Split Sky Air - daikintech.co.uk

Daikin Europe N.V. is approved by LRQA for its Quality ...... 12x2. (0.16x2). 14x2. (0.15x2). 13x2. (0.1x2). 10. Rated power input of each model is tabulated below. ...... 8.85. Twin. Model. FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2.
2MB taille 1 téléchargements 275 vues
RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit

Split Sky Air

air conditioning systems

technical data

Split - Sky Air

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com

EEDE05-1/3 • 05/2005 Prepared in Belgium by Goekint Graphics

Specifications are subject to change without prior notice.

• Outdoor Units • R410A • RZQ-B

TABLE OF CONTENTS RZQ-B

1 2

Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3

Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

5

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6

Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensional drawings and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

7

Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

8

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

9

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

10

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Refnet pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

11

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

• Split Sky Air • Outdoor Units

1

• Outdoor Units • R410A • RZQ-B

o t o aB i d 0- l t 1Q pu4Z 1 SOR

Features

2 1

2



Outdoor units for pair application



The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners.



During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy.



Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.



The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level



Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency



An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures.



A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

2

Specifications

2 2-1 TECHNICAL SPECIFICATIONS Casing Dimensions

Daikin white Painted galvanized steel plate

Packing

Height

mm

900

1475

1475

1475

mm

980

980

980

980

Depth

mm

420

420

420

420

Height

mm

770

1345

1345

1345

Width

mm

900

900

900

900

Depth

mm

320

320

320

320

kg

68

106

106

106

kg

72

111

111

111

mm

857

857

857

857

2

2

2

2

mm

1.40

1.40

1.40

1.40

3

5

5

5

m2

0.641

1.131

1.131

1.131

34

60

60

60

Machine Weight Dimensions

Length Fin Pitch Nr of Passes Face Area Nr of Stages

Tube type Fin

Type

WF fin Anti-corrosion treatment (PE)

Type

Propeller

Discharge direction

Horizontal

Quantity

1

2

2

2

Air Flow Rate (nominal)

Cooling

m3/min

54.50

103.0

103.0

99.0

Heating

m3/min

48.10

101.0

101.0

100.0

Motor

Quantity

1

2

2

2

Model

Fan Compressor

Speed (nominal at 230V) Motor

KFD-325-70-8A

Steps

8

8

8

8

Cooling

rpm

818

789

789

782

Heating

rpm

715

775

775

767

Output

W

70

70

70

70

Drive

direct drive 1

1

1

1

Model

2YC63BXD

JT100G-VD

JT1G-VDYR@T

JT100G-VD

Type

Hermetically sealed swing compressor

Quantity Motor

Motor Output

W

Hermetically sealed scroll compressor

1800

2200

2200

2200

_

33

33

33 -15.0

Starting Method

Inverter driven

Crankcase Heater

W

Min

°CDB

-15.0

-15.0

-15.0

Max

°CDB

50.0

50.0

50.0

50.0

Heating

Min

°CWB

-20.0

-20.0

-20.0

-20.0

Max

°CWB

15.5

15.5

15.5

15.5

Cooling

Sound Power

dBA

63.0

65.0

65.0

66.0

Sound Pressure

dBA

47.0

49.0

49.0

50.0

Heating

Sound Pressure

dBA

49.0

51.0

51.0

52.0

Sound Level (Night quiet)

Cooling

Sound Pressure

dBA

43.0

45.0

45.0

45.0

Refrigerant

Type kg

2.80

4.30

4.30

4.30

Operation Range Cooling

Sound Level (nominal)

Charge

R-410A

Control Nr of Circuits

2

Hi-XSS(8) Treatment

Motor

RZQ125B8V3B

Width

Nr of Rows

Fan

RZQ100B7W1B

Colour

Gross Weight Heat Exchanger

RZQ100B8V3B

Material

Unit

Weight

RZQ71B8V3B

Expansion valve (electronic type) 1

• Split Sky Air • Outdoor Units

1

1

1

3

• Outdoor Units • R410A • RZQ-B

2-1 TECHNICAL SPECIFICATIONS Refrigerant Oil

RZQ71B8V3B

Type Charged Volume

2

Piping connections

Liquid (OD)

RZQ100B8V3B

l Quantity

0.8

1.0

1.0

1.0

1

1

1

1

9.52

9.52

1

1

Flare connection

Diameter (OD) Gas

mm

Quantity

9.52

9.52

1

1

Type

Flare connection

Diameter (OD) Drain

mm

Quantity Type

Piping Length

RZQ125B8V3B

Daphne FVC68D

Type

2

RZQ100B7W1B

Daphne FVC50K

15.9

15.9

15.9

15.9

3

3

3

3

26

26

26

Hole

Diameter (OD)

mm

26

Minimum

m

5

5

5

5

Maximum

m

50

75

75

75

Equivalent

m

70

95

95

95

Chargeless m

30

30

30

30

Additional Refrigerant Charge

kg/m

see installation manual 4PW21412-1

Installation Maximum height difference

m

30.0

30.0

Max. internunit level difference m

0.5

0.5

Heat Insulation

30.0

30.0

0.5

0.5

Both liquid and gas pipes

Defrost Method

Pressure equalising

Defrost Control

Sensor for outdoor heat exchanger temperature

Capacity Control Method

Inverter controlled

Safety Devices

High pressure switch Fan motor thermal protector Fuse

Standard Accessories

Item

Tie-wraps

Quantity

2

2

Item Quantity

2-1 TECHNICAL SPECIFICATIONS Casing Dimensions

Colour Material Packing

Unit

Weight Heat Exchanger

Machine Weight Gross Weight Dimensions

Tube type Fin Fan

4

2

2

Installation manual

Height Width Depth Height Width Depth

mm mm mm mm mm mm kg kg mm

Length Nr of Rows Fin Pitch mm Nr of Passes Face Area m2 Nr of Stages Type Treatment

Type Discharge direction Quantity Air Flow Rate Cooling (nominal) Heating External static pressure (Max) Motor Quantity Model Position

m3/min m3/min

1

1

1

1

RZQ125B7W1B

RZQ140B7W1B

RZQ200B7W1B

RZQ250B7W1B

Daikin white Painted galvanized steel plate 1475 1475 1753 1753 980 980 1055 1055 420 420 860 860 1345 1345 1600 1600 900 900 930 930 320 320 765 765 106 106 225 226 111 111 236 237 857 857 1640 1640 2 2 2 2 1.40 1.40 2.00 2.00 5 5 16 16 1.131 1.131 1.948 1.948 60 60 54 54 Hi-XSS(8) WF fin Non-symmetric waffle louvre Anti-corrosion treatment (PE) Corrosion resistant Propeller Horizontal Vertical 2 2 1 1 99.0 99.0 175 175 100.0 100.0 175 175 60 Pa in high static pressure 2 2 1 1 KFD-325-70-8A Brushless DC Vertical

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

2-1 TECHNICAL SPECIFICATIONS Motor

Speed (nominal at Steps 230V) Cooling rpm Heating rpm Fan Motor Output W Drive Compressor Quantity Motor Model Type Speed rpm Motor W Output Starting Method Crankcase W Heater Motor Model Type Speed rpm Motor W Output Starting Method Crankcase W Heater Operation Range Cooling Min °CDB Max °CDB Heating Min °CWB Max °CWB Sound Level Cooling Sound dBA (nominal) Power Sound dBA Pressure Heating Sound dBA Power Sound dBA Pressure Sound Level Cooling Sound dBA (Night quiet) Pressure Refrigerant Type Charge kg Control Nr of Circuits Refrigerant Oil Type Charged Volume l Piping Liquid (OD) Quantity connections Type Diameter mm (OD) Gas Quantity Type Diameter mm (OD) Drain Quantity Type Diameter mm (OD) Piping Length Minimum m Maximum m Equivalent m Chargeless m Additional Refrigerant Charge kg/m Installation height Maximum m difference Max. internunit level difference m Heat Insulation Defrost Method Defrost Control Capacity Control Method

RZQ125B7W1B

RZQ140B7W1B

RZQ200B7W1B

RZQ250B7W1B

8 782 767 70

8 782 767 70

8 760 825 750

8 760 825 750

Direct drive 1 JT1G-VDYR@T

1 2 JT1G-VDYR@T Hermetically sealed scroll compressor 2200 2200

2200

2

2 2

Inverter 900~6480 2200

Direct on line 33

33

-

Hermetically sealed scroll compressor -

-

33

33 ON - OFF 2900 4500

Direct on line -

-

33

-15.0 50.0 -20.0 15.5 66.0

-15.0 50.0 -20.0 15.5 66.0

-5.0 46.0 -15.0 15.0 -

-5.0 46.0 -15.0 15.0 -

50.0

50.0

-

-

-

-

78.0

78.0

-

-

57.0

57.0

45.0

45.0

-

-

R-410A 4.30 8.00 Expansion valve (electronic type) 1 1 Daphne FVC68D 1.0 1.7 + 1.6 1 1 Flare connection 9.52 9.52

4.30 1 1.0 1 9.52 1

1

3

5 75 95 30

1.7 + 1.6 1 12.7 1 Braze connection

15.9

22.2

22.2

3

-

-

Hole 26

1

1

Flare connection 15.9

9.00

26

30.0

5 5 75 100 95 30 30 see installation manual 4PW21412-1 30.0 30.0

30.0

0.5

0.5

0.5

0.5

5 100 30

Both liquid and gas pipes Pressure equalising Sensor for outdoor heat exchanger temperature Inverter controlled

• Split Sky Air • Outdoor Units

Reversed cycle Sensor for outdoor heat exchanger temperature Inverter controlled

5

• Outdoor Units • R410A • RZQ-B

2-1 TECHNICAL SPECIFICATIONS

RZQ125B7W1B

Safety Devices

2 2

Standard Accessories

Item Quantity Item Quantity Item Quantity

2

RZQ200B7W1B

2

1

1 Installation manual

1

1

RZQ250B7W1B

High pressure switch Fan motor driver overload protector Inverter overload protector Overcurrent relay PC board fuse Installation manual 1 1 Additional refrigerant label 1 1 Connection pipes 4 4

Installation manual

2-2 ELECTRICAL SPECIFICATIONS Power Supply

RZQ140B7W1B

High pressure switch Fan motor thermal protector Fuse Tie-wraps

RZQ71B8V3B

RZQ100B8V3B

RZQ100B7W1B

RZQ125B8V3B

Name

V3

V3

W1B

V3

Phase

1

1

3N

1

Frequency

Hz

50

50

50

50 230

Voltage

V

230

230

400

Current

Recomended fuses

A

20

32

20

32

Voltage range

Minimum

V

207

207

360

207

Maximum

V

253

253

440

253

Wiring connections

For Power Supply Remark

see installation manual 4PW21412-1

For connection with indoor

see installation manual 4PW21412-1

Remark

Power Supply Intake

Outdoor unit only

2-2 ELECTRICAL SPECIFICATIONS Power Supply

Current

RZQ125B7W1B

RZQ140B7W1B

RZQ200B7W1B

Name

W1B

W1B

W1

W1

Phase

3N

3N

3N~

3N~

Frequency

Hz

50

50

50

50

Voltage

V

400

400

400

400

Nominal running current

Cooling

A

-

-

refer to electrical data indoor outdoor combination

Heating

A

-

-

refer to electrical data indoor outdoor combination

Starting current (cooling/heating)

Voltage range Wiring connections

RZQ250B7W1B

-

-

refer to electrical data indoor outdoor combination

Maximum running current

A

-

-

refer to electrical data indoor outdoor combination

Recomended fuses

A

20

20

32

32

Minimum

V

360

360

360

360

Maximum

V

440

440

440

440

For Power Supply Quantity Remark For connection with indoor

-

5

see installation manual 4PW21412-1

earth wire included

Quantity

-

4

Remark

see installation manual 4PW21412-1

earth wire included

Power Supply Intake

Outdoor unit only

Notes

See seperate drawings for electrical data Power supply to the FDQ indoor unit is separate

NOTES

6

1

Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.

2

Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m.

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

3

Electrical data

2 RZQ71-125B7 Unit combination Indoor unit Outdoor unit

3 Power supply Voltage range MCA

Hz-volts

TOCA

MFA

Comp. MSC RLA

OFM kW

IFM FLA

kW

FLA

3D048637A

SYMBOLS MCA TOCA MFA MSC

RLA OFM IFM FLA kW

NOTES

: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (See note 7) (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)

1

2 3

4 5 6 7 8

RLA is based on the following conditions: Power supply: 50Hz 230V Heating Cooling Indoor temperature 20.0°CDB Indoor temperature 27°CDB/19°CWB Outdoor temperature 7.0°CDB/6.0°CWB Outdoor temperature 35°CDB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.

• Split Sky Air • Outdoor Units

7

• Outdoor Units • R410A • RZQ-B

3

Electrical data

2 3

RZQ71-125-140B7 Unit combination Indoor unit Outdoor unit

Hz-volts

Power supply Comp. Voltage range MCA TOCA MFA MSC RLA

OFM kW

IFM FLA

kW

FLA

3D048638A

SYMBOLS MCA TOCA MFA MSC

RLA OFM IFM FLA kW

NOTES

: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (See note 7) (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)

1

2 3

4 5 6 7 8

8

RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Heating Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

3

Electrical data

2 3

RZQ200-250B7 Indoor unit

Unit combination Outdoor unit

Power supply Voltage range

Hz-volts

MCA

TOCA

MFA

Comp. MSC RLA

OFM kW

IFM FLA

kW

FLA

Max. 50Hz 440V Min. 50Hz 360V

Max. 50Hz 440V Min. 50Hz 360V

3TW26561-4A

SYMBOLS MCA TOCA MFA MSC

RLA OFM IFM FLA kW

NOTES

: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)

1

2 3

4 5 6 7 8

RLA is based on the following conditions: Power supply: 50Hz - 400V Heating Cooling Indoor temperature 20.0°CDB Indoor temperature 27°CDB/19°CWB Outdoor temperature 7.0°CDB/6.0°CWB Outdoor temperature 35°CDB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.

• Split Sky Air • Outdoor Units

9

• Outdoor Units • R410A • RZQ-B

4

Options

2 4

RZQ71∼140B7V3B Kit name Name of option

RZQ71B7V3B

RZQ100B8V3B

RZQ125B8V3B

RZQ100B7W1B Central drain plug Refrigerant branch piping

RZQ125B7W1B

RZQ140B7W1B

KKPJ5F180 Twin

KHRQ22M20TA7

Triple

-

Double twin

-

Demand adapter kit

KHRQ127H7 -

KHRQ22M20TA7 (3x) KRP58M51 3TW26739-1

Available options for RZQ200,250B7W1B Name of option Central drain pan kit Refrigerant branch piping

Kit name RZQ200B7W1B

RZQ250B7W1B KWC26B280

Twin Triple Double twin

KHRQ22M20TA7 KHRQ250H7 KHRQ22M20TA7 (3x) 4TW26569-3

10

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-1

Combination table

2 5

Possible combinations and standard capacity for twin, triple and double twin application Possible indoor combination Simultaneous operation

Outdoor models

Twin

Triple

Out

Out

In

In

In

In

Double twin Out

In

In

In

In

RZQ71B8V3B

35-35 (KHRQ22M20TA7)

RZQ100B8V3B RZQ100B7W1B

50-50 (KHRQ22M20TA7)

35-35-35 (KHRQ127H7)

RZQ125B8V3B RZQ125B7W1B

60-60 (KHRQ22M20TA7)

50-50-50 (KHRQ127H7)

35-35-35-35 (3x KHRQ22M20TA7)

RZQ140B7W1B

71-71 (KHRQ22M20TA7)

50-50-50 (KHRQ127H7)

35-35-35-35 (3x KHRQ22M20TA7)

In

3TW26739-2

NOTES 1

Possible indoor units: FCQ35-71, FFQ35-60, FHQ35-71, FBQ35-71, FUQ71, FAQ71

2

Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).

3

When different indoor models are used in combination, designate the infrared remote control that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).

4

Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.

Possible combinations and standard capacity for twin, triple and double twin operation Possible indoor combination Simultaneous operation

Outdoor models

Twin

Triple

Out

Out

In

In

In

In

Double twin Out

In

In

In

In

RZQ200B7W1B

100-100 (KHRQ22M20TA7)

60-60-60 71-71-71 (KHRQ250H7)

50-50-50-50 (3x KHRQ22M20TA7)

RZQ250B7W1B

125-125 (KHRQ22M20TA7)

---

60-60-60-60 (3x KHRQ22M20TA7)

In

3TW26569-2

NOTES 1

Possible indoor units: FCQ50-125, FFQ50-60, FHQ50-125, FBQ50-125, FAQ71-100, FUQ71-125, FDQ125

2

Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).

3

When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).

4

Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.

• Split Sky Air • Outdoor Units

11

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ71B8V3B

Coefficient of power input. (-)

Cooling

Capacity range

Rated point

Cooling capacity Cooling capacity

Indoor

EWB

230V [50Hz]

EDB

(°C)

(°C)

16.0 18.0 19.0 19.5 22.0 24.0

22 25 27 27 30 32

25 SHC (kW) 4.39 4.82 4.80 4.79 4.73 4.66

TC (kW) 6.47 7.43 7.58 7.66 8.05 8.37

CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85

TC (kW) 6.46 7.20 7.35 7.43 7.81 8.12

30 SHC (kW) 4.43 4.72 4.71 4.70 4.64 4.58

Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93

TC (kW) 6.66 6.95 7.10 7.17 7.55 7.85

35 SHC (kW) 4.62 4.61 4.60 4.59 4.54 4.48

CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02

TC (kW) 6.39 6.67 6.82 6.89 7.26 7.55

40 SHC (kW) 4.49 4.47 4.46 4.46 4.41 4.35

CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048602

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ71D 19 (0.10)

FCQ71B 18 (0.10)

FBQ71 19 (0.11)

FHQ71 17 (0.10)

FAQ71 19 (0.08)

FUQ71 19 (0.07)

Twin

Model AFR (BF)

FCQ35x2 14x2 (0.16x2)

FFQ35x2 10x2 (0.25x2)

FBQ35x2 11.5x2 (0.15x2)

FHQ35x2 13x2 (0.2x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ71D 1.98 1.97

FCQ71B 2.16 2.56

FBQ71 2.14 2.09

FHQ71 2.46 2.67

FAQ71 2.36 2.42

FUQ71 2.21 2.34

Twin

Model Cooling Heating

12

FCQ35x2 2.27 2.62

FFQ35x2 2.29 2.64

FBQ35x2 2.25 2.20

FHQ35x2 2.53 2.81

• Split Sky Air • Outdoor Units

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

Caution: TC and SHC are shown by kW

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ100B8V3B (Pair + Twin/triple)

Coefficient of power input. (-)

Cooling

Rated point

Capacity range

Cooling capacity Cooling capacity

Indoor

EWB

230V [50Hz]

EDB

(°C)

(°C)

16.0 18.0 19.0 19.5 22.0 24.0

22 25 27 27 30 32

25 SHC (kW) 6.19 6.78 6.76 6.75 6.66 6.57

TC (kW) 9.12 10.5 10.7 10.8 11.3 11.8

CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85

TC (kW) 9.10 10.1 10.4 10.5 11.0 11.4

30 SHC (kW) 6.25 6.65 6.63 6.62 6.54 6.45

Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93

TC (kW) 9.38 9.79 10.0 10.1 10.6 11.1

35 SHC (kW) 6.51 6.49 6.48 6.47 6.39 6.30

CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02

TC (kW) 9.00 9.40 9.60 9.71 10.2 10.6

40 SHC (kW) 6.32 6.30 6.29 6.28 6.21 6.13

CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048603

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ100D 30 (0.11)

FCQ100B 28 (0.16)

FBQ100 27 (0.20)

FHQ100 24 (0.14)

FAQ100 23 (0.10)

FUQ100 29 (0.07)

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

(m3/min)

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ35Bx3 14x3 (0.16x3)

FFQ35x3 10x3 (0.25x3)

FBQ35x3 11.5x3 (0.15x3)

FHQ35x3 13x3 (0.2x3)

FCQ35Bx3 2.78 3.31

FFQ35x3 2.79 3.21

FBQ35x3 3.01 3.16

FHQ35x3 3.32 3.79

Twin

Model AFR (BF)

FCQ50Bx2 15x2 (0.16x2)

FFQ50x2 12x2 (0.16x2)

FBQ50x2 14x2 (0.15x2)

FHQ50x2 13x2 (0.1x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ100D 2.44 2.56

FCQ100B 2.64 3.14

FBQ100 2.86 3.00

FHQ100 3.15 3.60

Triple

FAQ100 2.78 3.39

FUQ100 3.12 3.28

Model Cooling Heating

Twin

Model Cooling Heating

FCQ50Bx2 2.78 3.31

FFQ50x2 2.79 3.21

FBQ50x2 3.01 3.16

FHQ50x2 3.32 3.79

• Split Sky Air • Outdoor Units

13

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ100B7W1B (Pair + Twin/triple)

Coefficient of power input. (-)

Cooling

Rated point

Capacity range

Cooling capacity Cooling capacity

Indoor

EWB

400V [50Hz]

EDB

(°C)

(°C)

16.0 18.0 19.0 19.5 22.0 24.0

22 25 27 27 30 32

25 SHC (kW) 6.19 6.78 6.76 6.75 6.66 6.57

TC (kW) 9.12 10.5 10.7 10.8 11.3 11.8

CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85

TC (kW) 9.10 10.1 10.4 10.5 11.0 11.4

30 SHC (kW) 6.25 6.65 6.63 6.62 6.54 6.45

Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93

TC (kW) 9.38 9.79 10.0 10.1 10.6 11.1

35 SHC (kW) 6.51 6.49 6.48 6.47 6.39 6.30

CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02

TC (kW) 9.00 9.40 9.60 9.71 10.2 10.6

40 SHC (kW) 6.32 6.30 6.29 6.28 6.21 6.13

CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048605

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ100D 30 (0.11)

FCQ100B 28 (0.16)

FBQ100 27 (0.20)

FHQ100 24 (0.14)

FAQ100 23 (0.10)

FUQ100 29 (0.07)

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

(m3/min)

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ35Bx3 14x3 (0.16x3)

FFQ35x3 10x3 (0.25x3)

FBQ35x3 11.5x3 (0.15x3)

FHQ35x3 13x3 (0.2x3)

FCQ35Bx3 2.78 3.31

FFQ35x3 2.79 3.21

FBQ35x3 3.01 3.16

FHQ35x3 3.32 3.79

Twin

Model AFR (BF)

FCQ50Bx2 15x2 (0.16x2)

FFQ50x2 12x2 (0.16x2)

FBQ50x2 14x2 (0.15x2)

FHQ50x2 13x2 (0.1x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ100D 2.44 2.56

FCQ100B 2.64 3.14

FBQ100 2.86 3.00

FHQ100 3.15 3.60

Triple

FAQ100 2.78 3.39

FUQ100 3.12 3.28

Twin

Model Cooling Heating

14

FCQ50Bx2 2.78 3.31

FFQ50x2 2.79 3.21

FBQ50x2 3.01 3.16

FHQ50x2 3.32 3.79

• Split Sky Air • Outdoor Units

Model Cooling Heating

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ125B8V3B (Pair + Twin / triple / double twin)

Coefficient of power input. (-)

Cooling

Rated point

Capacity range

Cooling capacity Cooling capacity

Indoor

EWB

EDB

(°C)

(°C)

16.0 18.0 19.0 19.5 22.0 24.0

22 25 27 27 30 32

230V [50Hz]

TC (kW) 11.4 13.1 13.3 13.5 14.2 14.7

25 SHC (kW) 7.73 8.48 8.45 8.44 8.33 8.21

CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85

TC (kW) 11.4 12.7 12.9 13.1 13.8 14.3

30 SHC (kW) 7.81 8.32 8.29 8.28 8.18 8.06

Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93

TC (kW) 11.7 12.2 12.5 12.6 13.3 13.8

35 SHC (kW) 8.14 8.12 8.09 8.08 7.99 7.88

CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02

TC (kW) 11.3 11.8 12.0 12.1 12.8 13.3

40 SHC (kW) 7.90 7.88 7.86 7.85 7.76 7.67

CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048604A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ125D 30 (0.13)

FCQ125B 31 (0.07)

FBQ125 35 (0.14)

FHQ125 30 (0.13)

Model AFR (BF)

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)

FUQ125 32 (0.07)

FDQ125 45 (0.25)

Twin

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)

Double twin

Model AFR (BF)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ125D 3.54 3.59

FCQ125B 3.88 4.36

FBQ125 3.98 3.99

Triple

FHQ125 4.45 4.50

FUQ125 4.05 4.36

FDQ125 4.15 3.69

Model Cooling Heating

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

Double twin

Twin

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

• Split Sky Air • Outdoor Units

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

15

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ125B7W1B (Pair + Twin / triple / double twin)

Coefficient of power input. (-)

Cooling

Rated point

Capacity range

Cooling capacity Cooling capacity

Indoor

EWB

EDB

(°C)

(°C)

16.0 18.0 19.0 19.5 22.0 24.0

22 25 27 27 30 32

400V [50Hz]

TC (kW) 11.4 13.1 13.3 13.5 14.2 14.7

25 SHC (kW) 7.73 8.48 8.45 8.44 8.33 8.21

CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85

TC (kW) 11.4 12.7 12.9 13.1 13.8 14.3

30 SHC (kW) 7.81 8.32 8.29 8.28 8.18 8.06

Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93

TC (kW) 11.7 12.2 12.5 12.6 13.3 13.8

35 SHC (kW) 8.14 8.12 8.09 8.08 7.99 7.88

CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02

TC (kW) 11.3 11.8 12.0 12.1 12.8 13.3

40 SHC (kW) 7.90 7.88 7.86 7.85 7.76 7.67

CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048606A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ125D 30 (0.13)

FCQ125B 31 (0.07)

FBQ125 35 (0.14)

FHQ125 30 (0.13)

Model AFR (BF)

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)

FUQ125 32 (0.07)

FDQ125 45 (0.25)

Twin

CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)

Double twin

Model AFR (BF)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ125D 3.54 3.59

FCQ125B 3.88 4.36

FBQ125 3.98 3.99

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)

Triple

FHQ125 4.45 4.50

FUQ125 4.05 4.36

FDQ125 4.15 3.69

Model Cooling Heating

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

Double twin

Twin

16

AFR: BF: EWB: EDB: TC: SHC: PI:

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

• Split Sky Air • Outdoor Units

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ140B7W1B (Pair + Twin / triple / double twin)

Coefficient of power input. (-)

Cooling

Capacity range

Rated point

Cooling capacity Cooling capacity

Indoor

EWB

EDB

(°C)

(°C)

16.0 18.0 19.0 19.5 22.0 24.0

22 25 27 27 30 32

400V [50Hz]

TC (kW) 12.8 14.6 15.0 15.1 15.9 16.5

25 SHC (kW) 8.66 9.50 9.47 9.45 9.33 9.20

CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85

TC (kW) 12.7 14.2 14.5 14.7 15.4 16.0

30 SHC (kW) 8.74 9.31 9.29 9.27 9.16 9.03

Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93

TC (kW) 13.1 13.7 14.0 14.1 14.9 15.5

35 SHC (kW) 9.12 9.09 9.07 9.05 8.95 8.83

CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02

TC (kW) 12.6 13.2 13.4 13.6 14.3 14.9

40 SHC (kW) 8.84 8.82 8.80 8.79 8.69 8.59

CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048607

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ140D 30 (0.07)

Model AFR (BF)

FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 18x2 19x2 17x2 19x2 19x2 (0.1x2) (0.11x2) (0.1x2) (0.07x2) (0.08x2)

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

Twin

(m3/min)

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)

Double twin

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)

Triple

Model Cooling Heating

FCQ140D 4.65 4.52

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69

Double twin

Twin

Model Cooling Heating

Model AFR (BF)

FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 4.81 4.95 4.99 4.99 4.92 5.52 5.06 5.69 5.05 5.22

• Split Sky Air • Outdoor Units

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69

17

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ200B7W1B (Pair / Twin / Triple / Double twin)

Coefficient of power input. (-)

Cooling

22.4

7.5

Cooling capacity (kW) Cooling capacity

Indoor TC (kW) 20.2 21.3 21.8 22.3 23.4 24.4

°CWB 16 18 19 20 22 24

400V [50Hz]

25 SHC (kW) 17.0 17.1 17.1 17.1 17.0 16.8

CPI (-) 0.82 0.83 0.84 0.84 0.85 0.86

TC (kW) 19.4 20.4 20.9 21.4 22.4 23.4

30 SHC (kW) 16.3 16.4 16.4 16.4 16.3 16.1

Outdoor temperature (°CDB) CPI (-) 0.90 0.91 0.92 0.92 0.94 0.95

TC (kW) 18.6 19.5 20.0 20.5 21.4 22.4

35 SHC (kW) 15.5 15.7 15.6 15.6 15.6 15.4

CPI (-) 0.98 0.99 1.00 1.01 1.02 1.03

TC (kW) 17.7 18.6 19.1 19.6 20.5 21.4

40 SHC (kW) 14.8 14.9 14.9 14.9 14.9 14.7

CPI (-) 1.06 1.07 1.08 1.09 1.10 1.12 3TW26561-2A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Pair

Model AFR (BF)

Triple

FDQ200 69 0.31

Model AFR (BF)

Twin

Model AFR (BF)

FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 28x2 27x2 24x2 29x2 23x2 (0.16x2) (0.2x2) (0.14x2) (0.07x2) (0.1x2)

10. Rated power input of each model is tabulated below.

FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 18x3 18x3 15x3 19x3 19x3 17x3 17x3 19x3 19x3 (0.1x3) (0.1x3) (0.11x3) (0.11x3) (0.11x3) (0.2x3) (0.1x3) (0.07x3) (0.08x3)

Double twin

Model AFR (BF)

FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 15x4 12x4 14x4 13x4 (0.16x4) (0.16x4) (0.15x4) (0.1x4)

Pair

Model Cooling Heating

Triple

FDQ200 6.43 7.54

Model Cooling Heating

Twin

Model Cooling Heating

18

FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 5.87 6.36 7.00 6.93 6.18 7.16 6.85 8.21 7.48 7.74

• Split Sky Air • Outdoor Units

FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 6.18 6.18 6.20 6.69 6.69 7.37 7.37 7.30 6.50 7.54 7.54 7.32 7.21 7.21 8.65 8.65 7.88 8.14

Double twin

Model Cooling Heating

FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 6.18 6.20 6.69 7.37 7.54 7.32 7.21 8.65

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-2

Cooling capacity tables

2 5

RZQ250B7W1B (Pair / Twin / Double twin)

Coefficient of power input. (-)

Cooling

28

9.1

Cooling capacity (kW) Cooling capacity

Indoor TC (kW) 25.4 26.6 27.2 27.8 29.0 30.2

°CWB 16 18 19 20 22 24

400V [50Hz]

25 SHC (kW) 21.5 21.5 21.5 21.4 21.2 20.9

CPI (-) 0.79 0.80 0.80 0.81 0.81 0.82

TC (kW) 24.4 25.5 26.1 26.7 27.8 29.0

30 SHC (kW) 20.7 20.6 20.6 20.5 20.3 20.1

Outdoor temperature (°CDB) CPI (-) 0.88 0.89 0.90 0.91 0.92 0.93

TC (kW) 23.4 24.5 25.0 25.5 26.6 27.7

35 SHC (kW) 19.8 19.8 19.8 19.7 19.5 19.3

CPI (-) 0.98 0.99 1.00 1.01 1.02 1.03

TC (kW) 22.3 23.4 23.9 24.4 25.5 26.5

40 SHC (kW) 19.0 18.9 19.0 18.9 18.7 18.4

CPI (-) 1.08 1.09 1.10 1.11 1.12 1.13 3TW26571-2A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Pair

Model AFR (BF)

Double twin

FDQ250 89 0.34

Model AFR (BF)

Twin

Model AFR (BF)

FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 18x4 15x4 19x4 17x4 (0.1x4) (0.11x4) (0.11x4) (0.2x4)

FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 31x2 35x2 30x2 32x2 45x2 (0.07x2) (0.14x2) (0.13x2) (0.07x2) (0.25x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

Double twin

FDQ250 8.30 8.85

Model Cooling Heating

Twin

Model Cooling Heating

FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 9.08 9.18 9.31 10.41 9.83 9.13 9.00 10.15

FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 8.62 8.84 9.89 9.00 9.22 9.34 8.55 9.64 9.34 7.91

• Split Sky Air • Outdoor Units

19

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ71B8V3B (Pair + Twin)

Coefficient of power input. (-)

Heating

Rated point

Capacity range

Heating capacity Heating capacity

Indoor EDB (°C) 16.O 18.O 20.0 21.O 22.O 24.0

TC (kW) 5.14 5.14 5.13 5.13 5.12 5.12

230V [50Hz]

−15

CPI (-) 1.06 1.10 1.15 1.17 1.19 1.23

TC (kW) 5.68 5.67 5.67 5.66 5.66 5.65

−10

CPI (-) 1.12 1.16 1.21 1.23 1.25 1.30

TC (kW) 6.22 6.21 6.20 6.20 6.19 6.19

−5

Outdoor temp. (°CWB) CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36

TC (kW) 6.75 6.74 6.74 6.73 6.73 6.72

0

CPI (-) 1.23 1.28 1.33 1.35 1.38 1.43

TC (kW) 8.02 8.01 8.00 8.00 7.99 7.98

6

CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08

TC (kW) 8.64 8.62 8.61 8.61 8.60 8.59

10

CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048602

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ71D 19 (0.10)

FCQ71B 18 (0.10)

FBQ71 19 (0.11)

FHQ71 17 (0.10)

FAQ71 19 (0.08)

FUQ71 19 (0.07)

Twin

Model AFR (BF)

FCQ35x2 14x2 (0.16x2)

FFQ35x2 10x2 (0.25x2)

FBQ35x2 11.5x2 (0.15x2)

FHQ35x2 13x2 (0.2x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ71D 1.98 1.97

FCQ71B 2.16 2.56

FBQ71 2.14 2.09

FHQ71 2.46 2.67

FAQ71 2.36 2.42

FUQ71 2.21 2.34

Twin

Model Cooling Heating

20

FCQ35x2 2.27 2.62

FFQ35x2 2.29 2.64

FBQ35x2 2.25 2.20

FHQ35x2 2.53 2.81

• Split Sky Air • Outdoor Units

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

Caution: TC and SHC are shown by kW

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ100B8V3B (Pair + Twin/triple)

Coefficient of power input. (-)

Heating

Capacity range

Rated point

Heating capacity Heating capacity

Indoor EDB

230V [50Hz]

−15

TC (kW) 7.16 7.15 7.15 7.14 7.14 7.13

(°C) 16.O 18.O 20.0 21.O 22.O 24.0

CPI (-) 1.01 1.05 1.09 1.12 1.14 1.18

TC (kW) 7.91 7.90 7.89 7.89 7.88 7.87

−10

CPI (-) 1.07 1.11 1.15 1.17 1.20 1.24

TC (kW) 8.66 8.65 8.64 8.63 8.63 8.62

−5

Outdoor temp. (°CWB) CPI (-) 1.12 1.16 1.21 1.23 1.26 1.30

TC (kW) 9.41 9.39 9.38 9.38 9.37 9.36

0

CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36

TC (kW) 11.2 11.2 11.2 11.2 11.2 11.2

6

CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08

TC (kW) 12.1 12.1 12.1 12.1 12.0 12.0

10

CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048603

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ100D 30 (0.11)

FCQ100B 28 (0.16)

FBQ100 27 (0.20)

FHQ100 24 (0.14)

FAQ100 23 (0.10)

FUQ100 29 (0.07)

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

(m3/min)

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ35Bx3 14x3 (0.16x3)

FFQ35x3 10x3 (0.25x3)

FBQ35x3 11.5x3 (0.15x3)

FHQ35x3 13x3 (0.2x3)

FCQ35Bx3 2.78 3.31

FFQ35x3 2.79 3.21

FBQ35x3 3.01 3.16

FHQ35x3 3.32 3.79

Twin

Model AFR (BF)

FCQ50Bx2 15x2 (0.16x2)

FFQ50x2 12x2 (0.16x2)

FBQ50x2 14x2 (0.15x2)

FHQ50x2 13x2 (0.1x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ100D 2.44 2.56

FCQ100B 2.64 3.14

FBQ100 2.86 3.00

FHQ100 3.15 3.60

Triple

FAQ100 2.78 3.39

FUQ100 3.12 3.28

Model Cooling Heating

Twin

Model Cooling Heating

FCQ50Bx2 2.78 3.31

FFQ50x2 2.79 3.21

FBQ50x2 3.01 3.16

FHQ50x2 3.32 3.79

• Split Sky Air • Outdoor Units

21

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ100B7W1B (Pair + Twin/triple)

Coefficient of power input. (-)

Heating

Capacity range

Rated point

Heating capacity Heating capacity

Indoor EDB

400V [50Hz]

−15

TC (kW) 7.16 7.15 7.15 7.14 7.14 7.13

(°C) 16.O 18.O 20.0 21.O 22.O 24.0

CPI (-) 1.01 1.05 1.09 1.12 1.14 1.18

TC (kW) 7.91 7.90 7.89 7.89 7.88 7.87

−10

CPI (-) 1.07 1.11 1.15 1.17 1.20 1.24

TC (kW) 8.66 8.65 8.64 8.63 8.63 8.62

−5

Outdoor temp. (°CWB) CPI (-) 1.12 1.16 1.21 1.23 1.26 1.30

TC (kW) 9.41 9.39 9.38 9.38 9.37 9.36

0

CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36

TC (kW) 11.2 11.2 11.2 11.2 11.2 11.2

6

CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08

TC (kW) 12.1 12.1 12.1 12.1 12.0 12.0

10

CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048605

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ100D 30 (0.11)

FCQ100B 28 (0.16)

FBQ100 27 (0.20)

FHQ100 24 (0.14)

FAQ100 23 (0.10)

FUQ100 29 (0.07)

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

(m3/min)

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ35Bx3 14x3 (0.16x3)

FFQ35x3 10x3 (0.25x3)

FBQ35x3 11.5x3 (0.15x3)

FHQ35x3 13x3 (0.2x3)

FCQ35Bx3 2.78 3.31

FFQ35x3 2.79 3.21

FBQ35x3 3.01 3.16

FHQ35x3 3.32 3.79

Twin

Model AFR (BF)

FCQ50Bx2 15x2 (0.16x2)

FFQ50x2 12x2 (0.16x2)

FBQ50x2 14x2 (0.15x2)

FHQ50x2 13x2 (0.1x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ100D 2.44 2.56

FCQ100B 2.64 3.14

FBQ100 2.86 3.00

FHQ100 3.15 3.60

Triple

FAQ100 2.78 3.39

FUQ100 3.12 3.28

Twin

Model Cooling Heating

22

FCQ50Bx2 2.78 3.31

FFQ50x2 2.79 3.21

FBQ50x2 3.01 3.16

FHQ50x2 3.32 3.79

• Split Sky Air • Outdoor Units

Model Cooling Heating

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ125B8V3B (Pair + Twin / triple / double twin)

Coefficient of power input. (-)

Heating

Capacity range

Heating capacity

Heating capacity

Indoor EDB

TC (kW) 8.83 8.82 8.81 8.81 8.80 8.79

(°C) 16.O 18.O 20.0 21.O 22.O 24.0

Rated point

−15

CPI (-) 1.05 1.10 1.14 1.16 1.18 1.22

TC (kW) 9.76 9.74 9.73 9.73 9.72 9.71

−10

230V [50Hz]

CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29

TC (kW) 10.7 10.7 10.7 10.6 10.6 10.6

−5

Outdoor temp. (°CWB) CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35

TC (kW) 11.6 11.6 11.6 11.6 11.6 11.5

0

CPI (-) 1.22 1.27 1.32 1.34 1.37 1.42

TC (kW) 14.0 14.0 14.0 14.0 14.0 14.0

6

CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08

TC (kW) 15.1 15.1 15.1 15.1 15.1 15.0

10

CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13

3D048604A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ125D 30 (0.13)

FCQ125B 31 (0.07)

FBQ125 35 (0.14)

FHQ125 30 (0.13)

Model AFR (BF)

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)

FUQ125 32 (0.07)

FDQ125 45 (0.25)

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)

Double twin

Twin

Model AFR (BF)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ125D 3.54 3.59

FCQ125B 3.88 4.36

FBQ125 3.98 3.99

Triple

FHQ125 4.45 4.50

FUQ125 4.05 4.36

FDQ125 4.15 3.69

Model Cooling Heating

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

Double twin

Twin

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

• Split Sky Air • Outdoor Units

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

23

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ125B7W1B (Pair + Twin / triple / double twin)

Coefficient of power input. (-)

Heating

Capacity range

Heating capacity

Heating capacity

Indoor EDB

TC (kW) 8.83 8.82 8.81 8.81 8.80 8.79

(°C) 16.O 18.O 20.0 21.O 22.O 24.0

Rated point

−15

CPI (-) 1.05 1.10 1.14 1.16 1.18 1.22

TC (kW) 9.76 9.74 9.73 9.73 9.72 9.71

−10

400V [50Hz]

CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29

TC (kW) 10.7 10.7 10.7 10.6 10.6 10.6

−5

Outdoor temp. (°CWB) CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35

TC (kW) 11.6 11.6 11.6 11.6 11.6 11.5

0

CPI (-) 1.22 1.27 1.32 1.34 1.37 1.42

TC (kW) 14.0 14.0 14.0 14.0 14.0 14.0

6

CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08

TC (kW) 15.1 15.1 15.1 15.1 15.1 15.0

10

CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13

3D048606A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

Model AFR (BF)

FCQ125D 30 (0.13)

FCQ125B 31 (0.07)

FBQ125 35 (0.14)

FHQ125 30 (0.13)

Model AFR (BF)

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)

FUQ125 32 (0.07)

FDQ125 45 (0.25)

CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)

Double twin

Twin

Model AFR (BF)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ125D 3.54 3.59

FCQ125B 3.88 4.36

FBQ125 3.98 3.99

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)

Triple

FHQ125 4.45 4.50

FUQ125 4.05 4.36

FDQ125 4.15 3.69

Model Cooling Heating

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

Double twin

Twin

24

AFR: BF: EWB: EDB: TC: SHC: PI:

FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

• Split Sky Air • Outdoor Units

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ140B7W1B (Pair + Twin / triple / double twin)

Coefficient of power input. (-)

Heating

Rated point

Capacity range

Heating capacity

Heating capacity

Indoor EDB

TC (kW) 9.82 9.80 9.79 9.79 9.78 9.77

(°C) 16.O 18.O 20.0 21.O 22.O 24.0

−15

CPI (-) 1.05 1.10 1.14 1.16 1.18 1.22

TC (kW) 9.80 10.8 10.8 10.8 10.8 10.8

−10

400V [50Hz]

CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29

TC (kW) 11.9 11.8 11.8 11.8 11.8 11.8

−5

Outdoor temp. (°CWB) CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35

TC (kW) 12.9 12.9 12.9 12.8 12.8 12.8

0

CPI (-) 1.22 1.27 1.32 1.34 1.37 1.42

TC (kW) 16.0 16.0 16.0 16.0 16.0 16.0

6

CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08

TC (kW) 17.3 17.2 17.2 17.2 17.2 17.2

10

CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048607

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

FCQ140D 30 (0.07)

Model AFR (BF)

FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 18x2 19x2 17x2 19x2 19x2 (0.1x2) (0.11x2) (0.1x2) (0.07x2) (0.08x2)

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Triple

Model AFR (BF)

Model AFR (BF)

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)

Double twin

Twin

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)

Triple

Model Cooling Heating

FCQ140D 4.65 4.52

FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69

Double twin

Twin

Model Cooling Heating

Model AFR (BF)

FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 4.81 4.95 4.99 4.99 4.92 5.52 5.06 5.69 5.05 5.22

• Split Sky Air • Outdoor Units

Model Cooling Heating

FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69

25

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ200B7W1B (Pair / Twin / Triple / Double twin)

Coefficient of power input. (-)

Heating

8.5

23

23.0 25

30

Heating capacity (kW) Heating capacity

Indoor TC (kW) 14.5 14.4 14.3 14.2 14.1

°CDB 16 18 20 22 24

400V [50Hz]

-15

CPI (-) 1.17 1.19 1.21 1.23 1.25

TC (kW) 17.3 17.2 17.1 17.0 16.8

-10

CPI (-) 1.22 1.25 1.27 1.29 1.31

TC (kW) 16.9 16.8 16.7 16.6 16.4

-5

Outdoor temperature (°CWB) CPI (-) 1.21 1.23 1.25 1.28 1.30

TC (kW) 18.1 18.0 17.9 17.8 17.6

0

CPI (-) 1.24 1.26 1.28 1.31 1.33

TC (kW) 23.3 23.2 23.0 22.8 22.7

6

CPI (-) 0.97 0.98 1.00 1.02 1.03

TC (kW) 25.4 25.3 25.1 24.9 24.7

10

CPI (-) 1.01 1.02 1.04 1.06 1.08

3TW26561-2A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Pair

Model AFR (BF)

Triple

FDQ200 69 0.31

Model AFR (BF)

Twin

Model AFR (BF)

FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 28x2 27x2 24x2 29x2 23x2 (0.16x2) (0.2x2) (0.14x2) (0.07x2) (0.1x2)

10. Rated power input of each model is tabulated below.

FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 18x3 18x3 15x3 19x3 19x3 17x3 17x3 19x3 19x3 (0.1x3) (0.1x3) (0.11x3) (0.11x3) (0.11x3) (0.2x3) (0.1x3) (0.07x3) (0.08x3)

Double twin

Model AFR (BF)

FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 15x4 12x4 14x4 13x4 (0.16x4) (0.16x4) (0.15x4) (0.1x4)

Pair

Model Cooling Heating

Triple

FDQ200 6.43 7.54

Model Cooling Heating

Twin

Model Cooling Heating

26

FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 5.87 6.36 7.00 6.93 6.18 7.16 6.85 8.21 7.48 7.74

• Split Sky Air • Outdoor Units

FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 6.18 6.18 6.20 6.69 6.69 7.37 7.37 7.30 6.50 7.54 7.54 7.32 7.21 7.21 8.65 8.65 7.88 8.14

Double twin

Model Cooling Heating

FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 6.18 6.20 6.69 7.37 7.54 7.32 7.21 8.65

• Outdoor Units • R410A • RZQ-B

5

Capacity tables

5-3

Heating capacity tables

2 5

RZQ250B7W1B (Pair / Twin / Double twin)

Coefficient of power input. (-)

Heating

9.1

31. 5

27.0

Heating capacity (kW) Heating capacity

Indoor TC (kW) 16.5 16.4 16.2 16.1 15.9

°CDB 16 18 20 22 24

400V [50Hz]

-15

CPI (-) 1.04 1.08 1.12 1.16 1.20

TC (kW) 19.4 19.2 19.0 18.8 18.7

-10

CPI (-) 1.09 1.14 1.18 1.23 1.27

TC (kW) 18.7 18.5 18.4 18.2 18.0

-5

Outdoor temperature (°CWB) CPI (-) 1.09 1.13 1.18 1.22 1.26

TC (kW) 19.9 19.7 19.5 19.3 19.2

0

CPI (-) 1.12 1.17 1.22 1.26 1.31

TC (kW) 27.5 27.2 27.0 26.8 26.5

6

CPI (-) 0.92 0.96 1.00 1.04 1.08

TC (kW) 29.9 29.6 29.3 29.1 28.8

10

CPI (-) 0.98 1.02 1.06 1.10 1.14

3TW26571-2A

NOTES

SYMBOLS

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.

AFR: BF: EWB: EDB: TC: SHC: PI: CPI:

Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.

(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)

Caution: TC and SHC are shown by kW

Pair

Model AFR (BF)

Double twin

FDQ250 89 0.34

Model AFR (BF)

Twin

Model AFR (BF)

FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 18x4 15x4 19x4 17x4 (0.1x4) (0.11x4) (0.11x4) (0.2x4)

FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 31x2 35x2 30x2 32x2 45x2 (0.07x2) (0.14x2) (0.13x2) (0.07x2) (0.25x2)

10. Rated power input of each model is tabulated below. Pair

Model Cooling Heating

Double twin

FDQ250 8.30 8.85

Model Cooling Heating

Twin

Model Cooling Heating

FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 9.08 9.18 9.31 10.41 9.83 9.13 9.00 10.15

FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 8.62 8.84 9.89 9.00 9.22 9.34 8.55 9.64 9.34 7.91

• Split Sky Air • Outdoor Units

27

• Outdoor Units • R410A • RZQ-B

6

Dimensional drawing & centre of gravity

6-1

Dimensional drawing

2 6

RZQ71B7V3B

unit (mm) Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8

Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock hole J34) Control wiring intake (knock hole J27) Drain outlet

3TW25144-1A

unit (mm)

RZQ100-125-140B7V3B Hole for anchor bolt 4-M12

1 2 3 4 5 6 7 8

Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) (2x) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock hole J34) Control wiring intake (knock hole J27) Drain outlet

3TW26071-1

28

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

6

Dimensional drawing & centre of gravity

6-1

Dimensional drawing

2 6 RZQ200B7

4 - 15 x 22.5 mm Oblong holes (foundation bolt hole) (Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

(Knock out hole)

(Knock out hole)

(for side-routed pipe)

Notes: 1 The dimensions marked with (a) are those with the installation of the provided pipes. 2 Refer to the installation instructions when the pipes are routed through the bottom of the unit.

1 2 3 4 5 6 7 8 9

(for front-routed pipe)

Liquid pipe connection port 9.52 flare connection Gas pipe connection port 22.2 braze connection Grounding terminal inside of switch box Power cord routing hole (side) - J 65 Power cord routing hole (front) - J 45 Power cord routing hole (bottom) - J 60 Power cord routing hole (front) - J 27 Pipe routing hole (front) Pipe routing hole (bottom) - see note 2

(Knock out hole)

(Knock out hole)

RZQ250B7

3TW26564-2

4 - 15 x 22.5 mm Oblong holes (foundation bolt hole) (Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

(Knock out hole)

(Knock out hole)

(for side-routed pipe)

Notes: 1 The dimensions marked with (a) are those with the installation of the provided pipes. 2 Refer to the installation instructions when the pipes are routed through the bottom of the unit.

1 2 3 4 5 6 7 8 9

(for front-routed pipe)

Liquid pipe connection port 12.7 flare connection Gas pipe connection port 22.2 braze connection Grounding terminal inside of switch box Power cord routing hole (side) - J 65 Power cord routing hole (front) - J 45 Power cord routing hole (bottom) - J 60 Power cord routing hole (front) - J 27 Pipe routing hole (front) Pipe routing hole (bottom) - see note 2

(Knock out hole)

(Knock out hole)

• Split Sky Air • Outdoor Units

3TW26574-2

29

• Outdoor Units • R410A • RZQ-B

6

Dimensional drawing & centre of gravity

6-2

Dimensional drawings and accessories

2 6 RZQ200-250B7

3D041017C

30

• Split Sky Air • Outdoor Units

• Outdoor Units • R410A • RZQ-B

6

Dimensional drawing & centre of gravity

6-3

Centre of gravity

2 6 RZQ200-250B7

Center of foundation bolt hole

Center of foundation bolt hole (oblong hole)

• Split Sky Air • Outdoor Units

Center of foundation bolt hole

Center of foundation bolt hole (oblong hole)

4TW26569-1

31

• Outdoor Units • R410A • RZQ-B

7

Piping diagram

2 7

RZQ71B (Pair) Electronic expansion valve

One way valve

One way valve

Filter One way valve

Service port 5/16″

One way valve

Heat exchanger

Capillary tube Solenoid valve Receiver

Strainer Heat exchanger 4-way valve

Muffler Low pressure sensor

Muffler One way valve

Field piping J9.5 C1220T-0

Service port 5/16″

Filter Field piping J15.9 C1220T-0 Compressor

High pressure switch

Indoor unit

Outdoor unit

Heating Cooling

Stop valve (with service port 5/16’ flare)

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW26735-1

RZQ100-125-140B (Pair) One way valve One way valve

One way valve

Heat exchanger

Filter Solenoid valve

One way valve

One way valve

Capillary tube

Electronic expansion valve

Capillary tube Receiver

Strainer

Capillary tube

Service port 5/16″ Heat exchanger 4-way valve

Filter

Low pressure switch

High pressure switch

Muffler

Field piping J9.5 C1220T-0

Service port 5/16″

Filter Field piping J15.9 C1220T-0 Compressor

Indoor unit

Outdoor unit Stop valve (with service port 5/16’ flare)

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

32

• Split Sky Air • Outdoor Units

Heating Cooling

3TW26745-1

• Outdoor Units • R410A • RZQ-B

7

Piping diagram

2 7

RZQ200-250B (Pair) Filter

Capillary tube

Receiver

Solenoid valve

Model RZQ200B RZQ250B

Check valve

Check valve

Filter

Fan

Check Check valve valve

Electronic expansion valve Electronic expansion valve

Filter

A 9.52 12.70

Heat exchanger pipe

Solenoid valve

Heat exchanger 4-way valve

High pressure sensor

Pressure regulating valve

Filter

Filter

Filter

Compressor

Field piping J A

Compressor

Filter

Capillary tube

Capillary tube

Indoor heat exchanger

High pressure switch

Oil separator

Oil separator

Filter

High pressure switch

Check valve

Low pressure sensor

Solenoid valve

Field piping J22.20

Fan

Stop valve (with service port on field piping side J 7.9mm flare connection)

Indoor unit

Outdoor unit Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.

3TW26565-1

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQ71B (Twin) Electronic expansion valve

One way valve

One way valve

Heat exchanger Filter One way valve

Service port 5/16″

Heat exchanger

Capillary tube

Solenoid valve Field piping Filter

One way valve

Receiver

Field piping Strainer

Indoor unit 4-way valve

Muffler Low pressure sensor

Muffler

Heat exchanger

One way valve Field piping J9.5

Branch duct connection Option

Service port 5/16″

Field piping J15.9 Compressor

Outdoor unit

Field piping Filter

Indoor unit

Field piping

High pressure switch

Stop valve (with service port 5/16’ flare)

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split Sky Air • Outdoor Units

Heating Cooling

3TW26735-2

33

• Outdoor Units • R410A • RZQ-B

7

Piping diagram

2 7

RZQ100-125-140B (Twin) One way valve One way valve

One way valve

One way valve

One way valve

Heat exchanger Filter Capillary tube

Solenoid valve

Electronic expansion valve

Capillary tube Receiver

Field piping Filter

Heat exchanger

Strainer

Capillary tube

Field piping Service port 5/16″

Indoor unit 4-way valve

Low pressure switch

Filter

High pressure switch

Muffler

Heat exchanger Field piping J9.5

Branch duct connection

Service port 5/16″

C1220T-0

Option

Field piping J15.9 Compressor

C1220T-0

Outdoor unit

Field piping Filter

Heating Cooling

Field piping

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

Stop valve (with service port 5/16’ flare)

Indoor unit

3TW26745-2

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQ200-250B (Twin) Filter

Capillary tube

Receiver

Solenoid valve

Filter

Model RZQ200B RZQ250B

Check valve

Check valve

Fan

Check Check valve valve

Electronic expansion valve Electronic expansion valve

Filter

A 9.52 12.70

Heat exchanger pipe

Solenoid valve

Heat exchanger 4-way valve

High pressure sensor

Pressure regulating valve

Filter

Filter

Fan

Capillary tube

Field piping

Filter Capillary tube

Compressor

Field piping

High pressure switch

Oil separator

Filter

High pressure switch

Oil separator

Indoor heat exchanger

Check valve

Compressor

Option Indoor heat exchanger

Low pressure sensor

Field piping J22.20 Stop valve (with service port on field piping side J 7.9mm flare connection)

Filter

Field piping J A Branch pipe

Indoor unit

Solenoid valve

Outdoor unit

Field piping

Fan

Field piping

Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.

Indoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

34

• Split Sky Air • Outdoor Units

3TW26565-2

• Outdoor Units • R410A • RZQ-B

7

Piping diagram

2 7 RZQ100-125-140B (Triple) Indoor unit Heat exchanger One way valve One way valve

Stop valve (with service port 5/16’ flare)

Filter

Field piping Filter

Capillary tube

Solenoid valve

Field piping

One way valve

Heat exchanger

One way valve

One way valve

Electronic expansion valve

Capillary tube

Indoor unit

Receiver

Heat exchanger

Strainer Capillary tube

Service port 5/16″ 4-way valve Field piping J9.5 C1220T-0 Field piping Filter

Field piping

Indoor unit Heat exchanger

Filter

Low pressure switch

High pressure switch

Muffler

Field piping J15.9 C1220T-0

Service port 5/16″

Branch duct connection Option

Compressor

Outdoor unit Field piping Filter

Field piping

Heating Cooling

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

3TW26745-3

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQ200-250B (Triple) Filter

Model RZQ200B RZQ250B

Filter

Heat exchanger pipe

Solenoid valve Check valve

Check valve

Fan

Check Check valve valve

Electronic expansion valve Electronic expansion valve

Indoor heat exchanger

Filter

A 9.52 12.70

Capillary tube

Receiver

Solenoid valve

Heat exchanger 4-way valve

Field piping

High pressure sensor

Pressure regulating valve

Check valve

Field piping J A Field piping

Fan

Field piping

Branch pipe

Indoor unit

Option Indoor heat exchanger

Compressor Capillary tube

Field piping J22.20 Stop valve (with service port on field piping side J 7.9mm flare connection)

Filter Capillary tube

Filter

High pressure switch

High pressure switch

Low pressure sensor

Compressor

Filter

Indoor heat exchanger

Oil separator

Indoor unit

Filter

Filter

Field piping

Oil separator

Fan

Solenoid valve

Outdoor unit Field piping

Fan

Field piping

Indoor unit

Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

• Split Sky Air • Outdoor Units

3TW26565-3

35

• Outdoor Units • R410A • RZQ-B

7

Piping diagram

2 7

RZQ100-125-140B (Double twin) Heat exchanger

Indoor unit

One way valve One way valve

One way valve

One way Capillary valve tube

One way valve

Field piping Field piping

Filter Heat exchanger

Indoor unit

Filter Solenoid valve

Field piping J9.5

Service port 5/16″

Field piping Filter

Electronic expansion valve Strainer Capillary tube

Capillary tube Receiver

Field piping J15.9

Heat exchanger

4-way valve

Field piping Heat exchanger

Indoor unit

Field piping J9.5

Branch duct connection

Filter

C1220T-0

Low pressure sensor

High pressure switch

Option Service port 5/16″

Field piping J15.9 Muffler

C1220T-0 Compressor Field piping Filter

Field piping

Heat exchanger

Outdoor unit Heating Cooling

Field piping J9.5 Stop valve (with service port 5/16’ flare)

Field piping J15.9

Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.

Field piping Field piping

Filter

3TW26755-4

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

RZQ200-250B (Double twin) Filter Solenoid valve

Field piping

Filter

Check valve

Check valve

Fan

Check Check valve valve

Electronic expansion valve Electronic expansion valve

Indoor unit Field piping J 9.52

Indoor heat exchanger

Heat exchanger pipe

Solenoid valve

Filter

Field piping

Fan

Model RZQ200B RZQ250B

Capillary tube

A 9.52 12.70

Receiver

Indoor heat exchanger

Heat exchanger Field piping J15.90

4-way valve

Field piping

High pressure sensor

Pressure regulating valve

Field piping J A Compressor

Field piping

Fan

Field piping J22.20

Field piping

Indoor unit

Field piping J 9.52

Indoor heat exchanger

Field piping J15.90

Capillary tube

Capillary tube

Filter

Option

Low pressure sensor Stop valve (with service port on field piping side J 7.9mm flare connection)

Compressor

Filter

High pressure switch

Branch pipe

High pressure switch

Oil separator

Indoor heat exchanger

Oil separator

Indoor unit

Filter

Filter

Check valve

Filter

Field piping

Fan

Solenoid valve

Outdoor unit Field piping

Fan

Field piping

Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.

Indoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

36

• Split Sky Air • Outdoor Units

3TW26565-4A

• Outdoor Units • R410A • RZQ-B

8

Wiring diagram

2 8

RZQ71B8V3B Indoor

: Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector

NOTE 1.

L N

Outdoor

: Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green ON OFF

NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off. El. comp. assy front

A1P A2P BS1 C1-C2-C3 DS1 F1U HAP (A1P) HAP (A2P) H1P (A1P)

Printed circuit board Printed circuit board (INV) Push button switch (forced defrost / pump down) Capacitor Dip switch Fuse (T6, 3A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red)

K1M(A2P) K1R(A1P) K2R(A1P) K2R(A2P) L1R M1C M1F PS Q1DI R1-R2 R1T

Magnetic contactor Magnetic relay (Y1S) Magnetic relay (Y2S) Magnetic relay Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air)

R2T R3T R4T R5T S1PH S1NPL RC TC V1R

Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal receiver circuit Signal transmission circuit Power module

V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F

View A

Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter

2TW26736-1A

Noise filter (with surge absorber)

RZQ100-125B8V3B Indoor

: Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector

NOTE 1.

L N

Outdoor

: Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green

ON OFF

NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off.

A1P A2P BS1 C1-C2-C3 DS1 E1HC F1U F2U F3U HAP (A1P) HAP (A2P) H1P (A1P)

Printed circuit board Printed circuit board (INV) Push button switch (forced defrost / pump down) Capacitor Dip switch Crankcase heater Fuse (T 6,3A/250V) Fuse Fuse (B 5A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red)

K1M(A2P) K1R(A1P) K2R(A1P) K3R(A1P) K4R (A1P) L1R M1C M1F PS Q1DI R1-R2 R1T

El. comp. assy front

Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (E1HC) Magnetic relay (Y2S) Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air)

R2T R3T R4T R5T S1PH S1NPL TC V1R

Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal transmission circuit Power module

• Split Sky Air • Outdoor Units

V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F Z1F

View A

Reactor box

Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter Noise filter Noise filter (with surge absorber)

2TW26746-1

37

• Outdoor Units • R410A • RZQ-B

8

Wiring diagram

2 8 RZQ100-125-140B7W1B Indoor

: Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector

NOTE 1.

L N

Outdoor

: Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green

ON OFF

NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off.

A1P A2P BS1 C1-C2-C3 DS1 F1U (A2P) F2U F3U F4U HAP (A1P) HAP (A2P) H1P (A1P)

Printed circuit board Printed circuit board (INV) Push button switch (forced defrost / pump down) Capacitor Dip switch Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (B 10A/250V) Fuse (B 10A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red)

K1M(A2P) K1R(A1P) K2R(A1P) K3R(A1P) K4R, K5R L1R M1C M1F PS Q1DI R1-R2

RZQ200-250B7

Reactor box El. comp. assy front

Magnetic contactor Magnetic relay (Y1S) Magnetic relay (Y2S) Magnetic relay (E1HC) Magnetic relay Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor

Power supply

R1T R2T R3T R4T R5T S1PH S1NPL RC TC V1R

Thermistor (air) Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal receiver circuit Signal transmission circuit Power module

V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F Z1F

View A

Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter

2TW26766-1

Noise filter Noise filter (with surge absorber)

Indoor

400V 3N ∼50Hz

Printed circuit board Main Inverter Fan motor Noise filter current sensor Push button switch Mode, set, return, test, forced defrost C2-C5,C63,C65 Capacitor DS1 Dip switch E1HC, E2HC Crankcase heater B ) (A4P) F1U Fuse (250V, 5A j B ) (A1P) F1U, F2U Fuse (250V, 10Aj F5U Field fuse H1P-H7P Pilot lamp (Pilotlamp service monitor - orange) Prepare test--------Flickering [H2P] Malfunction detection---Light up HAP Pilot lamp (Pilotlamp service monitor - green) K1 Magnetic relay K2S Magnetic relay (M2C) K2 Magnetic contactor (M1C) K2M Magnetic contactor (M2C) K1R-K7R Magnetic relay K1R K2M (A1P) K2R Y1S K3R E1HC (A1P) K4R E2HC (A1P) K5R Y2S K6R Y3S K7R Y4S L1R Reactor M1C, M2C Motor compressor M1F Motor fan PS Power circuit Q1DI Earth leakage breaker (max. 30mA) Q1RP Phase reversal detect circuit R10 Resistor (current sensor) R50, R59 Resistor R95 Resistor (current limiting) R1T, R32T Thermistor R1T Air (A1P) R32T M2C Discharge R1T Fin type (A2P) R4T Coil-deicer R2T Suction R5T Coil-outlet R31T M1C Discharge S1NPH Pressure sensor (high)

(NOTE 4)

A1P-A5P A1P A2P A3P A4P A5P BS1-BS5

38

ON XXX = Color of PCB connector YYY = (Marked) color of wire connector ZZZ = Color of wire

OFF

(NOTE 4)

(NOTE 4)

Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. 3. : Terminal strip : Connector : Terminal : Protective earth (screw) 4. For use of the option adaptor, how to use BS1 ∼ BS5 and DS1 switch and connection to X1M(A1P) or X3M refer to the installation manual. 5. Do not operate the unit by short-circuiting protection device S1PH, S2PH 6. BLK: Black / WHT: White / RED: Red / BLU: Blue GRY: Grey / BRN: brown / GRN: Green / YLW: Yellow / PNK: Pink

Detail of M1C, M2C

S1NPL S1PH, S2PH T1A T1R V1CP, V2CP V1R, V2R V1R X1M X2M X3M X4M

Pressure sensor (low) Pressure switch (high) current sensor Transformer(230V/20V) Safety devices input Power module (A2P) Power module (A3P) Terminal strip (Control) (A1P) Terminal (Power supply indoor) Terminal (Control) Terminal strip (Power supply)

Y1E Electronic expansion valve (Main) Y2E Electronic expansion valve (Subcool) Y1S-Y4S Solenoid valve Y1S 4-way valve Y2S Hot gas Y3S Receiver gas purge Y4S Liquid pipe Z1C, Z5C Noise filter (ferrite core) Z1F Noise filter (with surge absorber) Option connectors X36A Connector adaptor power supply

• Split Sky Air • Outdoor Units

Front layer

Rear layer Position in switch box

2TW26566-1

• Outdoor Units • R410A • RZQ-B

9

Sound data

9-1

Sound pressure spectrum

2 RZQ71B8V3B - Cooling Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

3TW26737-1

3TW26737-2

Octave band center frequency (Hz)

NOTES 1 2 3 4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

1 2 3 4

Measuring location (discharge side)

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

Measuring location (discharge side)

RZQ100B8V3B - Heating RZQ100B7W1B Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

3TW26747-1

Octave band center frequency (Hz)

3TW26747-2

NOTES

4

Octave band center frequency (Hz)

NOTES

RZQ100B8V3B - Cooling RZQ100B7W1B

1 2 3

9

RZQ71B8V3B - Heating

Octave band center frequency (Hz)

NOTES

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

1 2 3 Measuring location (discharge side)

• Split Sky Air • Outdoor Units

4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side)

39

• Outdoor Units • R410A • RZQ-B

9

Sound data

9-1

Sound pressure spectrum

2 9

RZQ125B8V3B - Heating RZQ125B7W1B Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

RZQ125B8V3B - Cooling RZQ125B7W1B

3TW26757-1

3TW26757-2

Octave band center frequency (Hz)

NOTES 1 2 3 4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

1 2 3 Measuring location (discharge side)

4

3TW26787-2

Octave band center frequency (Hz)

NOTES

40

Measuring location (discharge side)

Sound pressure level [dB(A)]

3TW26787-1

4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

RZQ140B8V3B - Heating

Sound pressure level [dB(A)]

RZQ140B8V3B - Cooling

1 2 3

Octave band center frequency (Hz)

NOTES

Octave band center frequency (Hz)

NOTES

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

1 2 3 Measuring location (discharge side)

• Split Sky Air • Outdoor Units

4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

Measuring location (discharge side)

• Outdoor Units • R410A • RZQ-B

9

Sound data

9-1

Sound pressure spectrum

2 9 Sound pressure level [dB(A)]

RZQ250B7

Sound pressure level [dB(A)]

RZQ200B7

3TW26567-1

3TW26577-1

Octave band center frequency (Hz)

NOTES 1 2 3 4

Octave band center frequency (Hz)

NOTES

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil

Microphone

1 2

Switchbox

Location of microphone

• Split Sky Air • Outdoor Units

3 4

Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Coil

Microphone

Switchbox

Location of microphone

41

• Outdoor Units • R410A • RZQ-B

9

Sound data

9-2

Sound power spectrum

2 9

RZQ100B8V3B - Cooling RZQ100B7W1B Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

RZQ71B7V3B - Cooling

3TW26737-3

3TW26747-3

Octave band center frequency (Hz)

NOTES 1 2 3 4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

1 2 3 4

RZQ125B8V3B - Cooling RZQ125B7W1B Sound pressure level [dB(A)]

3TW26787-3

Octave band center frequency (Hz)

NOTES

42

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

RZQ140B8V3B - Cooling

Sound pressure level [dB(A)]

3TW26757-3

1 2 3 4

Octave band center frequency (Hz)

NOTES

Octave band center frequency (Hz)

NOTES

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

• Split Sky Air • Outdoor Units

1 2 3 4

Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa

• Outdoor Units • R410A • RZQ-B

9

Sound data

9-2

Sound power spectrum

2 Sound power level (dB)

3TW26567-2

3TW26577-2

Octave band center frequency (Hz)

NOTES 1 2 3

9

RZQ250B7

Sound power level (dB)

RZQ200B7

Octave band center frequency (Hz)

NOTES

dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2. Measured according to ISO 3744

• Split Sky Air • Outdoor Units

1 2 3

dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2. Measured according to ISO 3744

43

Liquid side junction Suction gas side junction

Liquid side header

Discharge gas side header

10

44 1TW25799-1E

Liquid side junction

10

Closed pipes

Discharge gas side junction

• Outdoor Units • R410A • RZQ-B

Installation

10 - 1 Refnet pipe systems

2

• Split Sky Air • Outdoor Units Reducers - Expanders

• Outdoor Units • R410A • RZQ-B

10

Installation

10 - 2 Service space

2 10

RZQ71∼140B A. Non stacked installation

Legend Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present

In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.

In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models.

B. Stacked installation 2. Obstacles exist in front of the air inlet

1. Obstacles exist in front of the outlet side

Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass.

C. Multiple-row installation 1. Installation of one unit per row

2. Installing multiple units (2 units or more) in lateral connection per row

Relation of dimensions of H, A, and L are shown in the table below. L≤H H