MOUNTING HARDWARE
WHERE FREQUENT WASH DOWNS OCCUR SUPPLIED WITH SUB-122 ENVIRO KIT 06297T EXTERNAL MOUNTING TABS — INSERT TABS INTO FRAME SLOTS AS SHOWN
Safety Technology International, Inc. 2306 Airport Road • Waterford, Michigan 48327-1209 Phone: 248-673-9898 • Fax: 248-673-1246 Toll Free: 800-888-4784 • E-mail:
[email protected] Web: www.sti-usa.com OPTIONAL CONDUIT HUB SUB-6297B20 (ACCEPTS 3/4 in. RIGID CONDUIT FITTINGS) 19033 ANCHOR INCLUDES GASKET AND (4) PROVIDED MOUNTING HARDWARE
Safety Technology International (Europe) Ltd.
Unit 49G Pipers Road • Park Farm Industrial Estate • Redditch Worcestershire • B98 0HU • England • Tel: 44 (0) 1527 520 999 19013 SCREW #10 x 1 1/2 in. Fax: 44 (0) 1527 501 999 • Freephone: 0800 085 1678 (UK only) (4) PROVIDED E-mail:
[email protected] • Web: www.sti-europe.com
BACK OF FRAME ASSY. MAY BE DRILLED TO ALLOW WIRE ACCESS AS SHOWN
IF ADDED PROTECTION IS NEEDED DUE TO ENVIROMENTAL CONDITIONS ORDER SUB-122 ENVIRO KIT
TYPICAL NOTIFICATION APPLIANCE 629763 STANDOFF BLOCKS (4) MUST BE USED IN AREAS WHERE FREQUENT WASH DOWNS OCCUR SUPPLIED WITH SUB-122 ENVIRO KIT
6
19013 SCREW #10 x 1 1/2 in. (4) PROVIDED 01210 COVER ONLY BACK OF FRAME ASSY. MAY BE DRILLED TO ALLOW WIRE ACCESS AS SHOWN
LOCATED IN THIS AREA DRILL A 1/4 in.(6.3mm) DIA. HOLE
1. To minimize strobe light loss, regardless of the type of horn/strobe appliance used, the clear section (NOT the section containing the cutout slots), must be centered over the strobe light lens. Failure to follow these instructions may lead to light loss transmission. 2. Damage Stopper must be installed to comply with applicable NEC, NFPA and local codes. 1 in.(25mm) 3. In areas where frequent wash downs occur, standoff blocks must be used. 4. In applications where wash downs, rainfall or condensation occur, it is recommended APPROX that a drain or weep hole be provided. Refer to weep hole installation diagram. CENTER LINE 5. OF Damage Stopper may be installed outdoors when appliance carries an outdoor rating. UNDERSIDE OF LOCATED IN THIS AREA
!
INSTALL CLAMP IN NOTCH 2 AS SHOWN
IF ADDED PROTECTION IS 01210 COUVERCLE SEULEMENT NEEDED DUE TO ENVIROMENTAL CONDITIONS ORDER SUB-122 ENVIRO KIT
TYPICAL NOTIFICATION APPLIANCE
HEIGHT 8.5 in.(216mm)
19047 #8-32 x 3/8 in. SOCKET HEAD CAP SCREW (4) PROVIDED
19033 AN (4) PRO DEPTH 3.5 in.(89mm)
CLEAR SECTION
06297B FRAME ASSY.
INSTALLATION NOTES
COVER
629764 CLAMP (4) PROVIDED
OPTIONAL COND SUB(ACCEPTS 3/4 CONDUIT F INCLUDES GAS MOUNTING HA
2
06297T EXTERNAL MOUNTING TABS — CLEAR INSERT TABS INTO FRAME SECTION SLOTS AS SHOWN
06297B FRAME ASSY.
19033 ANCHOR (4) PROVIDED
1
01210 COVER ONLY
WIDTH 6.5 in.(165mm)
!
01210 COUVERCLE SEULEMENT 06297A BACKBOX 06297T MOUNTING TABS (4) PROVIDED
629764 CLAMP (4) PROVIDED
DRILL FOR CONDUIT ENTRY 3 3/8 in. (86mm)
19047 #8-32 x 3/8 in. SOCKET HEAD CAP SCREW (4) PROVIDED
3/4 in.(44mm) HEIGHT 8.5 in.(216mm) PRODUCT DIMENSIONS INTERNAL DIMENSIONS
REMARQUES SUR DRILLL’INSTALLATION A 1/4 in.(6.3mm) DIA. HOLE
1. Afin de minimiser la perte de lumière stroboscopique, quel que soit le type d’alarme sonore/de stroboscope utilisé, la section dégagée (et NON la section contenant les fentes de découpe), doit être centrée sur l’objectif stroboscopique. Le fait d’omettre ces instructions risque d’entraîner la perte de diffusion de la lumière. 2. Le Stopper de dégâts doit être installé de sorte à être conforme avec les normes NEC, NFPA applicables et les codes locaux. 3. Dans les zones où des jets d’eau fréquents surviennent, des blocs de détection à distance doivent être utilisés. 4. Dans les applications où des jets d’eau, des précipitations ou de la condensation se produisent, il est recommandé de prévoir un trou de vidange ou une barbacane. Reportez-vous à schéma d’installation d’une barbacane. 5. Il est possible d’installer un Stopper de dégâts à l’extérieur lorsque l’appareil est homologué pour utilisation à l’extérieur. 1 in.(25mm)
INSTALLATION INSTRUCTIONS - REFER TO EXPLODED VIEW 1. 2. 3. 4. 5. 6. 7. 8. 9.
Insert the (4) 06297T external mounting tabs into the frame assembly slots. APPROX Using backLINE box assembly as a template, place against mounting surface at proper location according to NFPA 72. CENTER Mark drill (4) OF and UNDERSIDE OFholes 1/4 in. (6.3mm) diameter, 1 1/4 in. (32mm) deep. COVER Insert the (4) anchors into the wall. Mount back box to wall with screws. Install electrical fittings as needed. Install horn/strobe appliance. Install cover with clips and screws. Test appliance according to appliance manufacturer’s instructions.
LOCATED IN THIS AREA DEPTH DRILL A 1/4 in.(6.3mm) DIA. HOLE 3.5 in.(89mm)
629763 STANDOFF BLOCKS (4) PROVIDED
19033 ANCHOR (4) PROVIDED
CLEANING INSTRUCTIONS
WIDTH 6.5 in.(165mm)
19013 SCREW #10 x 1 1/2 in. (4) PROVIDED
Rinse with water to remove abrasive dust and dirt. Wash with 629764 RETAINING CLIPS soap or mild detergent, using a soft cloth (do not scrub). Rinse (4) PROVIDED once more then dry with a soft cloth or chamois. To remove 19047with #8-32 x 3/8 in. SOCKET grease or wet paint, rub gently with a cloth wetted naphtha. Then wash and rinse. DO NOT USE RAZOR BLADES.HEAD (DOCAP SCREWS (4) PROVIDED NOT USE RAZOR BLADES.)
629762 DRAIN SCREEN
WEEP HOLE INSTALLATION
Electronic warranty form at www.sti-usa.com/wc14
INSTALLATION OF STI-1210B SPEAKER HORN/STROBE DAMAGE STOPPER® A 1-1/16 in. DIAMETER CONDUIT
1-3/4
1 in.(25mm)
APPROX PRODUCT DIMENSIONS CENTER LINE OF UNDERSIDE OF COVER
629761 NEOPRENE GASKET
All specifications and information shown were current as of publication and are subject without notice. ENTRY HOLE MUSTto BE change FIELD INSTALLED
CLEAR SECTION
A 1-1/16 in. 1210BIS APRIL2006 DIAMETER CONDUIT ENTRY HOLE MUST BE FIELD INSTALLED
!
0121
0121
UL INSTALLATION REQUIREMENTS STI-1210 / STI-1221 SERIES CAUTION
Attention
• This enclosure is rated to protect signaling appliances indoors and in areas of indirect weather exposure. The cover may be used outdoors only with devices also suitable for outdoor use. • When covering fire-signaling appliances with this enclosure, some light and sound loss occurs. Please follow these guidelines listed during installation. • Voice speaker appliance: No spacing adjustment is required for 0.5W, 1.0W and 2.0W appliances. • Refer to the appliance manufacturer's candela rating. Multiply this number by the light loss value from the chart below to determine the new candela rating. Use this number and refer to the notification layout table of NFPA 72 for proper device locations. • The use of this cover on audible devices decreases the sound output by 6dB(A). Actual sound level output should be checked after installation to determine if adequate sound levels exist. Refer to the notification layout table of NFPA 72 for proper device locations.
• Ce boîtier est homologué pour protéger les appareils de signalisation d’incendie à l’intérieur et dans les zones d’exposition indirecte aux intempéries. Le couvercle ne peut être utilisé à l’extérieur qu’avec les appareils appropriés pour une utilisation à l’extérieur aussi. • Le fait de couvrir les appareils de signalisation d’incendie au moyen de ce boîtier risque d’entraîner une certaine perte lumineuse et sonore. Veuillez vous conformer à ces directives lors de l’installation. • Haut-parleur: Aucun ajustement de distance n’est nécessaire pour les appareils à tension de 0,5 W, 1,0 W et 2,0 W. • Reportez-vous à la cote candéla du fabricant de l’appareil. Multipliez cette valeur par la valeur de la perte de lumière du tableau ci-dessous pour déterminer la nouvelle cote candéla. Utilisez cette nouvelle valeur et reportez-vous au tableau de disposition des alertes de la norme NFPA 72 pour les emplacements appropriés de l’appareil. • L’utilisation de ce couvercle sur les dispositifs sonores diminue la puissance sonore de 6 dB(A). Le niveau réel de la sortie sonore doit être vérifié après l’installation pour déterminer le maintien de niveaux sonores adéquats. Reportez-vous au tableau de disposition des alertes de la norme NFPA 72 pour les emplacements appropriés de l’appareil.
Performance Review - LIGHT DERATING FACTOR MANUFACTURER ADT SECURITY AMSECO
SERIES
STI-1210
STI-1221/1221A4X
MANUFACTURER
ADTG1-V SERIES
40%
34%
HONEYWELL
SERIES
STI-1210
STI-1221/1221A4X
XLS202 SERIES
40%
34%
SL24W-153075
22%
37%
HONEYWELL
XLSG1-HV SERIES
40%
34%
AMSECO – COLORED LENSES
SL24W-153075 A, B, G, OR R
47%
26%
HONEYWELL
XLSG1-HOV SERIES
40%
34%
AMSECO – COLORED LENSES
SL24C-3075110 A, B, G, OR R
47%
26%
MIRCOM
FS-240
47%
26%
AMSECO – COLORED LENSES
CSL24W-A, B, G, OR R
47%
26%
MIRCOM
MS SERIES
43%
45%
AMSECO – COLORED LENSES
CSL24C-A, B, G, OR R
47%
26%
MIRCOM
MG1-V SERIES
40%
34%
GES24 SERIES
-
31%
MIRCOM
MG1-HV SERIES
40%
34%
DETECTION SYSTEMS DETECTION SYSTEMS
GES24-15/75
-
-
MIRCOM
MG1-HOV SERIES
40%
34%
EST / EDWARDS
2440S SERIES
43%
45%
MIRTONE
MG1-V SERIES
43%
45% 31%
EST / EDWARDS
202 SERIES
43%
45%
NATIONAL TIME & SIGNAL
GES24 SERIES
-
EST / EDWARDS
G1-V SERIES
40%
34%
NATIONAL TIME & SIGNAL
GES24-15/75
-
-
EST / EDWARDS
G1-HV SERIES
40%
34%
POTTER ELECTRIC
AS-24-153075R
47%
26%
EST / EDWARDS
G1-HOV SERIES
40%
34%
POTTER ELECTRIC
AS-24-153075W
47%
26%
EST / EDWARDS
EG1-V SERIES
40%
34%
SECUTRON
GES24 SERIES
-
31%
EST / EDWARDS
EG1-HV SERIES
40%
34%
SECUTRON
GES24-15/75
-
-
EST / EDWARDS
EG1-HOV SERIES
40%
34%
SIEMENS
202- SERIES
43%
45% 34%
FARADAY LLC
2700
-
57%
SIEMENS
G1-V SERIES
40%
GENTEX
GES24 SERIES
-
31%
SIEMENS
U-MCS SERIES
-
-
GENTEX
GES24-15/75
-
-
SYSTEM SENSOR
SS24110ADA
46%
37%
SYSTEM SENSOR
61%
HARRINGTON SIGNAL
GES24 SERIES
-
31%
HARRINGTON SIGNAL
GES24-15/75
-
-
XLSG1-V SERIES
43%
45%
HONEYWELL
P2, PC2, P4, PC4, SX, SC
53%
WHEELOCK
RSS-24MCW
-
-
ZITON PTY LTD
ZG1-V SERIES
40%
34%
STI-1210 Series Sound Derating Factor: System Sensor P2, PC2, P4, PC4, SX, SC series models: 6.7 dBA, General: 6 dBA STI Generic Light Loss Value: STI-1210 Series: 53%; STI-1221 Series: 61% SAFETY TECHNOLOGY INTERNATIONAL, INC. • 2306 AIRPORT ROAD • WATERFORD • MICHIGAN 48327-1209 • PHONE: 248-673-9898 • FAX: 248-673-1246 • www.sti-usa.com
04/2006