2 10.3 3.0 1 / 220 ~ 240 / 50 97 25(416) 68(1133) 4.2 47 / 44 / 41 58 R410A, 2,200(77.6) 35(0.38) Rotary 5JD420XAD22 Brushless DC motor FV50S 1,300 CS-7L 115 Cross Flow Fan 75 Propeller Brushless DC motor 100 25 3*2.5 4*0.75 (Including Earth) 6.35(1/4) 15.88(5/8) 21.5 / 16.0(0.85 / 0.63) 1,209*346*205 47.6*13.6*8.1 870*1,060*320 34.3*41.7*12.6 19(41.9) 75(165.3) -10 ~ 43 (14 ~ 109.4) -15 ~ 24(5 ~ 75.2) 50(164) 30(98.4) SD + UE2 Thermistor Neo O O O 3/4/3 Auto Auto Wireless LCD 18°C ~ 30°C 16°C ~ 30°C O O 24h, On/Off O O 3 O O O O -
5. Dimensional drawings
Indoor units
5.1 Indoor Units
2008 Product Data
31
5. Dimensional drawings
32
2008 Product Data
Indoor units
5. Dimensional drawings
Indoor units
2008 Product Data
33
5. Dimensional drawings
Indoor units
296 45
2008 Product Data
140 188 45
Ø70
926
Ø70
65
221
175
34
5. Dimensional drawings
Indoor units
2008 Product Data
35
M10
140 188
Ø70
45
2008 Product Data 926
Place a level on raised tab
Unit Outline
42
Ø70 65
127 136
221
M10
178
168
66
296
36 175 45
925 189
46 56
5. Dimensional drawings Indoor units
49
59
295
148 77
71
107
1
28 50 50*6=300
567 354
915
2-R16
51 50
5
171 282 165
37
2
3
51 4
Installation plate
Remark
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lge.com/airconditioner
CHASSIS CODE: SE
3. The Unit is powered from the outdoor unit. Therefore power cable should be connected with the outdoor unit.
2. Unit shall be grounded in accordance with the local regulations or applicable national codes.
1. Unit should be installed in compliance with the installation manual in the product box.
Note
Knockout hole
5
Air suction grille
3 4
Display & signal receiver
2
Part Name Front panel
1
No.
ART COOL Mirror
5. Dimensional drawings Indoor units
2008 Product Data
37
53
282
140 188
Ø70
45
926
1107
5
Ø70 65 221
72 58 122
296
1
175 45
2008 Product Data 2
93
38 200
53
4
Air suction grille Knockout hole
3 4
Remark
ART COOL Mirror
CHASSIS CODE: S8
1. The unit should not be installed in a closed area. 2. In an area or space having no proper circulation, an air guide should be installed on the outdoor side.
Note
Display & signal receiver
2
Part Name Front panel
1
No.
76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lge.com/airconditioner
10 63
3
5. Dimensional drawings Indoor units
48
299
5. Dimensional drawings
Outdoor units
1
5.2 Outdoor Units
2008 Product Data
39
5. Dimensional drawings
1
Outdoor units
40
2008 Product Data
5. Dimensional drawings
2
5
320
3
4
TOOL CODE : UE1
Outdoor units
54 .6
360 79
340
301
546
25
319 808
870
ÿ5
31
16 0
1
76.4
2008 Product Data
41
5. Dimensional drawings
5
320
4
2
3
Part Name
Remark
TOOL CODE : UE2
Outdoor units
360 1060 10
340 320
1
1038 80 301
870
546
162
55
75 460 492
10
2008 Product Data
261
42
6. Wiring diagrams
Indoor Unit
6.1 Indoor units Models: AS-W096E1G0, AS-W0964GG1, AS-W126E1G0, AS-W1264GG1,AS-W1865GG1, AS-W2465DH2
Models: AS-W096F1G2, AS-W096F*G2, AS-W126F*G2
2008 Product Data
43
6. Wiring diagrams
Models: AS-W096U*H1, AS-W126U*H1, AS-W1863*H3
Models: AS-W096E*H2, AS-W126E*H2, AS-W126F1G2
44
2008 Product Data
Indoor Unit
6. Wiring diagrams
Indoor Unit
Models: AS-W096ADR0, AS-W126ADR0
2008 Product Data
45
6. Wiring diagrams
Indoor Unit
Models: AS-W1865DH2
CN_L/R(BL)
CN_U/D(WH)
CN_HVB(BL)
CN_DISP2(BL)
CN_DISP1(WH)
CN_MOTOR1 CN_TH1
CN_TH2
46
2008 Product Data
6. Wiring diagrams
Indoor Unit
Models: AS-W1868*H1
Models: AS-W2463*H3
2008 Product Data
47
6. Wiring diagrams Models: AS-W2468*H1
48
2008 Product Data
Indoor Unit
6. Wiring diagrams
Indoor Unit
Models:AS-W306DGM0,AS-W366DGM0
CN-U/D(WH) CN-DISP2(BL) CN-MOTOR1
CN-L/R(BL)
CN-HVB
CN-12V
CN-DISP1(WH)
CN-TH1 CN-TH2
2008 Product Data
49
6. Wiring diagrams
Outdoor units
6.2 Outdoor units Models: AS-W096E1G0, AS-W096U*H1, AS-W126E1G0, AS-W126U*H1AS-W096E*H2, AS-W126E*H2, AS-W096F1G2, AS-W096F*G2, AS-W126F1G2, AS-W126F*G2
Models: AS-W0964GG1, AS-W1264GG1
50
2008 Product Data
6. Wiring diagrams
Outdoor units
Models: AS-W096ADR0, AS-W126ADR0
2008 Product Data
51
6. Wiring diagrams
Outdoor units
Models: AS-W1865DH2
CN_FAN(A)
CN_4WAY
CN_COIL1 CN_COIL2 CN_TH3 (SUC/DIS_I)
CN_LEV1
52
2008 Product Data
CN_TH2 (AIR/PIPE)
CN_COM
6. Wiring diagrams
Outdoor units
Models: AS-W1865GG1, AS-W1863*H3
Models: AS-W1868*H1
2008 Product Data
53
6. Wiring diagrams Models: AS-W2463*H3
Models: AS-W2468*H1, AS-W2465DH2
54
2008 Product Data
Outdoor units
6. Wiring diagrams
Outdoor units
Models: AS-W306DGM0
CN-PFC-OUT
CN-PFC-IN
CN 4WAY
CN_H/P
CN_TH3 CN-TH2
CN-MOTOR1
CN_LEV1 CN_COM
2008 Product Data
55
6. Wiring diagrams
Outdoor units
Models: AS-W366DGM0
CN-PFC-OUT
CN-PFC-IN
CN 4WAY
CN_H/P
CN_TH3 CN-TH2
CN-MOTOR1 CN-MOTOR2
56
2008 Product Data
CN_LEV1 CN_COM
7. Refrigerant cycle diagram Model No : AS-W096U*H1, AS-W126U*H1, AS-W1865GG1, AS-W1863*H3, AS-W2463*H3 Indoor Unit
Outdoor Unit CHECK VALVE
Liquid Side
Th2
3-Way Valve
Th1
CAPILLARY TUBE Heat Exchanger (Condenser)
Heat Exchanger (Evaporator)
Th4
Th3
Gas Side 3-Way Valve
Reversing Valve
Accumulator
Compressor
Cooling Heating
N.B. : Th1 = Thermistor foor sansing indoor air temperature. Th2 = Thermistor for sensing evaporating temperature. Th3 = Thermistor foor sansing outdoor air temperature. Th4 = Thermistor foor sansing evaporating temperature.
2008 Product Data
57
7. Refrigerant cycle diagram Model no: AS-W096ADR0,AS-W0964GG1, AS-W096E*H2, AS-W096F1G2, AS-W096F*G2, AS-W096E1G0, AS-W126E1G0, AS-W126ADR0, AS-W126E*H2, AS-W126F1G2, AS-W126F*G2, AS-W1264GG1 Indoor Unit
Outdoor Unit
Liquid Side
Th2
EEV
2-Way Valve
Th1
Heat Exchanger (Condenser)
Heat Exchanger (Evaporator)
Th5
Th4
Gas Side 3-Way Valve
Accumulator Th3
Cooling Heating
Compressor
LOC.
58
Description
PCB Connector
Th1
Thermistor for indoor air temperature
CN-TH1(INDOOR)
Th2
Thermistor for evaporating temperature
CN-TH1(INDOOR)
Th3
Thermistor for discharge pipe temperature
CN-D_PIPE(OUTDOOR)
Th4
Thermistor for condensing temperature
CN-TH1(OUTDOOR)
Th5
Thermistor for outdoor air temperature
CN-TH1(OUTDOOR)
2008 Product Data
7. Refrigerant cycle diagram Model no: AS-W1865DH2, AS-W1868*H1 Indoor Unit
Outdoor Unit
Liquid Side EEV
2-Way Valve
Th2
Th5
Th1
Heat Exchanger (Evaporator)
Heat Exchanger (Condenser) Th4
Th3
Gas Side Reversing Valve
3-Way Valve
Th6
Th7
Cooling Heating
Compressor
LOC.
Description
Th1
Thermistor for indoor air temperature
Th2
Thermister for indoor pipe(in) temperature
Th3
Thermister for indoor pipe(out) temperature
Th4
Thermistor for outdoor air temperature
Th5
Thermister for outdoor pipe temperature
Th6
Thermistor for discharge pipe temperature
Th7
Thermistor for suction pipe temperature
PCB Connector CN_TH1(INDOOR) CN_TH2(INDOOR) CN_TH2(OUTDOOR) CN_TH3(OUTDOOR)
2008 Product Data
59
7. Refrigerant cycle diagram Model no: AS-W2468*H1, AS-W2465DH2 Indoor Unit
Outdoor Unit
Liquid Side EEV
3-Way Valve
Th2
Th5
Th1
Heat Exchanger (Evaporator)
Heat Exchanger (Condenser) Th4
Th3
Gas Side Reversing Valve
3-Way Valve
Th6
Th7
Cooling Heating
Compressor
LOC.
60
Description
Th1
Thermistor for indoor air temperature
Th2
Thermister for indoor pipe(in) temperature
Th3
Thermister for indoor pipe(out) temperature
Th4
Thermistor for outdoor air temperature
Th5
Thermister for outdoor pipe temperature
Th6
Thermistor for discharge pipe temperature
Th7
Thermistor for suction pipe temperature
2008 Product Data
PCB Connector CN_TH1(INDOOR) CN_TH2(INDOOR) CN_TH2(OUTDOOR) CN_TH3(OUTDOOR)
7. Refrigerant cycle diagram Model no: AS-W306DGM0, AS-W366DGM0 Indoor Unit
Outdoor Unit Reversing Valve
Liquid Side
Th3
3-Way Valve
Th7
Th1
Heat Exchanger (Evaporator)
Accumulator
High Pressure S/W
Th5
Heat Exchanger Th6 (Condenser) Inverter Compressor
Th2
Th4 Gas Side
EEV
3-Way Valve Cooling Heating
LOC.
Description
Th1
Thermister for indoor air temperature
Th2
Thermister for indoor pipe(in) temperature
Th3
Thermister for indoor pipe(out) temperature
Th4
Thermister for outdoor pipe temperature
Th5
Thermister for outdoor air temperature
Th6
Thermister for outdoor discharge pipe temperature(Inverter)
Th7
Thermister for outdoor suction pipe temperature(Inverter)
PCB Connector CN_TH1(INDOOR) CN-TH2(INDOOR) CN_TH2(OUTDOOR) CN_TH3(OUTDOOR)
2008 Product Data
61
8. Capacity tables
Cooling
8.1 Cooling Capacity
AS-W096ADR0 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.59 2.75 2.91 2.99 3.23 3.39
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 2.21 2.24 2.26 2.28 2.33 2.37
25 PI 0.36 0.49 0.53 0.53 0.53 0.53
TC 2.48 2.63 2.79 2.87 3.11 3.27
SHC 2.14 2.18 2.20 2.22 2.27 2.32
32 PI 0.37 0.49 0.53 0.54 0.55 0.55
TC 2.32 2.48 2.64 2.72 2.96 3.11
SHC 2.06 2.09 2.12 2.15 2.21 2.25
PI 0.50 0.59 0.62 0.63 0.65 0.66
Outdoor Air Temperature : °CDB 35 TC 2.25 2.41 2.57 2.64 2.88 3.04
SHC 1.99 2.03 2.06 2.08 2.14 2.19
40 PI 0.56 0.64 0.65 0.65 0.68 0.70
TC 2.16 2.31 2.47 2.55 2.78 2.94
SHC 1.93 1.97 2.01 2.03 2.10 2.15
43 PI 0.62 0.66 0.67 0.68 0.69 0.70
TC 2.10 2.25 2.41 2.49 2.72 2.88
SHC 1.86 1.91 1.94 1.97 2.04 2.09
PI 0.60 0.63 0.63 0.63 0.64 0.65
AS-W096E*H2 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.14 2.50 2.79 2.91 3.20 3.32
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 1.67 1.89 2.06 2.13 2.26 2.30
PI 0.43 0.43 0.44 0.45 0.45 0.46
TC 2.09 2.44 2.73 2.85 3.13 3.25
SHC 1.65 1.88 2.04 2.11 2.23 2.27
32 PI 0.50 0.51 0.52 0.53 0.54 0.54
TC 2.00 2.33 2.60 2.72 2.98 3.10
SHC 1.61 1.82 1.98 2.04 2.16 2.19
PI 0.59 0.60 0.61 0.62 0.62 0.63
Outdoor Air Temperature : °CDB 35 TC 1.94 2.26 2.52 2.64 2.89 3.00
SHC 1.58 1.78 1.93 1.99 2.10 2.13
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
62
25
2008 Product Data
40 PI 0.62 0.63 0.64 0.65 0.66 0.67
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 1.86 2.17 2.43 2.54 2.79 2.89
SHC 1.54 1.74 1.88 1.94 2.05 2.07
43 PI 0.66 0.67 0.68 0.69 0.70 0.71
TC 1.82 2.12 2.37 2.48 2.72 2.83
SHC 1.52 1.71 1.85 1.91 2.01 2.03
PI 0.68 0.69 0.70 0.71 0.72 0.73
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
8. Capacity tables
Cooling
AS-W096F1G2, AS-W096F*G2 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.19 2.55 2.85 2.98 3.27 3.40
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 1.71 1.94 2.11 2.18 2.31 2.35
25 PI 0.54 0.55 0.56 0.57 0.58 0.59
TC 2.14 2.50 2.79 2.92 3.20 3.33
SHC 1.69 1.92 2.09 2.16 2.28 2.32
32 PI 0.64 0.65 0.66 0.68 0.68 0.69
TC 2.04 2.38 2.66 2.78 3.05 3.17
SHC 1.65 1.86 2.02 2.09 2.21 2.24
PI 0.75 0.76 0.77 0.79 0.80 0.81
Outdoor Air Temperature : °CDB 35 TC 1.98 2.31 2.58 2.70 2.96 3.07
SHC 1.61 1.82 1.98 2.04 2.15 2.18
40 PI 0.79 0.80 0.82 0.83 0.84 0.85
TC 1.91 2.23 2.48 2.60 2.85 2.96
SHC 1.58 1.78 1.93 1.99 2.09 2.12
43 PI 0.84 0.86 0.87 0.88 0.89 0.91
TC 1.86 2.17 2.43 2.54 2.79 2.89
SHC 1.55 1.75 1.90 1.95 2.06 2.08
PI 0.87 0.88 0.90 0.91 0.92 0.94
AS-W096U*H1 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.14 2.50 2.79 2.91 3.20 3.32
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 1.67 1.89 2.06 2.13 2.26 2.30
25 PI 0.49 0.50 0.51 0.52 0.52 0.53
TC 2.09 2.44 2.73 2.85 3.13 3.25
SHC 1.65 1.88 2.04 2.11 2.23 2.27
32 PI 0.58 0.59 0.60 0.61 0.62 0.63
TC 2.00 2.33 2.60 2.72 2.98 3.10
SHC 1.61 1.82 1.98 2.04 2.16 2.19
PI 0.68 0.69 0.70 0.71 0.72 0.73
Outdoor Air Temperature : °CDB 35 TC 1.94 2.26 2.52 2.64 2.89 3.00
SHC 1.58 1.78 1.93 1.99 2.10 2.13
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
40 PI 0.72 0.73 0.74 0.75 0.76 0.77
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 1.86 2.17 2.43 2.54 2.79 2.89
SHC 1.54 1.74 1.88 1.94 2.05 2.07
43 PI 0.76 0.77 0.78 0.80 0.81 0.82
TC 1.82 2.12 2.37 2.48 2.72 2.83
SHC 1.52 1.71 1.85 1.91 2.01 2.03
PI 0.79 0.80 0.81 0.82 0.83 0.85
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
63
8. Capacity tables
Cooling
AS-W0964GG1 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.14 2.50 2.79 2.91 3.20 3.32
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 1.67 1.89 2.06 2.13 2.26 2.30
25 PI 0.54 0.55 0.55 0.56 0.57 0.58
TC 2.09 2.44 2.73 2.85 3.13 3.25
SHC 1.65 1.88 2.04 2.11 2.23 2.27
32 PI 0.64 0.65 0.66 0.67 0.68 0.69
TC 2.00 2.33 2.60 2.72 2.98 3.10
SHC 1.61 1.82 1.98 2.04 2.16 2.19
PI 0.74 0.75 0.77 0.78 0.79 0.80
Outdoor Air Temperature : °CDB 35 TC 1.94 2.26 2.52 2.64 2.89 3.00
SHC 1.58 1.78 1.93 1.99 2.10 2.13
40 PI 0.78 0.79 0.81 0.82 0.83 0.84
TC 1.86 2.17 2.43 2.54 2.79 2.89
SHC 1.54 1.74 1.88 1.94 2.05 2.07
43 PI 0.83 0.84 0.86 0.87 0.88 0.90
TC 1.82 2.12 2.37 2.48 2.72 2.83
SHC 1.52 1.71 1.85 1.91 2.01 2.03
PI 0.86 0.87 0.89 0.90 0.91 0.93
AS-W126ADR0 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 3.44 3.65 3.87 3.97 4.29 4.50
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 2.88 2.92 2.94 2.97 3.03 3.08
TC 3.29 3.50 3.71 3.82 4.14 4.35
SHC 2.79 2.83 2.86 2.89 2.95 3.01
32 PI 0.63 0.82 0.89 0.90 0.92 0.92
TC 3.09 3.30 3.51 3.62 3.93 4.14
SHC 2.67 2.72 2.76 2.79 2.87 2.93
PI 0.84 1.00 1.05 1.06 1.08 1.10
Outdoor Air Temperature : °CDB 35 TC 3.00 3.21 3.41 3.51 3.83 4.04
SHC 2.58 2.64 2.68 2.70 2.79 2.85
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
64
25 PI 0.60 0.82 0.88 0.89 0.89 0.89
2008 Product Data
40 PI 0.94 1.07 1.09 1.09 1.14 1.17
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 2.87 3.07 3.28 3.39 3.70 3.91
SHC 2.50 2.56 2.61 2.64 2.73 2.80
43 PI 1.03 1.11 1.13 1.13 1.15 1.18
TC 2.79 3.00 3.20 3.31 3.62 3.83
SHC 2.42 2.48 2.53 2.56 2.65 2.72
PI 1.01 1.06 1.06 1.06 1.07 1.09
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
8. Capacity tables
Cooling
AS-W126E1G0, AS-W126E*H2 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.85 3.33 3.71 3.89 4.27 4.43
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 2.22 2.53 2.75 2.84 3.01 3.06
25 PI 0.71 0.73 0.74 0.75 0.76 0.77
TC 2.79 3.26 3.63 3.80 4.17 4.33
SHC 2.21 2.50 2.72 2.81 2.97 3.02
32 PI 0.85 0.86 0.87 0.89 0.90 0.91
TC 2.66 3.10 3.46 3.63 3.98 4.13
SHC 2.14 2.43 2.63 2.72 2.87 2.92
PI 0.99 1.00 1.02 1.03 1.05 1.06
Outdoor Air Temperature : °CDB 35 TC 2.58 3.01 3.36 3.52 3.86 4.01
SHC 2.10 2.38 2.57 2.66 2.81 2.84
40 PI 1.04 1.06 1.07 1.09 1.10 1.12
TC 2.49 2.90 3.24 3.39 3.72 3.86
SHC 2.05 2.32 2.51 2.59 2.73 2.76
43 PI 1.11 1.12 1.14 1.16 1.17 1.19
TC 2.43 2.83 3.16 3.31 3.63 3.77
SHC 2.03 2.28 2.47 2.55 2.68 2.71
PI 1.14 1.16 1.18 1.20 1.21 1.23
AS-W126F1G2, AS-W126F*G2 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 3.43 3.64 3.85 3.96 4.28 4.49
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 2.82 2.85 2.88 2.90 2.96 3.02
25 PI 0.60 0.82 0.88 0.89 0.89 0.89
TC 3.28 3.49 3.70 3.81 4.12 4.33
SHC 2.73 2.77 2.80 2.83 2.89 2.95
32 PI 0.63 0.82 0.89 0.90 0.92 0.92
TC 3.08 3.29 3.50 3.61 3.92 4.13
SHC 2.62 2.67 2.70 2.73 2.81 2.87
PI 0.84 1.00 1.05 1.06 1.08 1.10
Outdoor Air Temperature : °CDB 35 TC 2.99 3.20 3.40 3.50 3.82 4.03
SHC 2.53 2.58 2.62 2.64 2.73 2.79
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
40 PI 0.94 1.07 1.09 1.09 1.14 1.17
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 2.86 3.07 3.27 3.38 3.69 3.90
SHC 2.45 2.51 2.55 2.59 2.67 2.74
43 PI 1.03 1.11 1.13 1.13 1.15 1.18
TC 2.78 2.99 3.19 3.30 3.61 3.82
SHC 2.36 2.43 2.47 2.51 2.59 2.66
PI 1.01 1.06 1.06 1.06 1.07 1.09
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
65
8. Capacity tables
Cooling
AS-W126U*H1 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.85 3.33 3.71 3.89 4.27 4.43
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 2.22 2.53 2.75 2.84 3.01 3.06
25 PI 0.71 0.73 0.74 0.75 0.76 0.77
TC 2.79 3.26 3.63 3.80 4.17 4.33
SHC 2.21 2.50 2.72 2.81 2.97 3.02
32 PI 0.85 0.86 0.87 0.89 0.90 0.91
TC 2.66 3.10 3.46 3.63 3.98 4.13
SHC 2.14 2.43 2.63 2.72 2.87 2.92
PI 0.99 1.00 1.02 1.03 1.05 1.06
Outdoor Air Temperature : °CDB 35 TC 2.58 3.01 3.36 3.52 3.86 4.01
SHC 2.10 2.38 2.57 2.66 2.81 2.84
40 PI 1.04 1.06 1.07 1.09 1.10 1.12
TC 2.49 2.90 3.24 3.39 3.72 3.86
SHC 2.05 2.32 2.51 2.59 2.73 2.76
43 PI 1.11 1.12 1.14 1.16 1.17 1.19
TC 2.43 2.83 3.16 3.31 3.63 3.77
SHC 2.03 2.28 2.47 2.55 2.68 2.71
PI 1.14 1.16 1.18 1.20 1.21 1.23
AS-W1264GG1 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 2.85 3.33 3.71 3.89 4.27 4.43
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 2.22 2.53 2.75 2.84 3.01 3.06
TC 2.79 3.26 3.63 3.80 4.17 4.33
SHC 2.21 2.50 2.72 2.81 2.97 3.02
32 PI 0.85 0.86 0.87 0.89 0.90 0.91
TC 2.66 3.10 3.46 3.63 3.98 4.13
SHC 2.14 2.43 2.63 2.72 2.87 2.92
PI 0.99 1.00 1.02 1.03 1.05 1.06
Outdoor Air Temperature : °CDB 35 TC 2.58 3.01 3.36 3.52 3.86 4.01
SHC 2.10 2.38 2.57 2.66 2.81 2.84
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
66
25 PI 0.71 0.73 0.74 0.75 0.76 0.77
2008 Product Data
40 PI 1.04 1.06 1.07 1.09 1.10 1.12
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 2.49 2.90 3.24 3.39 3.72 3.86
SHC 2.05 2.32 2.51 2.59 2.73 2.76
43 PI 1.11 1.12 1.14 1.16 1.17 1.19
TC 2.43 2.83 3.16 3.31 3.63 3.77
SHC 2.03 2.28 2.47 2.55 2.68 2.71
PI 1.14 1.16 1.18 1.20 1.21 1.23
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
8. Capacity tables
Cooling
AS-W1863*H3 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 4.28 4.99 5.57 5.83 6.40 6.64
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 3.34 3.79 4.12 4.26 4.52 4.59
25 PI 1.07 1.08 1.10 1.12 1.13 1.15
TC 4.19 4.89 5.45 5.71 6.26 6.50
SHC 3.31 3.75 4.08 4.21 4.46 4.53
32 PI 1.27 1.29 1.30 1.33 1.34 1.36
TC 3.99 4.66 5.20 5.44 5.97 6.19
SHC 3.22 3.64 3.95 4.08 4.31 4.37
PI 1.48 1.50 1.52 1.55 1.57 1.59
Outdoor Air Temperature : °CDB 35 TC 3.87 4.52 5.04 5.28 5.79 6.01
SHC 3.15 3.56 3.86 3.99 4.21 4.27
40 PI 1.55 1.58 1.60 1.63 1.65 1.67
TC 3.73 4.35 4.85 5.08 5.57 5.78
SHC 3.08 3.48 3.77 3.88 4.09 4.14
43 PI 1.65 1.68 1.70 1.73 1.76 1.78
TC 3.64 4.25 4.74 4.96 5.45 5.65
SHC 3.04 3.43 3.70 3.82 4.02 4.07
PI 1.71 1.73 1.76 1.79 1.81 1.84
AS-W1865DH2 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 5.18 5.50 5.81 5.97 6.45 6.77
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 4.27 4.32 4.36 4.40 4.49 4.57
25 PI 0.91 1.23 1.33 1.34 1.34 1.34
TC 4.95 5.27 5.59 5.75 6.22 6.54
SHC 4.13 4.19 4.24 4.28 4.38 4.47
32 PI 0.95 1.24 1.34 1.36 1.38 1.39
TC 4.65 4.97 5.28 5.44 5.91 6.23
SHC 3.96 4.04 4.10 4.14 4.25 4.35
PI 1.27 1.50 1.57 1.59 1.63 1.66
Outdoor Air Temperature : °CDB 35 TC 4.51 4.82 5.14 5.28 5.76 6.08
SHC 3.83 3.91 3.97 4.01 4.13 4.23
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
40 PI 1.42 1.61 1.64 1.64 1.72 1.75
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 4.31 4.62 4.94 5.10 5.57 5.88
SHC 3.71 3.80 3.87 3.92 4.05 4.15
43 PI 1.56 1.68 1.70 1.71 1.73 1.77
TC 4.19 4.51 4.82 4.98 5.45 5.76
SHC 3.58 3.68 3.75 3.80 3.93 4.03
PI 1.53 1.60 1.59 1.59 1.61 1.64
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
67
8. Capacity tables
Cooling
AS-W1865GG1 Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDBB 20 TC 5.18 5.50 5.81 5.97 6.45 6.77
Indoor Air Temperature °CWB 14 16 18 19 22 24
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 4.25 4.30 4.34 4.38 4.46 4.55
25 PI 0.96 1.30 1.40 1.42 1.42 1.41
TC 4.95 5.27 5.59 5.75 6.22 6.54
SHC 4.11 4.17 4.22 4.26 4.35 4.44
32 PI 1.00 1.31 1.41 1.43 1.45 1.47
TC 4.65 4.97 5.28 5.44 5.91 6.23
SHC 3.94 4.02 4.07 4.12 4.23 4.32
PI 1.34 1.58 1.66 1.68 1.72 1.75
Outdoor Air Temperature : °CDB 35 TC 4.51 4.82 5.14 5.28 5.76 6.08
SHC 3.81 3.89 3.95 3.99 4.11 4.21
40 PI 1.50 1.70 1.73 1.73 1.81 1.85
TC 4.31 4.62 4.94 5.10 5.57 5.88
SHC 3.69 3.78 3.85 3.90 4.02 4.13
43 PI 1.64 1.77 1.79 1.80 1.83 1.87
TC 4.19 4.51 4.82 4.98 5.45 5.76
SHC 3.56 3.66 3.73 3.78 3.91 4.01
PI 1.61 1.68 1.68 1.68 1.69 1.73
AS-W1868*H1 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 4.28 4.99 5.57 5.83 6.40 6.64
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 3.36 3.81 4.15 4.29 4.55 4.62
PI 1.07 1.09 1.11 1.13 1.14 1.16
TC 4.19 4.89 5.45 5.71 6.26 6.50
SHC 3.33 3.77 4.10 4.24 4.49 4.56
32 PI 1.27 1.29 1.31 1.34 1.35 1.37
TC 3.99 4.66 5.20 5.44 5.97 6.19
SHC 3.24 3.66 3.97 4.10 4.34 4.40
PI 1.48 1.51 1.53 1.56 1.58 1.60
Outdoor Air Temperature : °CDB 35 TC 3.87 4.52 5.04 5.28 5.79 6.01
SHC 3.17 3.58 3.88 4.01 4.23 4.29
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
68
25
2008 Product Data
40 PI 1.56 1.59 1.61 1.64 1.66 1.69
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 3.73 4.35 4.85 5.08 5.57 5.78
SHC 3.10 3.50 3.79 3.91 4.12 4.17
43 PI 1.66 1.69 1.72 1.74 1.77 1.79
TC 3.64 4.25 4.74 4.96 5.45 5.65
SHC 3.06 3.45 3.73 3.84 4.04 4.09
PI 1.72 1.75 1.77 1.80 1.83 1.85
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
8. Capacity tables
Cooling
AS-W2463*H3 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 5.70 6.66 7.43 7.77 8.53 8.85
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 4.45 5.05 5.50 5.68 6.03 6.13
25 PI 1.70 1.73 1.76 1.79 1.81 1.84
TC 5.58 6.52 7.27 7.61 8.35 8.67
SHC 4.41 5.00 5.43 5.62 5.95 6.04
32 PI 2.02 2.05 2.08 2.12 2.14 2.18
TC 5.32 6.21 6.93 7.25 7.96 8.26
SHC 4.29 4.86 5.27 5.44 5.75 5.83
PI 2.35 2.39 2.43 2.47 2.50 2.54
Outdoor Air Temperature : °CDB 35 TC 5.16 6.02 6.72 7.03 7.72 8.01
SHC 4.20 4.75 5.15 5.31 5.61 5.69
40 PI 2.48 2.52 2.56 2.60 2.63 2.67
TC 4.97 5.80 6.47 6.77 7.43 7.71
SHC 4.11 4.64 5.02 5.18 5.46 5.53
43 PI 2.64 2.68 2.72 2.77 2.80 2.84
TC 4.86 5.66 6.32 6.62 7.26 7.53
SHC 4.05 4.57 4.94 5.09 5.36 5.42
PI 2.72 2.77 2.81 2.86 2.89 2.94
AS-W2465DH2 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 5.70 6.66 7.43 7.77 8.53 8.85
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 4.45 5.05 5.50 5.68 6.03 6.13
25 PI 1.64 1.66 1.69 1.72 1.74 1.76
TC 5.58 6.52 7.27 7.61 8.35 8.67
SHC 4.41 5.00 5.43 5.62 5.95 6.04
32 PI 1.94 1.97 2.00 2.04 2.06 2.09
TC 5.32 6.21 6.93 7.25 7.96 8.26
SHC 4.29 4.86 5.27 5.44 5.75 5.83
PI 2.26 2.30 2.33 2.37 2.40 2.44
Outdoor Air Temperature : °CDB 35 TC 5.16 6.02 6.72 7.03 7.72 8.01
SHC 4.20 4.75 5.15 5.31 5.61 5.69
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
40 PI 2.38 2.42 2.46 2.50 2.53 2.57
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 4.97 5.80 6.47 6.77 7.43 7.71
SHC 4.11 4.64 5.02 5.18 5.46 5.53
43 PI 2.54 2.58 2.61 2.66 2.69 2.73
TC 4.86 5.66 6.32 6.62 7.26 7.53
SHC 4.05 4.57 4.94 5.09 5.36 5.42
PI 2.62 2.66 2.70 2.75 2.78 2.82
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
69
8. Capacity tables
Cooling
AS-W2468*H1 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 5.70 6.66 7.43 7.77 8.53 8.85
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 4.65 5.28 5.75 5.94 6.30 6.41
25 PI 1.61 1.63 1.65 1.68 1.70 1.73
TC 5.58 6.52 7.27 7.61 8.35 8.67
SHC 4.61 5.23 5.68 5.87 6.22 6.32
32 PI 1.90 1.93 1.96 1.99 2.02 2.05
TC 5.32 6.21 6.93 7.25 7.96 8.26
SHC 4.49 5.08 5.51 5.69 6.01 6.10
PI 2.22 2.25 2.29 2.33 2.36 2.39
Outdoor Air Temperature : °CDB 35 TC 5.16 6.02 6.72 7.03 7.72 8.01
SHC 4.39 4.97 5.38 5.56 5.87 5.95
40 PI 2.34 2.37 2.41 2.45 2.48 2.52
TC 4.97 5.80 6.47 6.77 7.43 7.71
SHC 4.30 4.85 5.25 5.41 5.71 5.78
43 PI 2.49 2.52 2.56 2.61 2.64 2.68
TC 4.86 5.66 6.32 6.62 7.26 7.53
SHC 4.24 4.78 5.17 5.33 5.61 5.67
PI 2.57 2.61 2.65 2.69 2.73 2.77
AS-W306DGM0 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 7.84 8.33 8.81 9.05 9.78 10.26
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 6.90 6.99 7.05 7.12 7.26 7.39
TC 7.50 7.98 8.46 8.70 9.43 9.91
SHC 6.68 6.78 6.85 6.92 7.08 7.22
32 PI 1.53 2.00 2.16 2.19 2.23 2.25
TC 7.04 7.52 8.00 8.24 8.96 9.44
SHC 6.41 6.53 6.62 6.70 6.88 7.03
PI 2.05 2.42 2.54 2.57 2.63 2.68
Outdoor Air Temperature : °CDB 35 TC 6.83 7.31 7.78 8.00 8.73 9.21
SHC 6.19 6.32 6.42 6.48 6.68 6.84
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
70
25 PI 1.46 1.98 2.15 2.17 2.17 2.16
2008 Product Data
40 PI 2.29 2.60 2.65 2.65 2.78 2.83
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 6.53 7.01 7.48 7.72 8.43 8.91
SHC 6.00 6.15 6.26 6.34 6.54 6.71
43 PI 2.52 2.71 2.75 2.76 2.80 2.86
TC 6.35 6.83 7.30 7.54 8.25 8.73
SHC 5.79 5.94 6.06 6.14 6.35 6.52
PI 2.46 2.58 2.58 2.57 2.60 2.65
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
8. Capacity tables
Cooling
AS-W366DGM0 Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
Outdoor Air Temperature : °CDB 20 TC 8.82 9.37 9.91 10.18 11.00 11.54
Indoor Air Temperature °CWB 14.0 16.0 18.0 19.0 22.0 24.0
°CDB 20.0 22.0 25.0 27.0 30.0 32.0
SHC 7.29 7.38 7.44 7.51 7.66 7.80
25 PI 1.65 2.23 2.41 2.44 2.44 2.43
TC 8.44 8.98 9.52 9.79 10.60 11.14
SHC 7.05 7.16 7.24 7.31 7.47 7.62
32 PI 1.72 2.25 2.43 2.46 2.50 2.53
TC 7.93 8.46 9.00 9.27 10.08 10.62
SHC 6.77 6.89 6.99 7.07 7.26 7.42
PI 2.31 2.72 2.86 2.89 2.96 3.01
Outdoor Air Temperature : °CDB 35 TC 7.68 8.22 8.75 9.00 9.83 10.36
SHC 6.54 6.67 6.78 6.84 7.05 7.22
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
40 PI 2.58 2.92 2.98 2.98 3.12 3.19
[m3/min] [°C] [°C] [kW] [kW] [kW]
TC 7.35 7.88 8.42 8.69 9.49 10.02
SHC 6.34 6.49 6.61 6.69 6.90 7.08
43 PI 2.83 3.05 3.09 3.10 3.15 3.22
TC 7.14 7.68 8.22 8.48 9.29 9.82
SHC 6.12 6.27 6.40 6.49 6.70 6.88
PI 2.77 2.90 2.90 2.89 2.92 2.98
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
71
8. Capacity tables
Heating
8.2 Heating Capacity
AS-W096ADR0, AS-W096E*H2 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 2.71 2.68 2.66 2.66 2.65 2.62
-10 PI 0.71 0.72 0.73 0.74 0.75 0.77
TC 2.85 2.84 2.84 2.84 2.84 2.82
-5 PI 0.69 0.71 0.73 0.74 0.75 0.77
TC 3.09 3.09 3.09 3.09 3.09 3.05
0 PI 0.72 0.75 0.77 0.78 0.79 0.81
TC 3.30 3.30 3.29 3.28 3.27 3.24
6 PI 0.78 0.80 0.82 0.83 0.84 0.86
TC 3.66 3.64 3.60 3.58 3.55 3.52
10 PI 0.83 0.85 0.87 0.88 0.89 0.90
TC 3.87 3.82 3.79 3.79 3.79 3.72
PI 0.92 0.94 0.96 0.97 0.98 0.99
TC 3.76 3.71 3.69 3.69 3.68 3.62
PI 0.83 0.85 0.87 0.88 0.89 0.90
TC 3.41 3.36 3.34 3.34 3.34 3.28
PI 0.89 0.91 0.93 0.94 0.95 0.96
TC 3.41 3.36 3.34 3.34 3.34 3.28
15 PI 0.87 0.88 0.90 0.90 0.91 0.92
TC 4.20 4.18 4.19 4.16 4.13 4.08
PI 0.96 0.97 0.99 1.00 1.00 1.01
TC 4.08 4.07 4.07 4.05 4.01 3.97
PI 0.87 0.88 0.90 0.90 0.91 0.92
TC 3.70 3.68 3.69 3.67 3.64 3.59
PI 0.93 0.94 0.96 0.96 0.97 0.98
TC 3.70 3.68 3.69 3.67 3.64 3.59
PI 0.92 0.93 0.94 0.94 0.94 0.95
AS-W096F1G2, AS-W096F*G2 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 2.63 2.61 2.59 2.58 2.58 2.55
-10 PI 0.78 0.79 0.81 0.82 0.83 0.85
TC 2.77 2.76 2.76 2.76 2.76 2.74
-5 PI 0.76 0.78 0.80 0.81 0.83 0.85
TC 3.00 3.00 3.01 3.01 3.00 2.97
0 PI 0.80 0.82 0.85 0.86 0.87 0.89
TC 3.21 3.20 3.20 3.19 3.18 3.15
6 PI 0.86 0.88 0.91 0.92 0.93 0.95
TC 3.56 3.53 3.50 3.48 3.45 3.43
10
15 PI 1.02 1.03 1.04 1.04 1.04 1.05
AS-W096U*H1 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 2.38 2.36 2.34 2.34 2.33 2.31
-10 PI 0.71 0.72 0.73 0.74 0.75 0.77
TC 2.51 2.50 2.50 2.50 2.50 2.48
-5 PI 0.69 0.71 0.73 0.74 0.75 0.77
TC 2.72 2.72 2.72 2.72 2.72 2.69
0 PI 0.72 0.75 0.77 0.78 0.79 0.81
TC 2.90 2.90 2.89 2.89 2.88 2.86
6 PI 0.78 0.80 0.82 0.83 0.84 0.86
TC 3.22 3.20 3.17 3.15 3.13 3.10
10
15 PI 0.92 0.93 0.94 0.94 0.94 0.95
AS-W0964GG1 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 2.38 2.36 2.34 2.34 2.33 2.31
-10 PI 0.76 0.77 0.78 0.79 0.80 0.82
TC 2.51 2.50 2.50 2.50 2.50 2.48
-5 PI 0.74 0.76 0.78 0.79 0.80 0.82
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
72
2008 Product Data
TC 2.72 2.72 2.72 2.72 2.72 2.69
[m3/min] [°C] [°C] [kW] [kW] [kW]
0 PI 0.77 0.80 0.82 0.83 0.84 0.87
TC 2.90 2.90 2.89 2.89 2.88 2.86
6 PI 0.83 0.86 0.88 0.89 0.90 0.92
TC 3.22 3.20 3.17 3.15 3.13 3.10
10
15 PI 0.99 1.00 1.00 1.01 1.01 1.01
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero. - Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB
8. Capacity tables
Heating
AS-W126ADR0, AS-W126E1G0, AS-W126E*H2 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 3.44 3.40 3.38 3.37 3.36 3.32
-10 PI 1.03 1.04 1.06 1.07 1.08 1.11
TC 3.62 3.61 3.61 3.61 3.61 3.57
-5 PI 1.00 1.03 1.05 1.07 1.08 1.11
TC 3.92 3.92 3.93 3.93 3.92 3.88
0 PI 1.05 1.08 1.11 1.13 1.14 1.17
TC 4.19 4.18 4.17 4.16 4.15 4.12
6 PI 1.13 1.16 1.19 1.20 1.22 1.25
TC 4.65 4.62 4.57 4.54 4.51 4.47
10 PI 1.21 1.23 1.26 1.27 1.28 1.30
TC 4.91 4.85 4.82 4.82 4.81 4.73
15 PI 1.25 1.28 1.30 1.31 1.31 1.33
TC 5.33 5.31 5.32 5.29 5.24 5.18
PI 1.34 1.35 1.36 1.36 1.36 1.37
AS-W126F1G2, AS-W126F*G2 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 3.16 3.13 3.10 3.10 3.09 3.05
-10 PI 0.95 0.96 0.98 0.99 1.00 1.02
TC 3.32 3.32 3.32 3.32 3.32 3.29
-5 PI 0.92 0.95 0.97 0.98 1.00 1.03
TC 3.60 3.61 3.61 3.61 3.61 3.56
0 PI 0.97 0.99 1.02 1.04 1.05 1.08
TC 3.85 3.84 3.83 3.83 3.82 3.79
6 PI 1.04 1.07 1.10 1.11 1.12 1.15
TC 4.27 4.24 4.20 4.17 4.14 4.11
10 PI 1.11 1.14 1.16 1.17 1.18 1.20
TC 4.51 4.46 4.43 4.43 4.42 4.35
PI 1.35 1.38 1.41 1.42 1.44 1.46
TC 4.25 4.20 4.17 4.17 4.17 4.10
PI 1.12 1.15 1.17 1.18 1.19 1.21
TC 4.30 4.24 4.21 4.21 4.21 4.14
15 PI 1.16 1.18 1.20 1.20 1.21 1.22
TC 4.90 4.88 4.89 4.86 4.82 4.76
PI 1.40 1.43 1.45 1.46 1.47 1.48
TC 4.62 4.60 4.61 4.58 4.54 4.49
PI 1.17 1.19 1.21 1.21 1.22 1.23
TC 4.66 4.65 4.66 4.63 4.59 4.53
PI 1.23 1.24 1.25 1.25 1.25 1.26
AS-W126U*H1 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 2.98 2.95 2.93 2.92 2.92 2.88
-10 PI 1.15 1.17 1.19 1.20 1.21 1.24
TC 3.13 3.13 3.13 3.13 3.13 3.10
-5 PI 1.12 1.15 1.18 1.20 1.21 1.25
TC 3.40 3.40 3.40 3.40 3.40 3.36
0 PI 1.17 1.21 1.24 1.26 1.28 1.31
TC 3.63 3.62 3.62 3.61 3.60 3.57
6 PI 1.26 1.30 1.33 1.35 1.36 1.40
TC 4.03 4.00 3.96 3.94 3.91 3.88
10
15 PI 1.50 1.51 1.52 1.52 1.52 1.54
AS-W1264GG1 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 3.01 2.98 2.96 2.95 2.94 2.91
-10 PI 0.95 0.97 0.99 1.00 1.01 1.03
TC 3.16 3.16 3.16 3.16 3.16 3.13
-5 PI 0.93 0.95 0.98 0.99 1.01 1.03
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
TC 3.43 3.43 3.44 3.44 3.43 3.39
[m3/min] [°C] [°C] [kW] [kW] [kW]
0 PI 0.97 1.00 1.03 1.05 1.06 1.09
TC 3.66 3.66 3.65 3.64 3.63 3.61
6 PI 1.05 1.08 1.10 1.12 1.13 1.16
TC 4.07 4.04 4.00 3.97 3.95 3.91
10
15 PI 1.24 1.25 1.26 1.26 1.26 1.27
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero. - Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB
2008 Product Data
73
8. Capacity tables
Heating
AS-W1863*H3 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 4.56 4.52 4.49 4.48 4.47 4.42
-10 PI 1.54 1.56 1.59 1.61 1.63 1.67
TC 4.80 4.79 4.79 4.79 4.79 4.75
-5 PI 1.50 1.54 1.58 1.60 1.62 1.67
TC 5.20 5.21 5.21 5.21 5.21 5.15
0 PI 1.57 1.62 1.67 1.69 1.71 1.76
TC 5.56 5.56 5.54 5.53 5.51 5.47
6 PI 1.69 1.74 1.78 1.81 1.83 1.87
TC 6.17 6.13 6.07 6.03 5.99 5.94
10 PI 1.81 1.85 1.89 1.91 1.92 1.96
TC 6.52 6.44 6.40 6.40 6.39 6.28
15 PI 1.88 1.92 1.95 1.96 1.97 1.99
TC 7.08 7.05 7.07 7.02 6.96 6.88
PI 2.00 2.03 2.04 2.04 2.04 2.06
AS-W1865DH2 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 4.56 4.52 4.49 4.48 4.47 4.42
-10 PI 1.44 1.46 1.49 1.51 1.52 1.56
TC 4.80 4.79 4.79 4.79 4.79 4.75
-5 PI 1.41 1.44 1.48 1.50 1.52 1.57
TC 5.20 5.21 5.21 5.21 5.21 5.15
0 PI 1.47 1.52 1.56 1.58 1.60 1.65
TC 5.56 5.56 5.54 5.53 5.51 5.47
6 PI 1.58 1.63 1.67 1.69 1.71 1.75
TC 6.17 6.13 6.07 6.03 5.99 5.94
10 PI 1.69 1.73 1.77 1.79 1.80 1.83
TC 6.52 6.44 6.40 6.40 6.39 6.28
PI 1.72 1.76 1.80 1.82 1.83 1.86
TC 6.23 6.15 6.11 6.11 6.10 6.00
PI 2.68 2.74 2.80 2.83 2.85 2.90
TC 8.54 8.43 8.38 8.38 8.37 8.23
15 PI 1.76 1.80 1.82 1.84 1.85 1.86
TC 7.08 7.05 7.07 7.02 6.96 6.88
PI 1.79 1.83 1.85 1.87 1.88 1.89
TC 6.76 6.74 6.75 6.71 6.65 6.58
PI 2.79 2.84 2.89 2.90 2.92 2.95
TC 9.27 9.24 9.25 9.19 9.12 9.01
PI 1.88 1.90 1.91 1.91 1.91 1.93
AS-W1865GG1 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 4.36 4.32 4.29 4.28 4.27 4.22
-10 PI 1.47 1.49 1.52 1.53 1.55 1.59
TC 4.59 4.58 4.58 4.58 4.58 4.54
-5 PI 1.43 1.47 1.51 1.53 1.55 1.59
TC 4.97 4.98 4.98 4.98 4.98 4.92
0 PI 1.50 1.54 1.59 1.61 1.63 1.68
TC 5.31 5.31 5.30 5.28 5.27 5.23
6 PI 1.61 1.66 1.70 1.72 1.74 1.78
TC 5.90 5.86 5.80 5.76 5.72 5.68
10
15 PI 1.91 1.93 1.94 1.95 1.95 1.96
AS-W2463*H3 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 5.98 5.92 5.88 5.86 5.85 5.78
-10 PI 2.28 2.32 2.36 2.38 2.41 2.47
TC 6.29 6.28 6.28 6.28 6.28 6.22
-5 PI 2.23 2.28 2.34 2.37 2.41 2.48
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
74
2008 Product Data
TC 6.82 6.82 6.83 6.83 6.83 6.74
[m3/min] [°C] [°C] [kW] [kW] [kW]
0 PI 2.33 2.40 2.47 2.50 2.54 2.61
TC 7.28 7.28 7.26 7.24 7.22 7.17
6 PI 2.50 2.58 2.64 2.68 2.71 2.78
TC 8.08 8.03 7.95 7.90 7.84 7.78
10
15 PI 2.97 3.00 3.02 3.03 3.03 3.05
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero. - Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB
8. Capacity tables
Heating
AS-W2465DH2 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 6.08 6.01 5.97 5.96 5.95 5.88
-10 PI 2.35 2.38 2.43 2.45 2.48 2.54
TC 6.39 6.38 6.38 6.38 6.38 6.32
-5 PI 2.29 2.35 2.41 2.44 2.48 2.55
TC 6.93 6.94 6.94 6.94 6.94 6.85
0 PI 2.40 2.47 2.54 2.57 2.61 2.68
TC 7.40 7.40 7.38 7.36 7.34 7.28
6 PI 2.58 2.65 2.72 2.75 2.79 2.86
TC 8.21 8.16 8.08 8.03 7.97 7.91
10 PI 2.76 2.82 2.88 2.91 2.93 2.98
TC 8.68 8.57 8.51 8.51 8.50 8.36
15 PI 2.87 2.92 2.97 2.99 3.00 3.03
TC 9.42 9.39 9.41 9.34 9.27 9.16
PI 3.06 3.09 3.11 3.11 3.11 3.14
AS-W2468*H1 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 6.35 6.28 6.24 6.22 6.21 6.14
-10 PI 2.36 2.40 2.44 2.47 2.49 2.55
TC 6.68 6.67 6.66 6.66 6.67 6.60
-5 PI 2.31 2.36 2.43 2.46 2.49 2.56
TC 7.24 7.25 7.25 7.25 7.25 7.16
0 PI 2.41 2.48 2.55 2.59 2.63 2.70
TC 7.73 7.73 7.71 7.69 7.67 7.61
6 PI 2.59 2.67 2.74 2.77 2.81 2.87
TC 8.58 8.52 8.44 8.39 8.33 8.26
10 PI 2.78 2.84 2.90 2.93 2.95 3.00
TC 9.07 8.95 8.89 8.89 8.88 8.73
PI 3.11 3.18 3.25 3.28 3.31 3.36
TC 10.31 10.18 10.12 10.11 10.10 9.93
PI 3.30 3.38 3.45 3.48 3.51 3.57
TC 11.17 11.03 10.96 10.96 10.94 10.76
15 PI 2.89 2.94 2.99 3.01 3.02 3.05
TC 9.84 9.81 9.83 9.76 9.68 9.57
PI 3.24 3.30 3.35 3.37 3.39 3.42
TC 11.19 11.16 11.18 11.10 11.01 10.88
PI 3.44 3.50 3.56 3.58 3.60 3.63
TC 12.12 12.09 12.11 12.03 11.93 11.79
PI 3.08 3.11 3.13 3.13 3.13 3.16
AS-W306DGM0 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 7.22 7.15 7.10 7.08 7.07 6.98
-10 PI 2.65 2.69 2.74 2.77 2.80 2.86
TC 7.59 7.58 7.58 7.58 7.58 7.51
-5 PI 2.59 2.65 2.72 2.75 2.79 2.87
TC 8.23 8.24 8.25 8.25 8.24 8.14
0 PI 2.71 2.78 2.86 2.90 2.94 3.03
TC 8.79 8.79 8.76 8.75 8.72 8.65
6 PI 2.91 2.99 3.07 3.11 3.15 3.22
TC 9.76 9.69 9.60 9.54 9.47 9.39
10
15 PI 3.45 3.49 3.51 3.51 3.51 3.54
AS-W366DGM0 Outdoor Air Temperature : °CWB
Indoor Air Temperature (°C) °CDB 16.0 18.0 20.0 21.0 22.0 24.0
-15 TC 7.82 7.74 7.69 7.67 7.66 7.56
-10 PI 2.81 2.85 2.91 2.94 2.97 3.04
TC 8.23 8.21 8.21 8.21 8.21 8.13
-5 PI 2.74 2.81 2.89 2.92 2.96 3.05
Symbol AFR : Air flow rate DB : Dry bulb temperature WB : Wet bulb temperature TC : Total capacity SHC : Sensible capacity PI : Power Input (Comp.+ indoor fan motor+outdoor fan motor)
TC 8.92 8.93 8.93 8.93 8.93 8.82
[m3/min] [°C] [°C] [kW] [kW] [kW]
0 PI 2.87 2.96 3.04 3.08 3.13 3.21
TC 9.52 9.52 9.50 9.47 9.45 9.37
6 PI 3.09 3.17 3.26 3.30 3.34 3.42
TC 10.57 10.50 10.40 10.33 10.26 10.18
10
15 PI 3.66 3.70 3.72 3.73 3.73 3.76
Notes 1. All capacities are net, evaporator fan motor heat is deducted. 2. Indicates nominal maximum capacity. 3. Direct interpolation is permissible. Do not extrapolate 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero. - Outdoor air : 85%RH. However, the condition on nominal capacity is 7°CDB/6°CWB
2008 Product Data
75
9. Capacity coefficient factor Cooling
Capacity(%)
100 30k/36k
24k 9k/12k/18k 90
80
70 7.5
15
30
50
Total Pipe Length(m)
Heating
Capacity(%)
100 9k/12k/18k
24k
30k/36k
90
80
70 7.5
15
Total Pipe Length(m)
76
2008 Product Data
30
50
9. Capacity coefficient factor Max. Pipe Length(m) 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 30 30 30 50 50
Model No. AS-W096ADR0 AS-W0964GG1 AS-W096E*H2 AS-W096E1G0 AS-W096F*G2 AS-W096F1G2 AS-W096U*H1 AS-W126ADR0 AS-W1264GG1 AS-W126E*H2 AS-W126E1G0 AS-W126F*G2 AS-W126F1G2 AS-W126U*H1 AS-W1863*H3 AS-W1865DH2 AS-W1865GG1 AS-W1868*H1 AS-W2463*H3 AS-W2465DH2 AS-W2468*H1 AS-W306DGM0 AS-W366DGM0 Indoor unit
Max. Elevation (m) 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 15 15 15 30 30
CAUTION:
Outdoor unit Outdoor unit
A B
A Outdoor unit
Indoor unit
Oil trap
B
Additional Refrigerant[g/m(oz/ft)] 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 20(0.22) 30(0.32) 30(0.32) 30(0.32) 30(0.32) 35(0.37)
A
Indoor unit
B
• Capacity is based on standard length and maximum allowance length is on the basis of reliability. • Oil trap should be installed every 5~7 meters.
If piping length is more than 5m
Notes ❈ Equivalent pipe length = actual pipe length + number of band x 0.3 ❈ Additional Refrigerant Charge Example: For Model No. AS-W126ADR0 having 15m pipe length, additional refrigerant to be charged is (15-7) x 20 = 160g * Refer to the specification for the maximum pipe length of each model. * 18k S5/S8 Chassis total piping length is 15m.
2008 Product Data
77
10. Operation range
Cooling
Heating
46
Operative
Outdoor Unit [°C DB]
24
Continuous operation Outdoor Unit [°C DB]
Warming up Operation
43
Continuous operation
-10
Operative
-10
-15 18 Indoor Unit [°C DB]
32
16
30
Indoor Unit [°C DB] Operative: Intermittent operation due to the operational conditions (indoor/outdoor temperature, humidity, load etc.) can cause the heating capacity to decrease.
78
2008 Product Data
11. Air flow and temperature distributions(reference data) General Wall Mouted 9kBtu/h Cooling
Heating
Discharge angle:45°
Discharge angle:50°
Air velocity [m/s]
2.7m
Air velocity [m/s]
2.7m
2m
2m 1.2 1.0
1.0 1m
0.75
1m
0.75 0.5
0.5 5m
4m
3m
2m
0m 0m
1m
Temperature [˚C]
2.7m
5m
4m
3m
2m
0m 0m
1m
Temperature [˚C]
2.7m
2m
23
5m
4m
25 3m
2m
1m
1m
28 29
24 2m
0m 0m
1m
5m
4m
3m
30 2m
0m 0m
1m
ART COOL Deluxe 9kBtu/h Cooling
Heating
Discharge angle:45°
Discharge angle:50°
Air velocity [m/s]
2.7m
Air velocity [m/s]
2.7m
2m
2m 1.2 1.0
1.0 1m
0.75
1m
0.75 0.5
0.5 5m
4m
3m
2m
0m 0m
1m
Temperature [˚C]
2.7m
5m
4m
3m
2m
1m
Temperature [˚C]
2.7m
2m
23
5m
4m
25 3m
2m
1m
1m
28 29
24 2m
1m
0m 0m
0m 0m
5m
4m
3m
30 2m
1m
0m 0m
2008 Product Data
79
11. Air flow and temperature distributions(reference data) ART COOL Deluxe 12kBtu/h Cooling
Heating
Discharge angle:45°
Discharge angle:50° Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m
2m
2m
1.2 1.0
1m
1.0
1m
0.75 0.5 5m
4m
3m
0.5
0.75
2m
1m
0m 0m
5m
4m
3m
2m
0m 0m
1m
Temperature [˚C]
Temperature [˚C]
23
2.7m
2.7m
2m
2m
30
1m
1m
29 24
25 5m
4m
3m
28
2m
1m
0m 0m
5m
4m
3m
2m
1m
0m 0m
ART COOL Standard 12kBtu/h Cooling
Heating
Discharge angle:45°
Discharge angle:45°
Air velocity [m/s]
2.7m
Air velocity [m/s]
2.7m
2m
2m
1.2 1.0
1m
1.0
1m
0.75 0.5 5m
4m
3m
0.75
2m
0.5
1m
Temperature [˚C]
0m 0m
2.7m
5m
4m
3m
2m
0m 0m
1m
Temperature [˚C]
2.7m
2m
23
2m
30
1m
1m
29 24
25 5m
80
4m
3m
2m
2008 Product Data
1m
0m 0m
28 5m
4m
3m
2m
1m
0m 0m
11. Air flow and temperature distributions(reference data) General Wall Mouted 12kBtu/h Cooling
Heating
Discharge angle:45°
Discharge angle:50° Air velocity [m/s]
Air velocity [m/s]
2.7m
2.7m
2m
2m 1.5
1.5 1.25
1.25 1.0
1.0 0.75
0.5 5m
4m
3m
2m
1m
5m
4m
3m
2m
0m 0m
1m
Temperature [˚C]
25 3m
2.7m
2m
2m
0m 0m
1m
1m
30 29
28
24 2m
2.7m
1m
23
4m
0.75
0.5 0m 0m
Temperature [˚C]
5m
1m
1m
5m
4m
3m
2m
1m
0m 0m
General Wall Mouted 18kBtu/h Cooling
Heating
Discharge angle:45°
Discharge angle:50°
Air velocity [m/s]
Air velocity [m/s]
1.5
8m
7m
6m
5m
4m
0.5 3m
2.7m
2.7m
2m
2m
1.25 0.75 1.0 2m
1m
0.5 0m
Temperature [˚C]
7m
6m
8m
7m
6m
5m
4m
3m
0.75 2m
1m
1.25 1.0 1m
0m
Temperature [˚C]
23
8m
1.5
1m
5m
25 4m
2.7m
2.7m
2m
2m 31
1m
24 3m
2m
29
28 1m
0m
8m
7m
6m
5m
4m
3m
2m
1m
30 1m
0m
2008 Product Data
81
12. Sound levels 12.1 Indoor Units Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20µPa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
1m 0.8m Microphone Sound Levels [dB(A)] H M L 22 31 27 25 32 28 22 31 27 22 31 27 25 35 29 25 35 29 28 34 32 22 36 27 25 38 30 22 37 27 22 37 27 25 39 32 25 39 32 28 35 33
Model AS-W096ADR0 AS-W0964GG1 AS-W096E*H2 AS-W096E1G0 AS-W096F*G2 AS-W096F1G2 AS-W096U*H1 AS-W126ADR0 AS-W1264GG1 AS-W126E*H2 AS-W126E1G0 AS-W126F*G2 AS-W126F1G2 AS-W126U*H1
Sound Levels [dB(A)] M H L 43 37 42 39 36 43 40 37 42 39 36 45 36 37 44 41 37 43 40 36 46 43 39 47 44 41
Model AS-W1863*H3 AS-W1865DH2 AS-W1865GG1 AS-W1868*H1 AS-W2463*H3 AS-W2465DH2 AS-W2468*H1 AS-W306DGM0 AS-W366DGM0
Sound Pressure Level AS-W096ADR0
AS-W096E1G0 AS-W096E*H2
AS-W096ADR0
80
80
80 High Middle Low
70
High Middle Low
70
NC-65
NC-65
50 NC-50
NC-45
40 NC-40
NC-35
30 NC-30
NC-25
20 Approximate Hearing Threshold
NC-55
50 NC-50
NC-40
NC-15
NC-30
10
500
1000
2000
4000
8000
Approximate Hearing Threshold 63
Octave Band Center Frequency (Hz)
80
NC-15
250
500
1000
2000
4000
NC-55
50
NC-50 NC-45
40 NC-40 NC-35
30
NC-30
NC-25
20
Approximate Hearing Threshold
NC-15
10 4000
8000
Octave Band Center Frequency (Hz)
2008 Product Data
NC-20 NC-15
10 63
8000
125
250
500
1000
2000
4000
8000
AS-W096U*H1 High Middle Low
High Middle Low
70
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30
NC-30
20
NC-25
Approximate Hearing Threshold
NC-20
2000
NC-25
NC-65
NC-65
Sound Pressure Level (dB re 20µPa )
Sound Pressure Level (dB re 20µPa )
NC-60
82
NC-30
Octave Band Center Frequency (Hz)
NC-65
1000
NC-35
80
70
60
500
NC-40
30
AS-W126ADR0 High Middle Low
250
NC-45
Appr oximate Hearing Thr eshold
80
70
125
NC-50
40
NC-20
125
NC-55
50
Octave Band Center Frequency (Hz)
AS-W096F1G2 AS-W096F*G2
63
NC-60
20
NC-25
60 NC-60
NC-55 50 NC-50
NC-15
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate Hearing Threshold
NC-20
10 63
Sound Pressure Level (dB re 20µPa )
250
NC-35
30
NC-20
125
NC-45
40
20
10 63
NC-60
Sound Pressure Level (dB re 20µPa )
NC-55
NC-65
60
60
Sound Pressure Level (dB re 20µPa )
Sound Pressure Level (dB re 20µPa )
60 NC-60
High Middle Low
70
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
12. Sound levels AS-W126E1G0 AS-W126E*H2
AS-W126F1G2 AS-W126F*G2
80
AS-W1264GG1 80
80
High Middle Low
70
NC-60
NC-55
50
NC-50 NC-45
40
NC-40
NC-35
30
NC-30
20
63
NC-60
NC-50 NC-45
40 NC-40
NC-30
500
1000
2000
4000
NC-25
Approximate Hearing Threshold
NC-15
250
NC-35
30
NC-20
125
NC-55
50
63
Octave Band Center Frequency (Hz)
125
250
500
1000
2000
4000
NC-50 NC-45
40 NC-40 NC-35
30
NC-30
NC-25
Approximate Hearing Threshold
80
63
NC-15
125
NC-50 NC-45
40 NC-40
NC-35
30
NC-30
4000
8000
High Middle Low
NC- 65
NC-65
Sound Pressure Level (dB re 20µPa )
NC-55
2000
70
60
50
1000
80 High Middle Low
70
NC-60
500
AS-W1865GG1 AS-W1863*H3
NC-65
60
250
Octave Band Center Frequency (Hz)
80 High Middle Low
NC-60
NC-55
50
NC-50 NC-45
40
NC-40
NC-35
30
NC-30
60 NC- 60 NC- 55
50 NC- 50 NC- 45
40 NC- 40 NC- 35
30
NC- 30
NC-25
20
20
Approximate Hearing Threshold
NC-25
NC-20
Approximate Hearing Threshold
NC-15
10 63
125
250
500
1000
2000
4000
8000
Appr oximate Hear ing Threshold
NC-15
63
125
250
500
1000
2000
4000
NC- 25
20
NC-20
10
Octave Band Center Frequency (Hz)
AS-W2463*H3
63
AS-W2465DH2 High Middle Low
High Middle Low
NC-65
NC-50
NC-45 40 NC-40
NC-35
30
NC-30
20
NC-25
Appr oximate Hearing Thr eshold
NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-15 125
250
500
1000
2000
4000
8000
NC-35
30
2000
4000
8000
High Middle Low
70
NC-65
60 NC-60
NC-55
50
NC-50 NC-45
40
NC-40
NC-35
30
NC-30
NC-30
20
NC-25
Approximate Hearing Threshold
NC-20
10 63
Sound Pressure Level (dB re 20µPa )
NC-55
1000
NC-65
60
60
50
500
AS-W2468*H1
70
NC-60
NC- 15
250
80
Sound Pressure Level (dB re 20µPa )
70
125
Octave Band Center Frequency (Hz)
80
80
NC- 20
10
8000
Octave Band Center Frequency (Hz)
Sound Pressure Level (dB re 20µPa )
NC-20
10
8000
AS-W1865DH2 AS-W1868*H1
70
NC-55
Octave Band Center Frequency (Hz)
AS-W126U*H1
Sound Pressure Level (dB re 20µPa )
NC-60
50
20
NC-15
10
8000
60
NC-20
Sound Pressure Level (dB re 20µPa )
10
60
20
NC-25
Approximate Hearing Threshold
NC-65
NC-65
Sound Pressure Level (dB re 20µPa )
Sound Pressure Level (dB re 20µPa )
NC-65
60
High Middle Low
70
Sound Pressure Level (dB re 20µPa )
70
High Middle Low
NC-15
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-25
Approximate Hearing Threshold
NC-20
10 63
20
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
2008 Product Data
83
12. Sound levels AS-W366DGM0
Sound Pressure Level (dB re 20µPa )
Sound Pressure Level (dB re 20µPa )
AS-W306DGM0
Octave Band Center Frequency (Hz)
84
2008 Product Data
Octave Band Center Frequency (Hz)
12. Sound levels 12.2 Outdoor Units Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20µPa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
Center of Outdoor Unit
1m
1m
Sound Levels [dB(A)] H 45 45 45 45 48 48 48 45 45 45 45 48 48 48
Model AS-W096ADR0 AS-W0964GG1 AS-W096E*H2 AS-W096E1G0 AS-W096F*G2 AS-W096F1G2 AS-W096U*H1 AS-W126ADR0 AS-W1264GG1 AS-W126E*H2 AS-W126E1G0 AS-W126F*G2 AS-W126F1G2 AS-W126U*H1
Sound Pressure Level
AS-W1863*H3 AS-W1865DH2 AS-W1865GG1 AS-W1868*H1 AS-W2463*H3 AS-W2465DH2 AS-W2468*H1 AS-W306DGM0 AS-W366DGM0
AS-W096E1G0 AS-W096E*H2 AS-W096U*H1
AS-W096ADR0
AS-W096F1G2 AS-W096F*G2
80
80
80
70
70
70
NC-65
NC-65
NC-50 NC-45
40
NC-40
NC-35
30
NC-30
20
63
NC-50
NC-45
40 NC-40
NC-30
250
500
1000
2000
4000
NC-25
Approximate Hearing Threshold
NC-15
125
NC-35
30
NC-20
10
NC-55
50
20
NC-25
Approximate Hearing Threshold
60 NC-60
10
8000
Sound Pressure Level (dB re 20µPa )
NC-55
50
Sound Pressure Level (dB re 20µPa )
NC-60
NC-60
NC-55
50 NC-50 NC-45
40 NC-40
NC-30
250
500
1000
2000
4000
8000
NC-25
20
Approximate Hearing Threshold
NC-20
125
NC-35
30
NC-15
63
Octave Band Center Frequency (Hz)
63
80
70
70
NC-40
NC-35
30
NC-30
20
NC-25
Approximate Hearing Threshold
NC-15
63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
4000
8000
NC-65
60 NC-60
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30 NC-30
20
NC-25
Approximate Hearing Threshold
NC-20
10
2000
70
NC-60
NC-55
50 NC-50
NC-15
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20 Approximate Hearing Threshold
NC-20
10 63
Sound Pressure Level (dB re 20µPa )
NC-45
Sound Pressure Level (dB re 20µPa )
NC-50
40
1000
80
60
50
500
AS-W126E1G0 AS-W126E*H2
NC-65
NC-55
250
NC-65
60 NC-60
NC-15
125
Octave Band Center Frequency (Hz)
AS-W126ADR0
80
NC-20
10
Octave Band Center Frequency (Hz)
AS-W0964GG1
Sound Pressure Level (dB re 20µPa )
NC-65
60
60
Sound Pressure Level (dB re 20µPa )
Sound Levels [dB(A)] H 57 55 56 54 57 56 55 54 58
Model
NC-20 NC-15
10 63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
2008 Product Data
85
12. Sound levels AS-W126F1G2 AS-W126F*G2 AS-W126U*H1
AS-W1264GG1
AS-W1863*H3
80
80
80
70
70
70
50 NC-50 NC-45
40 NC-40
NC-35
30
NC-30
NC-25
Approximate Hearing Threshold
NC-60 NC-55
50 NC-50 NC-45
40 NC-40
30
NC-30
Approximate Hearing Threshold
NC-15
63
125
250
500
1000
2000
4000
NC-55
NC-50
NC-45
40 NC-40
NC-30
63
125
250
500
1000
2000
4000
NC-25
20 Approximate Hearing Threshold
NC-15
10
8000
NC-35
30
NC-20
Octave Band Center Frequency (Hz)
10
8000
AS-W1865DH2 80
70
70
70
NC-35
30
NC-30
NC-25
20
Approximate Hearing Threshold 63
NC-55
50 NC-50
NC-45
40 NC-40
NC-35
30 NC-30
Approximate Hearing Threshold
NC-15
125
250
500
1000
2000
4000
NC-25
20
NC-20
10
8000
NC-55
NC-50
NC-45 40 NC-40
NC-35 30 NC-30
125
250
500
1000
2000
4000
Approximate Hearing Threshold
70
70
70
NC-65
NC-45
NC-40
NC-35
NC-30
NC-25
20
Approximate Hearing Threshold 125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
86
2008 Product Data
NC-55
50
NC-50 NC-45
40
NC-40
NC-35
30
NC-30
20
NC-25
Approximate Hearing Threshold
NC-20 NC-15
10 63
NC-60
NC-15
125
250
500
1000
1000
2000
4000
8000
2000
4000
Octave Band Center Frequency (Hz)
8000
NC-65 NC-60 NC-55
50
NC-50 NC-45
40
NC-40 NC-35
30
NC-30 NC-25
20
NC-20
10 63
Sound Pressure Level (dB re 20µPa )
NC-50
500
60
60
Sound Pressure Level (dB re 20µPa )
50
250
AS-W2468*H1 80
NC-65
125
Octave Band Center Frequency (Hz)
AS-W2465DH2
30
NC-15 63
8000
80
60
NC-20
10
80
40
NC-25
20
NC-15
63
AS-W2463*H3
8000
50
Octave Band Center Frequency (Hz)
NC-55
4000
NC-60
NC-20
10
Octave Band Center Frequency (Hz)
NC-60
2000
60 NC-60
Sound Pressure Level (dB re 20µPa )
NC-40
Sound Pressure Level (dB re 20µPa )
NC-45
40
1000
NC-65
60
NC-50
500
NC-65
NC-65
60
50
250
AS-W1865GG1
80
NC-55
125
Octave Band Center Frequency (Hz)
80
NC-60
NC-20 NC-15
63
Octave Band Center Frequency (Hz)
AS-W1868*H1
Sound Pressure Level (dB re 20µPa )
NC-60
50
NC-25
20
NC-20
10
NC-35
Sound Pressure Level (dB re 20µPa )
NC-55
Sound Pressure Level (dB re 20µPa )
Sound Pressure Level (dB re 20µPa )
60
60 NC-60
20
Sound Pressure Level (dB re 20µPa )
NC-65
NC-65
NC-65
60
10
Approximate Hearing Threshold
63
NC-20 NC-15
125
250
500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
12. Sound levels
AS-W366DGM0
Sound Pressure Level (dB re 20µPa )
Sound Pressure Level (dB re 20µPa )
AS-W306DGM0
Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
2008 Product Data
87
13. Remote controller Models: AS-W096E*H2/AS-W126E*H2/AS-W096F1G2/AS-W126F1G2/ AS-W096F*G2/AS-W126F*G2/AS-W1868*H1/AS-W2468*H1 The controls will look like the following. 1. ON/OFF BUTTON Used to turn off/on the unit.
Signal transmitter
2. OPERATION MODE SELECTION BUTTON Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4. INDOOR FAN SPEED SELECTOR BUTTON Used to select fan speed in four steps low, medium, high and CHAOS. 5. JET COOL BUTTON Used to start or stop the speed cooling. (It operates fan in super high speed in cooling mode) 14
1
10
4 3
2 5 17 8 13 9 15
7. TIMER AND TIME SETTING BUTTON Used to set the time of starting and stopping operation.
18 6 7
8. TIME SETTING BUTTONS Used to adjust the time.
11 16
9. TIMER SET / CLEAR BUTTON Used to set and to cancel the timer operation.
8
10. SLEEP MODE AUTO BUTTON Used to set sleep mode auto operation.
12
11. ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 12. RESET BUTTON Used prior to resetting time.
Operation Mode
13. AUTO CLEAN BUTTON Used to set auto clean mode.
Cooling Operation Auto Operation or Auto Changeover
14. PLASMA BUTTON Used to start or stop the plasma-purification function.
Healthy Dehumidification Operation
15. CLEAR ALL BUTTON Used to cancel all timer setting. 16. ENERGY SAVING COOLING BUTTON(OPTIONAL) Used to save Energy.
Heating Operation
17. LCD LUMINOSITY BUTTON(OPTIONAL) Used to adjust LCD luminosity.
Air Circulation
• Cooling Model(
88
6. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction.
), Heat Pump Model(
2008 Product Data
)
18. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL) Used to set the desired horizontal airflow direction.
13. Remote controller Models: AS-W096ADR0/AS-W126ADR0 The controls will look like the following. Signal transmitter
1. ON/OFF BUTTON Used to turn off/on the unit. 2. OPERATION MODE SELECTION BUTTON Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4. INDOOR FAN SPEED SELECTOR BUTTON Used to select fan speed in four steps low, medium, high and CHAOS.
14 10
2 5 17 8 13 9 15
Operation Mode
1
5. JET COOL BUTTON Used to start or stop the speed cooling. (It operates fan in super high speed in cooling mode)
4 3
6. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction.
18 6 7
7. TIMER AND TIME SETTING BUTTON Used to set the time of starting / stopping and sleeping operation
11 16
8. TIME SETTING BUTTONS Used to adjust the time.
8
9. TIMER SET / CLEAR BUTTON Used to set and to cancel the timer operation.
12
10. SLEEP MODE AUTO BUTTON Used to set sleep mode auto operation. 11. ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 12. RESET BUTTON Used prior to resetting time.
Cooling Operation Auto Operation or Auto Changeover
13. FUNCTION SETTING BUTTON Used to set auto clean and smart clean mode regularly.
Healthy Dehumidification Operation
14. SMART CLEAN BUTTON Used to start or stop the smart clean function. 15. CLEAR ALL BUTTON Used to cancel all timer setting.
Heating Operation
16. ENERGY SAVING COOLING BUTTON Used to save Energy.
Air Circulation
• Cooling Model(
), Heat Pump Model(
)
17. LED LUMINOSITY BUTTON Used to adjust bruch and display LED luminosity. 18. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON Used to set the desired horizontal airflow direction.
2008 Product Data
89
13. Remote controller Wireless Remote Controller The controls will look like the following. Signal transmitter
5
1
6 3 4 10
2 7 11 8 13
9 12 17 19 18 14
15
11.
16
Flip-up door (opened)
Operation Mode Cooling Operation Auto Operation or Auto Changeover
Healthy Dehumidification Operation Heating Operation
• Cooling Model(
), Heat Pump Model(
1. START/STOP BUTTON Used to turn off/on the unit. 2. OPERATION MODE SELECTION BUTTON Used to select the operation mode. 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. 4. INDOOR FAN SPEED SELECTOR BUTTON Used to select fan speed in four steps low, medium, high and CHAOS. 5. JET COOL BUTTON Used to start or stop the speed cooling. (It operates fan in super high speed in cooling mode) 6. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction. 7. ON/OFF TIMER BUTTONS Used to set the time of starting and stopping operation. 8. TIME SETTING BUTTONS Used to adjust the time. 9. TIMER SET/CANCEL BUTTON Used to set and to cancel the timer operation. 10. SLEEP MODE AUTO BUTTON Used to set sleep mode auto operation.
)
AIR CIRCULATION BUTTON(OPTIONAL) Used to circulate the room air without cooling or heating. ENERGY-SAVING COOLING MODE BUTTON (OPTIONAL) For inverter type models 12. ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 13. PLASMA BUTTON(OPTIONAL) Used to start or stop the plasma-purification function. 14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL) Used to set the desired horizontal airflow direction. 15. RESET BUTTON Used prior to resetting time. 16. 2nd F BUTTON Used prior to using modes printed in blue at the bottom of buttons. 17. AUTO CLEAN BUTTON(OPTIONAL) Used to set auto clean mode. In some models this button has a 2nd function of LED luminosity control. 18. HEATER BUTTON(OPTIONAL) (Not available in all models) 19. LCD LUMINOSITY BUTTON(OPTIONAL) Used to adjust LCD luminosity.
NOTE To use the functions printed in blue at the bottom of the buttons press 2nd F button first and then the required function button. Pressing the 2nd F button activates the blue printed function of the respective button. To cancel the function press the 2nd F button again else it will automatically cancel if remains idle after 10 seconds.
90
2008 Product Data
14. Installation Installation Map
NOTICE Installation parts you should purchase.
Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break.
Air Discarge Vertical Air deflector Operation Indication Lamps
Vinyl tape (Wide)
Forced Operation Button
Saddle
• Apply after carrying out a drainage test. • To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Air Inlet Vents
Gas side piping (Optional Parts) Liquid side piping (Optional Parts) Additional drain pipe
Air Outlet Vents
Base Plate
Vinyl tape (Narrow) Drain Hose Connecting cable (Optional Parts)
2008 Product Data
91
14. Installation Select the best Location Indoor unit 1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit.
More than 100mm
More than 200mm
3. Make sure that condensation drainage can be conveniently routed away. More than 100mm
4. Do not install near a doorway. 5. Ensure that the interval between a wall and the left (or right) of the unit is more than 100mm. The unit should be installed as high as possible on the wall, allowing a minimum of 200mm from ceiling.
More than 2300mm
6. Use a metal detector to locate studs to prevent unnecessary damage to the wall.
Install the indoor unit on the wall where the height from the floor is more than 2.3 meters.
Outdoor unit 1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. 2. Ensure that the space around the back and sides is more than 300mm. The front of the unit should have more than 700mm of space.
More than 600mm
More than 300mm
3. Do not place animals and plants in the path of the warm air. 4. Take the weight of the air conditioner into account and select a place where noise and vibration are minimum. 5. Select a place where the warm air and noise from the air conditioner do not disturb neighbors.
92
2008 Product Data
More than 700mm
More than 300mm
More than 600mm
14. Installation Fixing Installation Plate The wall you select should be strong and solid enough to prevent vibration 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level.
Installation Plate
Chassis Hook
Type “A”
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
Drill a Hole in the Wall • Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
WALL
(3/16"~5/16")
Outdoor
5-7mm
Indoor
Flaring Work Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.
Copper pipe
90°
Slanted Uneven Rough
1. Use the piping kit accessory or the pipes purchased locally. 2. Measure the distance between the indoor and the outdoor unit. 3. Cut the pipes a little longer than measured distance. 4. Cut the cable 1.5m longer than the pipe length.
2008 Product Data
93
14. Installation Burrs removal
Pipe
1. Completely remove all burrs from the cut cross section of pipe/tube.
Reamer
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Point down
Putting nut on
Flare nut
• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Copper tube
1. Firmly hold copper pipe in a bar in the dimension shown in the table below. 2. Carry out flaring work with the flaring tool. Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4
A mm 1.1~1.3 1.5~1.7 1.6~1.8 1.6~1.8 1.9~2.1
Check
Bar
Cone Copper pipe Clamp handle
Red arrow mark
Smooth all round Inside is shiny without scratches
2. If a flared section is defective, cut it off and do flaring work again.
= Improper flaring =
Even length all round
2008 Product Data
Bar Yoke
1. Compare the flared work with the figure by.
94
Handle
"A"
Flaring work
Inclined Surface Cracked Uneven damaged thickness
14. Installation Connecting the Piping Indoor 1. Prepare the indoor unit's piping and drain hose for installation through the wall. 2. Pull the plastic tubing cover(see the illustration by) and pull the tubing and drain hose away from chassis.
2
1
For right rear piping 1. Route the indoor tubing and the drain hose in the direction of rear right. 2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole. • Do not connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later. 3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the uper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
Drain hose
Tape Connecting pipe Drain hose
Connecting cable
4. Indoor unit installation Hook the indoor unit onto the upper portion of the installation plate.(Engage the hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Connecting cable
Drain hose
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
2008 Product Data
95
14. Installation For left rear piping 1. Route the indoor tubing and the drain hose to the required piping hole position.
1
2
2. Insert the piping, drain hose, and the connecting cable into the piping hole. Drain pipe
3. Insert the connecting cable into the indoor unit. • Don't connect the cable to the indoor unit. • Make a small loop with the cable for easy connection later.
Connecting cable
4. Tape the drain hose and the connecting cables.
5. Indoor unit installation • Hang the indoor unit from the hooks at the top of the installation plate. • Mount the tubing cover between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Indoor unit Tubing cover Installation plate 8cm
Connecting the piping to the indoor unit and drain hose to drain pipe. 1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
Indoor unit tubing
Flare nut
Pipes
2. Tighten the flare nut with a wrench. Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8
Torque kgf.m 1.8~2.5 3.4~4.2 5.5~6.6 6.3~8.2
3. Mount the clamp on the boss with a type "B" screw.(optional) 4. When extending the drain hose at the indoor unit, install the drain pipe.
96
2008 Product Data
Open-end wrench (fixed) Flare nut Wrench
Connection pipe
Indoor unit tubing
Type "B" screw Clamp Boss
Drain hose
14. Installation Wrap the insulation material around the connecting portion. 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
Drain pipe
Indoor unit drain hose Vinyl tape(narrow)
Adhesive
2. Wrap the area which accommodates the rear piping housing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Insulation material
Indoor unit pipe
Connection pipe
Wrap with vinyl tape Vinyl tape (wide) Connecting cable Pipe Vinyl tape(narrow)
Wrap with vinyl tape Pipe
Vinyl tape(wide) Drain hose
Reroute the pipings and the drain hose across the back of the chassis.
Piping for passage through piping hole
Indoor unit installation 1. Mount the tubing cover in the original positon. 2. Ensure that the hooks are properly seated on the installation plate by moving it left and right. 3. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Connecting cable
Drain hose
2008 Product Data
97
14. Installation
Installation Information. For left piping. Follow the instruction below.
Good case • Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case • Following bending type from right to left may cause damage to the tubing.
98
2008 Product Data
14. Installation Outdoor Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks. • When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Ø19.05 3/4
Torque kgf.m 1.8~2.5 3.4~4.2 5.5~6.5 6.3~8.2 9.9~12.1
Outdoor unit
Liquid side piping (Smaller diameter)
Torque wrench Gas side piping (Bigger diameter)
2008 Product Data
99
14. Installation Connecting the Cables Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
• The circuit diagram is subject to change without notice. • The earth wire should be longer than the common wires. • When installing, refer to the circuit diagram on the front panel. • Connect the wires firmly so that they may not be pulled out easily. • Connect the wires according to color codes, referring to the wiring diagram. Main power source
If a power plug is not used, provide a circuit breaker between power source and the unit as shown by.
Circuit Breaker Use a circuit breake or time delay fuse.
Air Conditioner
The power cord connected to the Indoor unit should be selected according to the following specifications(Type "B" approved by HAR or SAA). (mm2)
45
10
Grade NORMAL CROSS -SECTIONAL AREA Cable Type(B)
9k~12k
±5 ±3
12k SU / 18k 18k S3 / 24k~36k
1.0
1.5
2.5
H05VV-F
H05VV-F
H05VV-F
The power connecting cable connecting the indoor and outdoor unit should be selected according to the following specifications (Type "B" approved by HAR or SAA). (mm2) 45
Grade NORMAL CROSS -SECTIONAL AREA
9k S4 / 12k S4 9k~18k 18k S3 / 24k 30k~36k 1.0
Cable Type(B)
100
1.5
2.5
0.75
H07RN-F H07RN-F H07RN-F H07RN-F
2008 Product Data
±5 10
±3
14. Installation Outdoor 1. Remove the control cover from the unit by loosening the screw. Connect the wires to the terminals on the control board individually.
Outdoor Unit
1(L) 2(N) 3
2. Secure the cable onto the control board with the cord clamp. 3. Refix the control cover to the original position with the screw. 4. Use a recognized circuit breaker between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted. Circuit Breaker (A)
Connecting cable
Cord clamp
Cover control
Grade 9k~12k 18k S5 15
18k
24k
30k~36k
20
30
25
According to the confirmation of the above conditions, prepare the wiring as follows. 1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover. 2. The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.) 3. Specification of power source. 4. Confirm that electrical capacity is sufficient. 5. See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 6. Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. 7. Always install an earth leakage circuit breaker in a wet or moist area. 8. The following would be caused by voltage drop. • Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.
9. The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
2008 Product Data
101
14. Installation Checking the Drainage To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Connecting area drain hose
Leakage checking
Drain piping 1. The drain hose should point downward for easy drain flow.
Downward slope
2. Do not make drain piping like the following. Accumulated drain water Air
Do not raise
Water leakage
102
2008 Product Data
Water leakage
Waving
Tip of drain hose dipped in water Water leakage
Ditch
Less than 50mm gap
14. Installation Forming the Piping Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes. • If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
Pipe Drain hose Vinyl tape(narrow)
Wrap with vinyl tape(wide)
In cases where the outdoor unit is installed below the indoor unit perform the following. 1. Tape the piping, drain hose and connecting cable from down to up. 2. Secure the tapped piping along the exterior wall using saddle or equivalent.
In cases where the Outdoor unit is installed above the Indoor unit perform the following. 1. Tape the piping and connecting cable from down to up. 2. Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room. 3. Fix the piping onto the wall by saddle or equivalent.
2008 Product Data
103
14. Installation Air Purging Air purging The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5. Water may lead to corrosion of parts in the refrigeration system. Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
Air purging with vacuum pump 1. Preparation • Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage. 2. Leak test • Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses. Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close. • Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap. To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position. 1. Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth. 2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Indoor unit
Manifold valve Pressure gauge Lo Hi
Charge hose
Nitrogen gas cylinder(in vertical standing position) Outdoor unit
104
2008 Product Data
14. Installation Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. 3. To open the 2-way valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 sec, and close it. 4. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. 5. If bubbles come out, the pipes have leakage
Gas side
Liquid side Hexagonal wrench
2-way valve (Open)
Evacuation 1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
Cap
3-way valve (Close)
Indoor unit
Required time for evacuation when 30 gal/h vacuum pump is used If tubing length is less than 10m (33 ft) 10 min. or more
If tubing length is longer than 10m (33 ft) 15 min. or more
2. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job 1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve. 2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve. 3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose. 4. Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system. 5. Replace the valve caps at both gas and liquid side service valves and fasten them tight. This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
Outdoor unit
Manifold valve Pressure gauge
Lo
Hi
Close
Open
Vacuum pump
2008 Product Data
105
14. Installation Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open.
Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction. 2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly. 3. Reattach the cover by pushing it back into position.
NOTICE • Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries. • Remove the batteries from the remote controller if the system is not used for a long time.
Settlement of outdoor unit 1. Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount. 2. When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake. 3. If the vibration of the unit is transmitted to the hose, secure the unit with an anti-vibration rubber.
Bolt
Tubing connection
Evaluation of the performance Operate the unit for 15~20 minutes, then check the system refrigerant charge:
Intake temperature
1. Measure the pressure of the gas side service valve. 2. Measure the temperature of the intake and discharge of air.
Discharge air
3. Ensure the difference between the intake temperature and the discharge is more than 8°C 4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
Discharge temperature
The air conditioner is now ready for use. ambient Refrigerant Outside TEMP. R410A 35°C (95°F)
106
2008 Product Data
The pressure of the gas side service valve. 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
14. Installation NOTICE If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
PUMP DOWN This is performed when the unit is relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.
Be sure to perform Pump Down procedure in the cooling mode.
Pump Down Procedure 1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve. 2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant. 3. Close the liquid side service valve(all the way). 4. Turn on the unit's operating switch and start the cooling operation. 5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected into the outdoor unit.
2008 Product Data
107
14. Installation 14.1. Installation Guide at the Seaside CAUTION 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit) 1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
Sea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
• It should be strong enough like concrete to prevent the sea wind from the sea. • The height and width should be more than 150% of the outdoor unit.
Sea wind
• It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
108
2008 Product Data
P/No.: 3828A20892L
Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com
All rights reserved Printed in Korea Mar./2008 The specifications, designs, and information in this brochure are subject to change without notice.
File No. : A8974 Volume:1
Certificate No. : E00626/1
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.