EEDEN08-720
technical data
Altherma
ERHQ006-008AD EKHBH/X008AA ERHQ011-016AA EKHBH/X016AB EKHWS(U) EKSOL
Altherma ERHQ006-008AD EKHBH/X008AA ERHQ011-016AA EKHBH/X016AB EKHWS(U) EKSOL
Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
“The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”
Naamloze Vennootschap Zandvoordestraat 300 B-8400 Ostend, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende
EEDEN0 8 - 7 2 0
EEDEN08-720 - 02/2008 Printed in Belgium by Goekint Graphics Copyright © Daikin
Daikin units comply with the European regulations that guarantee the safety of the product.
EEDEN08-720
technical data Altherma
ERHQ006-008AD EKHBH/X008AA ERHQ011-016AA EKHBH/X016AB EKHWS(U) EKSOL
• • R-410A • ALTHERMA
rA e0 h1 t4 l- RA
Heating only
Heat pump 4
• Altherma •
EEDEN08-720
technical data Altherma
Part 1/3: ERHQ006-008AD EKHBH/X008AA
• Outdoor units • R-410A • ERHQ006-008AD
TABLE OF CONTENTS ERHQ006-008AD
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heating/ Cooling capacity tables
4
12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 13 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13 14
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Wiring diagram
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• Altherma • Outdoor units
17
7
• Outdoor units • R-410A • ERHQ006-008AD
1 D iA n8 0u 0 a - r m 6 o rA0 o e0 dh1Q t4H uRl- EA•OR
1
•
Features Cost effective alternative to a fossil fuel boiler
•
Easy to install
Low energy bills and low CO2 emissions
•
Total solution for year round comfort
1
8
• Altherma • Outdoor units
• Outdoor units • R-410A • ERHQ006-008AD
2
Specifications
2-1 NOMINAL CAPACITY AND NOMINAL INPUT Indoor Units Condition 1
Heating capacity Heating PI
Condition 2
ERHQ006AD
ERHQ007AD
ERHQ008AD
EKHBH008AA
EKHBH008AA
EKHBH008AA
Minimum
kW
4.36
4.36
4.36
Nominal
kW
5.75
6.84
8.43
Maximum
kW
7.45
8.79
9.58
Nominal
kW
1.26
1.58
2.08 4.05
COP
Nominal
4.56
4.34
Heating
Minimum
kW
3.87
3.87
3.87
Nominal
kW
5.03
6.10
7.64
Maximum
kW
6.68
7.98
8.76
Heating PI
Nominal
kW
1.58
1.95
2.54
COP
Nominal
3.18
3.13
3.00
Notes
Condition 1: cooling Ta 35°C - LWE 18°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 35°C ( DT = 5°C )
Notes
Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
2-1 NOMINAL CAPACITY AND NOMINAL INPUT Indoor Units Condition 1
Heating capacity
Cooling capacity
Condition 2
Minimum
kW
ERHQ006AD
ERHQ007AD
ERHQ008AD
EKHBX008AA
EKHBX008AA
EKHBX008AA
4.36
4.36
4.36
Nominal
kW
5.75
6.84
8.43
Maximum
kW
7.45
8.79
9.58
Minimum
kW
4.82
4.82
4.82
Nominal
kW
7.20
8.16
8.37
Maximum
kW
7.20
8.50
8.91
Heating PI
Nominal
kW
1.26
1.58
2.08
Cooling PI
Nominal
kW
2.27
2.78
2.97
COP
Nominal
4.56
4.34
4.05
EER
Nominal
3.17
2.94
2.82
Heating
Minimum
kW
3.87
3.87
3.87
Nominal
kW
5.03
6.10
7.64
Maximum
kW
6.68
7.98
8.76
Minimum
kW
3.67
3.67
3.67
Nominal
kW
5.12
5.86
6.08
Cooling
Maximum
kW
5.12
6.13
7.10
Heating PI
Nominal
kW
1.58
1.95
2.54
Cooling PI
Nominal
kW
2.16
2.59
2.75
COP
Nominal
3.18
3.13
3.00
EER
Nominal
2.37
2.26
2.21
Notes
Condition 1: cooling Ta 35°C - LWE 18°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 35°C ( DT = 5°C )
Notes
Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C ) - heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
2-2 TECHNICAL SPECIFICATIONS Casing
Colour
Dimensions
Unit
ERHQ006AD
Weight Packing
ERHQ008AD
Polyester painted galvanised steel Height
mm
Width
mm
797 960
Depth
mm
390 735
Height
mm
Width
mm
825
Depth
mm
300
Unit
kg
56
Packed Unit
kg
61
Material
EPS
Material
Carton
Weight
2
Ivory white
Material
Packing
ERHQ007AD
1
kg
• Altherma • Outdoor units
5
9
• Outdoor units • R-410A • ERHQ006-008AD
2
1
Specifications
2-2 TECHNICAL SPECIFICATIONS Heat Exchanger Specifications
2
Length
ERHQ006AD
845
mm
1.8
Nr of Rows Fin Pitch Nr of Stages
32 Hi-Xa(8)
Type
WF fin
Treatment Fan
Anti-corrosion treatment (PE)
Type
Propeller
Quantity Motor
1 Quantity Output
Compressor
1 W
53
Quantity Motor
1 Model
2YC63BXD#C
Type Operation Range
Sound Level (nominal)
Hermetically sealed swing compressor
Motor Output
W
Min
°CWB
Max
°CWB
25
Cooling
Min
°CDB
10
Max
°CDB
43
Sanitary water
Min
°CDB
-20
Max
°CDB
Sound Power
dBA
61
61
62
Sound Pressure
dBA
48
48
49
Sound Power
dBA
63
63
63
Sound Pressure
dBA
48
48
50
Heating
Heating Cooling
Refrigerant
Type kg
Control Type
Piping Connections
Liquid
Type
Flare connection mm
Type
6.35 Flare connection
mm
Quantity
15.9 1
Type Piping Length
1.7 1
Diameter (OD) Drain
43
FVC50K Diameter (OD)
Gas
-20
Expansion valve(electronic type)
Nr of Circuits Refrigerant Oil
1,920
R-410A
Charge
Socket
Diameter (OD)
mm
Minimum
m
3
Maximum
m
30
Additional Refrigerant Charge
kg/m
Installation Maximum height difference
m
18
0.02>10m 20
Defrost Method
Reverse cycle
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Standard Accessories
Installation manual
Standard Accessories
10
ERHQ008AD
2
Tube type Fin
ERHQ007AD
mm
Item Quantity
1
Item
Drain plug
Quantity
1
Notes
See operation range drawing
Notes
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information.
• Altherma • Outdoor units
• Outdoor units • R-410A • ERHQ006-008AD
2
Specifications
2-3 ELECTRICAL SPECIFICATIONS Power Supply
V3
Phase
1~
Frequency
Hz
50
Voltage
V
230
Starting current Maximum running Current
Wiring Connections
ERHQ007AD
Name
Voltage Range Current
ERHQ006AD
Minimum
V
-10%
Maximum
V
+10%
Heating
A
11
Cooling
A
11
Heating
A
18
Cooling
A
16.25
Minimum Ssc value
kVA
Recommended fuses
A
1 2
Equipment complying with EN/IEC 61000-3-12 20
For power supply Quantity
3
For connection with indoor
Quantity
4
Remark
Included earth wiring
• Altherma • Outdoor units
ERHQ008AD
11
• Outdoor units • R-410A • ERHQ006-008AD
3
Capacity tables
3-1
Heating/ Cooling capacity tables
COOLING
1
Model
3 006
007
008
Tamb (°C) LWE (°C) 7 11 13 16 20 7 11 13 16 20 7 11 13 16 20
20 CC 6.01 6.81 7.23 7.88 8.80 7.15 8.09 8.57 9.33 10.4 8.24 9.26 9.79 10.6 11.7
25 PI 1.56 1.57 1.57 1.56 1.55 2.05 2.09 2.11 2.13 2.16 2.43 2.49 2.52 2.57 2.63
CC 5.73 6.50 6.90 7.54 8.42 6.84 7.73 8.20 8.92 9.9 7.90 8.87 9.38 10.17 11.3
30 PI 1.75 1.77 1.78 1.78 1.79 2.28 2.34 2.36 2.40 2.44 2.68 2.76 2.80 2.86 2.94
CC 5.43 6.17 6.56 7.17 8.03 6.50 7.34 7.79 8.49 9.48 7.52 8.45 8.93 9.69 10.75
35 PI 1.95 1.98 2.00 2.01 2.03 2.52 2.59 2.63 2.68 2.73 2.94 3.05 3.10 3.17 3.26
CC 5.12 5.83 6.20 6.79 7.63 6.13 6.94 7.36 8.03 8.99 7.10 7.79 8.14 8.68 9.39
40 PI 2.16 2.21 2.23 2.26 2.29 2.77 2.87 2.91 2.97 3.04 3.23 3.31 3.36 3.41 3.48
CC 4.80 5.30 5.56 5.95 6.48 5.35 5.84 6.09 6.46 6.96 5.68 6.12 6.34 6.67 7.09
43 PI 2.39 2.32 2.28 2.22 2.13 2.68 2.62 2.59 2.53 2.44 2.86 2.80 2.77 2.71 2.61
CC 4.59 4.98 5.18 5.46 5.82 4.89 5.21 5.36 5.57 5.82 4.87 5.18 5.33 5.55 5.80
PI 2.53 2.38 2.30 2.18 1.99 2.59 2.43 2.34 2.20 1.99 2.59 2.43 2.35 2.20 1.99
HEATING (Peak values)
Model
006
007
008
LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7
30 HC 3.93 4.65 5.14 6.06 6.89 8.03 4.87 5.67 6.21 7.23 8.14 9.40 5.42 6.27 6.84 7.92 8.9 10.2
35 PI 1.48 1.52 1.54 1.57 1.57 1.57 1.82 1.88 1.91 1.95 1.97 1.98 2.06 2.13 2.17 2.22 2.26 2.28
HC 3.67 4.32 4.77 5.62 6.38 7.45 4.62 5.34 5.83 6.77 7.61 8.79 5.16 5.93 6.46 7.45 8.35 9.58
40 PI 1.59 1.65 1.68 1.72 1.74 1.75 1.94 2.02 2.07 2.13 2.16 2.19 2.19 2.29 2.34 2.41 2.46 2.51
HC 3.47 4.07 4.49 5.28 6.00 7.00 4.43 5.09 5.55 6.42 7.21 8.32 4.97 5.68 6.17 7.10 7.93 9.10
45 PI 1.71 1.79 1.83 1.88 1.91 1.94 2.08 2.18 2.24 2.32 2.37 2.42 2.34 2.46 2.53 2.62 2.69 2.76
HC 3.33 3.89 4.28 5.03 5.72 6.68 4.30 4.92 5.35 6.17 6.92 7.98 4.86 5.51 5.97 6.85 7.65 8.76
50 PI 1.84 1.94 1.99 2.06 2.11 2.15 2.23 2.36 2.42 2.52 2.59 2.66 2.51 2.65 2.73 2.85 2.93 3.02
HC 3.25 3.78 4.15 4.87 5.53 6.47 4.24 4.82 5.23 6.02 6.74 7.78 4.80 5.42 5.86 6.70 7.47 8.56
PI 1.99 2.10 2.16 2.25 2.31 2.37 2.40 2.55 2.63 2.75 2.83 2.92 2.70 2.86 2.95 3.10 3.20 3.31
HEATING (integrated values*)
Model
006
007
008
LWC Tamb -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7 -15 -10 -7 -2 2 7
30 HC 3.50 4.14 4.52 5.27 5.92 8.03 4.34 5.04 5.46 6.29 7.00 9.40 4.82 5.58 6.02 6.89 7.6 10.2
35 PI 1.40 1.45 1.45 1.46 1.45 1.57 1.73 1.79 1.80 1.81 1.81 1.98 1.96 2.03 2.04 2.07 2.08 2.28
HC 3.27 3.85 4.20 4.89 5.49 7.45 4.11 4.75 5.13 5.89 6.55 8.79 4.59 5.28 5.69 6.48 7.18 9.58
40 PI 1.51 1.56 1.58 1.60 1.60 1.75 1.85 1.92 1.94 1.98 1.99 2.19 2.08 2.17 2.20 2.25 2.27 2.51
HC 3.09 3.62 3.95 4.59 5.16 7.00 3.94 4.53 4.88 5.59 6.20 8.32 4.43 5.06 5.43 6.17 6.82 9.10
45 PI 1.62 1.70 1.72 1.75 1.76 1.94 1.98 2.07 2.10 2.15 2.18 2.42 2.23 2.34 2.37 2.44 2.47 2.76
HC 2.97 3.46 3.77 4.38 4.92 6.68 3.83 4.38 4.71 5.37 5.96 7.98 4.32 4.91 5.26 5.96 6.58 8.76
SYMBOLS CC HC PI LWE LWC Tamb
12
50 PI 1.75 1.84 1.87 1.92 1.94 2.15 2.12 2.24 2.28 2.35 2.38 2.66 2.39 2.52 2.57 2.65 2.70 3.02
HC 2.89 3.36 3.65 4.24 4.76 6.47 3.77 4.29 4.60 5.23 5.80 7.78 4.27 4.82 5.15 5.83 6.43 8.56
PI 1.89 2.00 2.03 2.10 2.13 2.37 2.28 2.42 2.47 2.56 2.61 2.92 2.56 2.72 2.78 2.88 2.94 3.31
* The integrated heating capacity and power input, is the average heating capacity and power input during 1 cycle. (from end of defrost till end of the next defrost).
3TW57782-1
NOTES
: Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW) : Leaving Water Evaporator temperature (°C) : Leaving Water Condensor temperature (°C) : Ambient temperature (°C) RH=85%
• Altherma • Outdoor units
1
2
3
Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 3∼8°C Power input Power input is total input according to Eurovent rating standard 6/C/003-2006
• Outdoor units • R-410A • ERHQ006-008AD
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing unit (mm)
ERHQ006-008 AD Drain outlet (I.D. J 15.9 hose for connection)
4
Wall height on air outlet side = less than 1200
Minimum space for air passage
1
In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10)
Name plate Brand name label
Wiring inlet
Terminal strip with earth terminal
Outdoor air temperature thermistor
Liquid stop valve (J6.4 CuT) Service port
• Altherma • Outdoor units
Gas stop valve (J15.9 CuT)
3D060289
13
• Outdoor units • R-410A • ERHQ006-008AD
1
4
Dimensional drawing & centre of gravity
4-2
Centre of gravity
ERHQ006-008 AD
4
The position of foundation bolt 4D042258L
14
• Altherma • Outdoor units
• Outdoor units • R-410A • ERHQ006-008AD
5
Piping diagram
ERHQ006-008AD
1
Outdoor unit Heat exchanger
5
Outdoor air temperature thermistor
Capillary tube 1
Capillary tube 2 Capillary tube 3
Heat exchanger thermistor
Muffler with filter
Refrigerant flow Cooling Heating
Capillary tube 4
Filter Motor operated valve
Propeller fan
Filter Four way valve on : heating
Muffler with filter
Field piping
Muffler Liquid stop valve
Muffler Field piping Discharge pipe thermistor
Compressor
Accumulator
Gas stop valve with service port
3D052750B
• Altherma • Outdoor units
15
• Outdoor units • R-410A • ERHQ006-008AD
1
6
Wiring diagram
6-1
Wiring diagram
ERHQ006-008AD
6 Power supply
To indoor unit
Sheet metal
Indoor
g Field wiring
(outdoor) (discharge) (Condenser) Outdoor Z1C∼Z7C X1M, X2M Y1E V2, V3, V5, V9, V100 SA2 FU1, FU2, FU3: AC1, AC2 U, V, W, X11A, X12A E1, E2 HR1, HR2
16
: Ferrite core : Terminal strip : Electronic expansion valve coil : Varistor : Surge arrester : Fuse
: Connector
MRM10, MRM20 MRC/W R1T∼R3T S2∼S102 LEDA L N SW1 SW4 M1C M1F L1R
: Magnetic relay : Thermistor : Connector : Pilot lamp : Live : Neutral : Forced operation on/off switch SW (SW1) : Local setting SW (SW4) : Compressor motors : Fan motor : Reactor
• Altherma • Outdoor units
Q1L PM1 PCB1,2 Y1R Sheet metal
: Overload protector : Power module : Printed circuit board : Reversing solenoide valve coil : Terminal strip fixed plate
3D052296E
• Outdoor units • R-410A • ERHQ006-008AD
7
Sound data
7-1
Sound pressure spectrum ERHQ007AD Heating
3TW57557-2
Octave band center frequency (Hz)
2 3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
1
Coil Microphone
2 3 4
Location of microphone
Coil Microphone
Location of microphone
Sound pressure level (dB) Octave band center frequency (Hz)
3TW57557-1
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Octave band center frequency (Hz)
NOTES
NOTES
3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
ERHQ006AD Cooling
Sound pressure level (dB)
3TW57557-2
2
Octave band center frequency (Hz)
NOTES
ERHQ008AD Heating
1
7
3TW57557-2
NOTES 1
1
Sound pressure level (dB)
Sound pressure level (dB)
ERHQ006AD Heating
1 Coil Microphone
2 3 4
Location of microphone
• Altherma • Outdoor units
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil Microphone
Location of microphone
17
• Outdoor units • R-410A • ERHQ006-008AD
7-1
Sound pressure spectrum
ERHQ007AD Cooling
ERHQ008AD Cooling Sound pressure level (dB)
7
Sound data
Sound pressure level (dB)
1
7
3TW57557-1
Octave band center frequency (Hz)
3TW57557-1
NOTES 1 2 3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
1 Coil Microphone
2 3 4
Location of microphone
18
Octave band center frequency (Hz)
NOTES
• Altherma • Outdoor units
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil Microphone
Location of microphone
• Indoor units • R-410A • EKHBH(X)008AA
TABLE OF CONTENTS EKHBH(X)008AA
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 24
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
4
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 27 Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
7
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
8
Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Static pressure drop unit
• Altherma • Indoor units
31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
19
• Indoor units • R-410A • EKHBH(X)008AA
1 A T A I8 0N 0U a ) m X R rA( O e0H O h1B Dt4H NKl- E•AIR
1
•
Features Cost effective alternative to a fossil fuel boiler
•
Easy to install
Low energy bills and low CO2 emissions
•
Total solution for year round comfort
1
20
• Altherma • Indoor units
• Indoor units • R-410A • EKHBH(X)008AA
2 2-1
Specifications TECHNICAL SPECIFICATIONS
EKHBH008AA
Outdoor units W
230
Colour Packing
Unit
Weight
Packing
Epoxy polyester painted galvanised steel Height
mm
Width
mm
660
Depth
mm
610
1225
922
Height(1)
mm
Width
mm
502
Depth
mm
361
Machine weight
kg
50
Gross Weight
kg
65
Material
EPS
Material
Wood
Material
Carton
Material
PP (straps)
Weight Main components
Pump
kg
10
Type
Water cooled
Nr. of speed Nominal ESP unit
3 Heating
kPa
Cooling
kPa
Power input Water side Heat exchanger
W
49
49 51
130
Type
Brazed plate
Qty
1
Water volume
l
Water flow rate Min.
l/min
Water flow rate No
Heating (3)
l/min
Cooling (2)
l/min
0.67 12 16.5
16.5 14.7
Insulation material Expansion vessel Water filter
Polyurethane foam
Volume
l
Max. water pressure
bar
10 3
Pre pressure
bar
1
Diameter perforations
mm
1
Material Water circuit
Brass
Piping connections diameter (7)
inch
G 1 (MALE)
Piping
inch
1-1/4"
Safety valve
bar
3
Manometer
Yes
Drain valve / Fill valve
Yes
Shut off valve
Yes
Air purge valve
Yes
Total water volume (6)
l
5.5
Refrigerant Circuit
Gas side diameter
mm
15.9
Liquid side diameter
mm
6.35
Sound Level
Sound Pressure (4)
dBA
28
Sound Power (8)
dBA
42
Ambient
Operation range
Waterside
Heating
°C
Cooling
°C
Heating (5)
°C
Cooling
°C
Outdoor units
-20~25
-20~25 10~43
15~50
15~50 5~22 ERHQ007AD
Nominal input (Indoor only) Casing
2
RAL9010
Material Dimensions
1
ERHQ006AD
Nominal input (Indoor only) Casing
EKHBX008AA
W
230
Colour
RAL9010
Material
Epoxy polyester painted galvanised steel
• Altherma • Indoor units
21
• Indoor units • R-410A • EKHBH(X)008AA
2 2-1
1
Specifications TECHNICAL SPECIFICATIONS
Dimensions
Packing
2 Unit
Weight Packing
EKHBH008AA
Height
mm
Width
mm
1225 660
Depth
mm
610
Height(1)
mm
922
Width
mm
502
Depth
mm
361
Machine weight
kg
50
Gross Weight
kg
65
Material
EPS
Material
Wood
Material
Carton
Material
PP (straps)
Weight Main components Pump
kg
10
Type
Water cooled
Nr. of speed
Water side Heat exchanger
3
Nominal ESP Heating unit Cooling
kPa
Power input
W
45
Expansion vessel
49 130
Type
Brazed plate
Qty
1
Water volume
l
Water flow rate Min.
l/min
Water flow rate Nom.
Heating (3)
l/min
Cooling (2)
l/min
0.67 12 19.6
16.8 Polyurethane foam
l
10
Max. water pressure
bar
3
Pre pressure
bar
1
mm
1
Material
Brass
Piping connections diameter (7)
inch
G 1 (MALE)
Piping
inch
1-1/4"
Safety valve
bar
3
Manometer
Yes
Drain valve / Fill valve
Yes
Shut off valve
Yes
Air purge valve
Yes
Total water volume (6) Refrigerant Circuit Gas side diameter
Operation range
l
5.5
mm
15.9 6.35
Liquid side diameter
mm
Sound Pressure (4)
dBA
28
Sound Power (8)
dBA
42
Ambient Waterside
Heating
°C
Cooling
°C
Heating (5)
°C
Cooling
°C
-20~25
-20~25
15~50
15~50
10~43 5~22
Outdoor units
ERHQ008AD
Nominal input (Indoor only) Casing
Colour
Dimensions
Packing
W
230 RAL9010
Material
Unit
22
19.6
Volume
Water filter Diameter perforations
Sound Level
45
kPa
Insulation material
Water circuit
EKHBX008AA
Epoxy polyester painted galvanised steel Height
mm
1225
Width
mm
660
Depth
mm
610
Height(1)
mm
922
Width
mm
502
Depth
mm
361
• Altherma • Indoor units
• Indoor units • R-410A • EKHBH(X)008AA
2 2-1
Specifications TECHNICAL SPECIFICATIONS
Weight Packing
EKHBH008AA
Machine weight
kg
50
Gross Weight
kg
65
Material Material
Wood
Material
Carton kg
10
Type
Water cooled
Nr. of speed Nominal ESP unit
3 Heating
kPa
Cooling
kPa
Power input Water side Heat exchanger
38
38 48
W
130
Type
Brazed plate
Qty
1
Water volume
l
Water flow rate Min.
l/min
Water flow rate Nom.
Heating (3)
l/min
Cooling (2)
l/min
0.67 12 24.1
24.1 17.4
Insulation material Expansion vessel Water filter
Polyurethane foam
Volume
l
Max. water pressure
bar
10 3
Pre pressure
bar
1
Diameter perforations
mm
1
Material Water circuit
Brass
Piping connections diameter (7)
inch
G 1 (MALE)
Piping
inch
1-1/4"
Safety valve
bar
3
Manometer
Yes
Drain valve / Fill valve
Yes
Shut off valve
Yes
Air purge valve
Yes
Total water volume (6)
l
5.5
Refrigerant Circuit
Gas side diameter
mm
15.9
Liquid side diameter
mm
6.35
Sound Level
Sound Pressure (4)
dBA
28
Sound Power (8)
dBA
42
Ambient
Operation range
Waterside
2
PP (straps)
Weight Pump
1
EPS
Material Main components
EKHBX008AA
Heating
°C
Cooling
°C
Heating (5)
°C
Cooling
°C
Notes
-20~25
-20~25
15~50
15~50
10~43 5~22 (1) With option kit EKHBDP installed: Height=936mm
Notes
(2) Tamb 35°C - LWE 7°C (DT=5°C)
Notes
(3) DB/WB 7°C/6°C-LWC 35°C(DT=5°C)
Notes
(4) The sound pressure level is measured via a microphone at 1m from the unit. It is a relative value, depending on the distance and acoustic environment. The sound pressure level mentioned is valid for pump medium speed.
Notes
(5) 15°C-25°C: BUH only, no Heatpump operation=during commissioning.
Notes
(6) Including piping+PHE+backup heater/excluding expansion vessel.
Notes
(7) Value mentioned is connection after ball valves. Connection at unit is G1 1/2 female
Notes
(8) DB/WB 7°C/6°C-LWC 35°C(DT=5°C), medium pump speed
• Altherma • Indoor units
23
• Indoor units • R-410A • EKHBH(X)008AA
2
1
2-2
Specifications
ELECTRICAL SPECIFICATIONS
Electric heater
2
Power Supply
Phase Hz
50
Voltage
V
230
Current
Running Current
A
Voltage Range
Minimum
+10% Quantity of wires Type of wires
6V3 Phase
1~
Frequency
Hz
50
Voltage
V
230
Current
Running Current
A
Voltage Range
Minimum
26 -10%
Maximum
+10% Quantity of wires Type of wires
3G Select diameter and type according to national and local regulations
Type
6WN Phase
3~
Frequency
Hz
50
Voltage
V
400
Current
Running Current
A
Voltage Range
Minimum
+10% Quantity of wires Type of wires
4G Select diameter and type according to national and local regulations
Type Power Supply
8.7 -10%
Maximum
Wiring For power Connections supply backup heater
6T1 Phase
3~
Frequency
Hz
50
Voltage
V
230
Current
Running Current
A
Voltage Range
Minimum
+10% Quantity of wires Type of wires
4G Select diameter and type according to national and local regulations
Type Power Supply
15.1 -10%
Maximum
Wiring For power Connections supply backup heater
9WN Phase
3~
Frequency
Hz
50
Voltage
V
400
Current
Running Current
A
Voltage Range
Minimum
13 -10%
Maximum
+10%
Wiring For power Connections supply backup heater
24
3G Select diameter and type according to national and local regulations
Type
Power Supply
Electric heater
13 -10%
Maximum
Wiring For power Connections supply backup heater
Electric heater
1~
Frequency
Power Supply
Electric heater
EKHBX008AA
3V3
Wiring For power Connections supply backup heater Electric heater
EKHBH008AA
Type
Quantity of wires Type of wires
• Altherma • Indoor units
4G Select diameter and type according to national and local regulations
• Indoor units • R-410A • EKHBH(X)008AA
2
2-2
Specifications
ELECTRICAL SPECIFICATIONS
Electric heater
Power Supply
9T1
1
3~
2
EKHBH008AA
Type Phase Frequency
Hz
EKHBX008AA
50
Voltage
V
230
Current
Running Current
A
22.6
Voltage Range
Minimum
-10%
Maximum
+10%
Wiring For power Connections supply backup heater
Quantity of wires Type of wires
Wiring Connections Connection type
4G Select diameter and type according to national and local regulations
For power supply connection to Optional Warm Water Tank + Q2L
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations For more details of the voltage range and current refer to installation manual EKHBH/ X008AA*
Connection type
For connection with R5T
Quantity of wires
Wire included in option EKHWS*
Type of wires
Wire included in option EKHWS*
Connection type
For connection with A3P
Quantity of wires
Depends on thermostat type, refer to installation manual EKHBH/X008AA*
Type of wires
Select diameter and type according to national and local regulations Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Connection type
For connection with M2S
Quantity of wires
3G
Type of wires
Select diameter and type according to national and local regulations Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
Connection type
For connection with M3S
Quantity of wires
3G or 4G
Type of wires
Select diameter and type according to national and local regulations Voltage: 230V/Maximum current: 100mA/Minimum 0,75 mm²
• Altherma • Indoor units
25
• Indoor units • R-410A • EKHBH(X)008AA
3
Options
Factory mounted optional equipment for EKHB(H/X)008AA**
1
Reference
Description Heating only model EKHBH008A... Reversible model EKHBX008A...
A3V3
3V3
Back up heater 3kW 1∼230 V
V
V
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
6V3
Back up heater 6kW 1∼230 V
⎯
⎯
V
V
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
6W1
Back up heater 6kW 3∼400 V
⎯
⎯
⎯
⎯
V
V
⎯
⎯
⎯
⎯
⎯
⎯
6T1
Back up heater 6kW 3∼230 V
⎯
⎯
⎯
⎯
⎯
⎯
V
V
⎯
⎯
⎯
⎯
9W1
Back up heater 9kW 3∼400 V
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
V
V
⎯
⎯
9T1
Back up heater 9kW 3∼230 V
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
V
V
3
A6V3 A3V3
A6V3
A6T1
A6V3
A6WN
A9WN A6T1
A9T1 A9WN
A9T1
Outdoor combination table for EKHB(H/X)008AA**
ERHQ006ADV3
ERHQ007ADV3
ERHQ008ADV3
EKHBH008AA*
Heating only indoor unit
V
V
V
EKHBX008AA*
Reversible indoor unit
V
V
V
ERHQ006ADV3
ERHQ007ADV3
ERHQ008ADV3
V
V
V
Kit availability for ERHQ006AD*
EKBPHT16
Bottom plate heater (1)
Kit availability for EKHB(H/X)008AA*
Reference
Description Heating only model EKHBH008A... Reversible model EKHBX008A...
A3V3
A6V3
EKHWS150A3V3
Domestic hot water tank 150l 1-230V
V
V
EKHWS200A3V3
Domestic hot water tank 200l 1-230V
V
EKHWS300A3V3
Domestic hot water tank 300l 1-230V
V
EKHWS200A3Z2
Domestic hot water tank 200l 2-400V
EKHWS300A3Z2
A3V3
A6WN
A6T1
A6V3
A6WN
V
V
V (*) V (*)
V
V
V
V
V
V
⎯
⎯
⎯
⎯
V
Domestic hot water tank 300l 2-400V
⎯
⎯
⎯
⎯
V
EKHWSU150A3V3
Domestic hot water tank 150l 1-230V
V
V
V
V
EKHWSU200A3V3
Domestic hot water tank 200l 1-230V
V
V
V
V
EKHWSU300A3V3
Domestic hot water tank 300l 1-230V
V
V
V
V
EKHBDP
Option kit for condensate free cooling operation
⎯
V
⎯
V
⎯
EKRP1HB
Digital I/O PCB (2)
V
V
V
V
V
A9WN
A9T1
A6T1
A9WN
V
V
V (*) V (*)
V
A9T1 V
V (*) V (*)
V
V
V (*) V (*)
V
V
V (*) V (*)
V
V
V (*) V (*)
V
V
V
⎯
⎯
V
V
⎯
⎯
V
⎯
⎯
V
V
⎯
⎯
V (*) V (*)
V
V
V (*) V (*)
V
V
V (*) V (*)
V
V
V (*) V (*)
V
V
V (*) V (*)
V
V
V (*) V (*)
V
V
V
⎯
V
⎯
V
⎯
V
V
V
V
V
V
V
V
(*) If neutral line is available
Kit available for EKHWS*
Reference
Description EKHWS... EKHWSU...
15A3V3
200A3V3/Z2 300A3V3/Z2 150A3V3
200A3V3
EKUHWA
Option kit for UK EKHWSU150-300V3
⎯
⎯
⎯
V
V
300A3V3 V
EKSOLHWAV1
Solarkit (3)
V
V
V
V
V
V
EKWBSWW150
Wall bracket for EKSWW150V3
V
⎯
⎯
V
⎯
⎯
Remarks: Other combinations than mentioned in this option TW are not guaranteed. (1) Heater tape that can be fixed on the bottom plate to prevent ice formation. (2) Address card that provides two additional output connections (remote alarm and remote ON/OFF signalisation). In EKSOLHWAV1, the same digital I/O PCB as for EKRP1HB is already included. 3TW57789-2C (3) Kit to be mounted on domestic hot water tank that provides connection to solar panels for additional water heating.
26
• Altherma • Indoor units
• Indoor units • R-410A • EKHBH(X)008AA
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
EKHBH008AA
1
FIXATION
4
Service door (Closed) 361 (Open) 553 G 1 (Male)
Dimensions wallbracket
Minimum space for service & ventilation
Min. 150
Min. 200
Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection G 1 1/2 (female) j 4 Water OUT connection G 1 1/2 (female) j 5 Power supply intake (+ domestic hot water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J6.35 flare connection j 14 Shut off valves with drain/fill valve (accessory delivered with unit) j 15 Holes for fixation j 16 Switchbox terminals j 17 Switchbox terminals option domestic hot water tank j 18 Wallbracket
3TW57784-1A
EKHBX008AA FIXATION
Service door (Closed) 361 (Open) 553 G 1 (Male)
Dimensions wallbracket
Minimum space for service & ventilation
Min. 150
Min. 200
Center of gravity j 1 Pump + switch for speed setting j 2 Remocon j 3 Water IN connection G 1 1/2 (female) j 4 Water OUT connection G 1 1/2 (female) j 5 Power supply intake (+ domestic hot water tank) j 6 Air purge j 7 Expansion vessel+j 7A nipple+j 7B Drain j 8 Blow off valve j 9 Blow off drain (flexible hose J20) j 10 Pressure gauge j 11 Water filter j 12 Suction pipe connection J15.9 flare connection j 13 Liquid pipe connection J6.35 flare connection j 14 Shut off valves with drain/fill valve (accessory delivered with unit) j 15 Holes for fixation j 16 Switchbox terminals j 17 Switchbox terminals option domestic hot water tank j 18 Wallbracket
3TW57784-2A
• Altherma • Indoor units
27
• Indoor units • R-410A • EKHBH(X)008AA
5
1
Piping diagram
EKHBH(X)008AA R4T R3T R2T R1T
5
Water side
Inlet water thermistor Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat-exchanger thermistor
Field installation Filter Inlet Shut off valve
Refrigerant side
Safety valve Drain valve
Pressure gauge
Drain
Expansion vessel Cooling (EKHBX) Heating (EKHBX + EKHBH)
Option backup heater Drain valve
Field installation
Air purge
Flowswitch
Pump
Outlet Shut off valve
Overview Electric heater body Evaporator Condensor
Outdoor unit
Refr. out Refr. in
Water inlet Refrigerant side
Water side
Refr. in Water outlet Refr. out
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe PSpinned pipe
28
• Altherma • Indoor units
3TW56715-1
• Indoor units • R-410A • EKHBH(X)008AA
6
Wiring diagram
6-1
Wiring diagram
EKHBH(X)008AA3V3
1
Only for EKSOLHWAV1 Option
Power supply 230V 1N∼50Hz
Solar pump connection
Outdoor unit
>> See note 2
See note 2
See note 2
See note 2
See note 2
See note 2
See note 2
See note 2
typical 3 to 4 persons usage pattern. High Daily demand up to 550 l -> 4 to 6 persons usage pattern.
(2) Heat-up time: Definition: Heat-up time The time required to reheat the domestic hot water tank to 55°C after tapping a certain volume of hot water at 40°C. note: changing the field settings (see installation manual) can influence the heat-up time.
Tank 150L 200L 300L
Heat-up time for 150 L (bath) 60 60 50
Setpoint temp. (°C) 55 55 55
Heat-up time for 50 L (shower) 45 40 30
Conditions for testing: Ta = 7°CDB / 6°CWB, Troom = 20°C, Tstart = 10°C, outdoor unit type: ERYQ007
(3) Efficiency of sanitary hot water production: In the ALTHERMA by Daikin system both the heat-pump and the electric booster heater supply the energy to produce sanitary hot water. The higher the portion of energy supplied by the heat-pump, the more energy efficient the system is. Lowering the setpoint temperature increases the portion of energy supplied by the heat-pump and thus the efficiency of the system.
Heat-pump portion
Definition: Heat-pump portion Percentage of energy supplied by the heat-pump in the total energy need for sanitary hot water.
Setpoint temp. (°C) Conditions:
Real life condition Outdoor temperature Room temperature Outdoor unit type Tank type Field settings
Simulation of a daily usage based upon ′medium′ usage pattern. 7°CDB / 6°CWB 20°CDB ERYQ007 200l Default field settings (see installation manual).
4TW57839-1
70
• Altherma • Domestic hot water tank
• Domestic hot water tank • DOMESTIC HOT WATER TANK • EKHWS
4
Dimensional drawing & centre of gravity
4-1
Dimensional drawing
3
EKHWS j 1 Water mains in female 3/4’’ BSP j 2 Water mains out female 3/4’’ BSP j 3 Thermistor connection j 4 Flow (from EKHB(H/X)*) female 3/4’’ BSP j 5 Return (to EKHB(H/X)*) female 3/4’’ BSP j 6 Switchbox j 7 Thermal protector j 8 Anode j 9 Cable entry power, booster heater and thermal protection cable j 10 Re-circulation connection female 3/4’’ BSP j 11 Cable entry from EKHB(H/X)* (see EKSOLHWAV1) j 12 Cable entry (to EKSOLHWAV1) j 13 Thermistor connection (See EKSOLHWAV1)
Required service space around the tank
1
3 4
3TW57834-1
EKHWSU Water connections kit
Water connections
j 1 j 2 j 3 j 4 j 5 j 6 j 7 j 8
Water IN (cold) Water OUT (hot) Flow from EKHB(H/X)* Return to EKHB(H/X)* Temperature relief valve Thermistor connection Thermistor connection (SeeEKSOLHWAV1) Re-circulation hole
22MM 3/4’’ female BSP 3/4’’ female BSP 3/4’’ female BSP 15MM 1/2’’ female BSP 3/4’’ female BSP
j 9 j 10 j 11 j 12 j 13 j 14 j 15 j 16 j 17
Pressure reducing valve Expansion relief valve T-piece (to tundish) Tundish T-piece (to expansion vessel) Adapter (expansion vessel) Expansion vessel Drain valve Solenoid valve
22MM-22MM 22MM-22MM 15MM-15MM-1/2’’ female BSP 22MM-15MM 22MM-22MM-22MM 22MM-3/4’’ female BSP female BSP 22MM-3/4’’ hale BSP 3/4’’ female BSP-3/4’’ hale BSP
Other
j 18 j 19 j 20 j 21 j 22 j 23 j 24 j 25 j 26
Switchbox Thermal protector 1+Thermostat Cable entry power, booster heater, therminal protector Cable entry power solenoid valve Cable entry solenoid valve Blind stop + 2 plastic screw-on closing caps for pressure reducing valve Thermal protector 2+Thermostat Cable entry (to EKSOLHWAV1) Cable entry from EKHB(H/X)* (see EKSOLHWAV1) Required service space Model EKHWSU150A3V3 EKHWSU200A3V3 EKHWSU300A3V3
H1 900 1150 1600
H2 1015 1265 1715
H3 255 410 410
H4 130 200 200
3TW57834-2
• Altherma • Domestic hot water tank
71
• Domestic hot water tank • DOMESTIC HOT WATER TANK • EKHWS
5
Piping diagram
EKHWSU Field supply
Field installation (delivered with indoor unit)
Indoor
Load
Shut off valve
Water return
Shut off valve
Water flow
Outdoor
3-way motorized valve
Option domestic hot water tank
Water flow
3
Water return
Option domestic hot water tank Water main IN
Water main OUT
5 Pressure reducing valve with integrated non return valve line strainer Expansion relief valve T-piece
Tundish
2-way solenoid valve
Expansion vessel *Field installation delivered with EKUHWA kit T-piece
Drain valve
RST Y1S M3S
Domestic hot water thermistor Solenoid valve 3-way motorized valve
3TW57835-1 Check valve
72
Flare connection
Screw connection
Flange connection
Pinched pipe
Spinned pipe
• Altherma • Domestic hot water tank
• Domestic hot water tank • DOMESTIC HOT WATER TANK • EKHWS
6
Wiring diagram
6-1
Wiring diagram
3
EKHWSU
1 EKHB/X* Switchbox
E4H F2B F2U K3M L N Q2T Q2L Q3L X2M∼X4M X5M1∼X7M Y1S
EKHWSU**0A3V3 Water tank Switch box
: Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat Domestic hot water tank : Thermostat protector domestic hot water tank Thermal protector Booster heater : Terminal block : Terminal block : Solenoid valve
3 6
Notes: 1 This wiring diagram applies to the EKHWSU option : Field wiring 2 : Field wiring : Wire colour : Terminal strip : Protective earth 3 BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet 4 Please refer to the EKHWSU**DA3V3 option manual for more installation details.
3TW57836-1
• Altherma • Domestic hot water tank
73
• Domestic hot water tank • DOMESTIC HOT WATER TANK • EKHWS
7
Operation range EKHW DOMESTIC HOT MODE outdoor temp (°CDB)
3 7
water temperature sanitary tank (°C)
BOOSTER HEATER OPERATION ONLY
4TW57753-1A
74
• Altherma • Domestic hot water tank
• Solar Kit • SOLAR KIT • EKSOLHWAV1
TABLE OF CONTENTS EKSOLHWAV1
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
77
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
77
3
77
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 78 Dimensional drawing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
4
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Wiring diagram
• Altherma • Solar Kit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
75
• Solar Kit • SOLAR KIT • EKSOLHWAV1
1
Features
t 1 i V aKA m W r H r e L a hO l tS oKl ESA
3 1
76
• Altherma • Solar Kit
• Solar Kit • SOLAR KIT • EKSOLHWAV1
2 2-1
Specifications TECHNICAL SPECIFICATIONS
Dimensions
Packing
Unit
Weight Packing
Height
mm
340
Depth
mm
295
Height
mm
770
Width
mm
305
Depth
mm
270
Unit
kg
8
Packed Unit
kg
9
Material Type Pressure drop
Solar side kPa
21.5
Maximum inlet temperature
Solar side °C
110
W
Type W
Sound
Sound Pressure
dBA
Water circuit
Piping connections diameter inch
Insulation material
5
46 27 3/4" FBSP EPP
°C
35
Minimum
°C
1
ELECTRICAL SPECIFICATIONS Phase Voltage
EKSOLHWAV1
1~
Frequency Hz Voltage range
1,400
Maximum
Power Supply
2
3
Power input
Unit
3
water cooled
Number of speeds
2-2
1 Brazed plate
K Logarithmic mean temperature difference (LMTD)
Ambient temperature
3
Carton kg
Capacity
Pump
795
Width
Weight Heat Exchanger
mm
EKSOLHWAV1
V
50 220-240
Minimum
-10%
Maximum
+10%
Power Supply Intake
indoor unit
• Altherma • Solar Kit
77
• Solar Kit • SOLAR KIT • EKSOLHWAV1
3
Dimensional drawing & centre of gravity
3-1
Dimensional drawing EKSOLHWAV1 + EKHWS200-300*
EKSOLHWAV1 + EKHWS150*
Detail 1
3
Detail 1
3
Switchbox domestic hot water tank
j 11 Cable entry (Altherma indoor unit) j 12 Cable entry (Pump cable) Components
j 1 j 2 j 3 j 4
Pump + switch for speed setting Heat exchanger EPP casing Non return valves
Accessories (delivered with EKSOLHWAV1) Connection type j 13 Thermistor sockel (thermistor solar pump station) (internal diameter 6.1mm) j 14 Adapter 3/4″M BSP-3/4″M BSP j 15 Adapter 3/4″F BSP-3/4″M BSP j 16 Adapter 3/4″M BSP-3/4″M BSP
CONNECTIONS j 5 Inlet connection from solar pump station j 6 Return connection to solar pump station j 7 Inlet connection from Altherma indoor unit j 8 Return connection to Altherma indoor uint j 9 EKSOLHWAV1 return connection to the domestic hot water tank heatexchanger j j 9a 200-300l Tank 9b 150l Tank j 10 EKSOLHWAV1 inlet connection from the domestic hot water tank heatexchanger
78
3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP
• Altherma • Solar Kit
Minimum space for service & ventilation
Detail 1 Scale: 1/4
Service space
Scale: 1/20
3TW57844-1
• Solar Kit • SOLAR KIT • EKSOLHWAV1
3
Dimensional drawing & centre of gravity
3-1
Dimensional drawing
3 EKSOLHWAV1 + EKHWS200-300*
EKSOLHWAV1 + EKHWS150*
Detail 2 Scale: 1/4
Detail 2
Detail 1
3 3
Switchbox domestic hot water tank
j 11 Cable entry (Altherma indoor unit) j 12 Cable entry (Pump cable) Components
j 1 j 2 j 3 j 4
Pump + switch for speed setting Heat exchanger EPP casing Non return valves
Accessories (delivered with EKSOLHWAV1) Connection type j 13 Thermistor sockel (thermistor solar pump station) (internal diameter 6.1mm) j 14 Adapter 3/4″M BSP-3/4″M BSP j 15 Adapter (Field supply) 3/4″F BSP-3/4″M BSP
Minimum space for service & ventilation
Model EKHWSU150* EKHWSU200* EKHWSU300*
H1 430 400 400
Service space
CONNECTIONS j 5 Inlet connection from solar pump station j 6 Return connection to solar pump station j 7 Inlet connection from Altherma indoor unit j 8 Return connection to Altherma indoor uint j 9 EKSOLHWAV1 return connection to the domestic hot water tank heatexchanger j j 9a 200-300l Tank 9b 150l Tank j 10 EKSOLHWAV1 inlet connection from the domestic hot water tank heatexchanger
3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP 3/4″F BSP
EKUHWA Kit j 16 Solenoid valve 3/4″F BSP-3/4″F BSP j 17 Adapter 3/4″M BSP-3/4″M BSP Solenoid valve
3/4″F BSP
• Altherma • Solar Kit
Scale: 1/20
3TW57844-2
79
• Solar Kit • SOLAR KIT • EKSOLHWAV1
4
Piping diagram
EKSOLHWAV1
Overview
Indoor
3-way motorized valve
Load
Shut off valve Shut off valve
Water from indoor
Field supply Solar collector
Solenoid valve 3-way motorized valve
Field supply
Field installation (delivered with indoor unit)
Outdoor
Y1S M3S
Option domestic hot water tank
Field supply Solar pump station
Water to tank
Medium from solar collector Option solar kit Medium to solar collector
3
Water from tank * Delivered with EKUHWA kit
Water to indoor
4
Detail 1 Only for EKHWSU* Water from indoor
Water to tank
Detail 1
2-way solenoid valve *
Medium from solar collector For EKHW(S/E)*
Plate heat exchanger
Medium to solar collector
Non return valve Pump Water to indoor
Water from tank Non return valve
Check valve
80
Flare connection
Screw connection
Flange connection
3TW57845-1 Pinched pipe
• Altherma • Solar Kit
Spinned pipe
• Solar Kit • SOLAR KIT • EKSOLHWAV1
5
Wiring diagram
5-1
Wiring diagram
3
EKSOLHWAV1 with EKHWS*V3 EKHWS*V3 Switchbox
EKHB/X* Switchbox
Solar pump
3 5
EKHB/X* Switchbox E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S
: Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block : Solenoid valve
Notes: 1
2 3
: Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual.
3TW57846-1
EKSOLHWAV1 with EKHWS*Z2 EKHWS*Z2 Switchbox
EKHB/X* Switchbox
Solar pump
EKHB/X* Switchbox E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S
: Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block : Solenoid valve
Notes: 1
2 3
: Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual.
3TW57846-1
• Altherma • Solar Kit
81
• Solar Kit • SOLAR KIT • EKSOLHWAV1
5
Wiring diagram
5-1
Wiring diagram
EKSOLHWAV1 with EKHWSU EKHWS*V3 Switchbox
EKUHWA
EKHB/X* Switchbox
Notes: 1
3 5
2 3
: Field wiring : Field wiring : Wire colour : Terminal strip : Protective earth BLK=Black RED=Red BLU=Blue WHT=White PNK=Pink YLW=Yellow BRN=Brown GRY=Grey GNR=Green ORG=Orange VIO=Violet For more installation details please refer to the relevant installation manual.
EKSOLHWAV1
EKHB/X* Switchbox
E4H F2B F2U K3M L N Q2T Q2L Q3L Q3T X2M∼X4M X5M1∼X7M Y1S
: Booster heater : Fuse booster heater : Fuse 5A/250V : Contactor booster heater : Line : Neutral : Thermostat protector 1 domestic hot water tank : Thermal protector : Thermal protector 2 Booster heater : Thermostat protector 2 domestic hot water tank : Terminal block : Terminal block : Solenoid valve
3TW57846-1
82
• Altherma • Solar Kit