RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit
Split Sky Air
air conditioning systems
technical data
Split - Sky Air
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com
EEDE05-1/3 • 05/2005 Prepared in Belgium by Goekint Graphics
Specifications are subject to change without prior notice.
• Outdoor Units • R410A • RZQ-B
TABLE OF CONTENTS RZQ-B
1 2
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Dimensional drawings and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Refnet pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
11
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• Split Sky Air • Outdoor Units
1
• Outdoor Units • R410A • RZQ-B
o t o aB i d 0- l t 1Q pu4Z 1 SOR
Features
2 1
2
•
Outdoor units for pair application
•
The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners.
•
During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy.
•
Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
•
The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level
•
Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency
•
An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures.
•
A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
2
Specifications
2 2-1 TECHNICAL SPECIFICATIONS Casing Dimensions
Daikin white Painted galvanized steel plate
Packing
Height
mm
900
1475
1475
1475
mm
980
980
980
980
Depth
mm
420
420
420
420
Height
mm
770
1345
1345
1345
Width
mm
900
900
900
900
Depth
mm
320
320
320
320
kg
68
106
106
106
kg
72
111
111
111
mm
857
857
857
857
2
2
2
2
mm
1.40
1.40
1.40
1.40
3
5
5
5
m2
0.641
1.131
1.131
1.131
34
60
60
60
Machine Weight Dimensions
Length Fin Pitch Nr of Passes Face Area Nr of Stages
Tube type Fin
Type
WF fin Anti-corrosion treatment (PE)
Type
Propeller
Discharge direction
Horizontal
Quantity
1
2
2
2
Air Flow Rate (nominal)
Cooling
m3/min
54.50
103.0
103.0
99.0
Heating
m3/min
48.10
101.0
101.0
100.0
Motor
Quantity
1
2
2
2
Model
Fan Compressor
Speed (nominal at 230V) Motor
KFD-325-70-8A
Steps
8
8
8
8
Cooling
rpm
818
789
789
782
Heating
rpm
715
775
775
767
Output
W
70
70
70
70
Drive
direct drive 1
1
1
1
Model
2YC63BXD
JT100G-VD
JT1G-VDYR@T
JT100G-VD
Type
Hermetically sealed swing compressor
Quantity Motor
Motor Output
W
Hermetically sealed scroll compressor
1800
2200
2200
2200
_
33
33
33 -15.0
Starting Method
Inverter driven
Crankcase Heater
W
Min
°CDB
-15.0
-15.0
-15.0
Max
°CDB
50.0
50.0
50.0
50.0
Heating
Min
°CWB
-20.0
-20.0
-20.0
-20.0
Max
°CWB
15.5
15.5
15.5
15.5
Cooling
Sound Power
dBA
63.0
65.0
65.0
66.0
Sound Pressure
dBA
47.0
49.0
49.0
50.0
Heating
Sound Pressure
dBA
49.0
51.0
51.0
52.0
Sound Level (Night quiet)
Cooling
Sound Pressure
dBA
43.0
45.0
45.0
45.0
Refrigerant
Type kg
2.80
4.30
4.30
4.30
Operation Range Cooling
Sound Level (nominal)
Charge
R-410A
Control Nr of Circuits
2
Hi-XSS(8) Treatment
Motor
RZQ125B8V3B
Width
Nr of Rows
Fan
RZQ100B7W1B
Colour
Gross Weight Heat Exchanger
RZQ100B8V3B
Material
Unit
Weight
RZQ71B8V3B
Expansion valve (electronic type) 1
• Split Sky Air • Outdoor Units
1
1
1
3
• Outdoor Units • R410A • RZQ-B
2-1 TECHNICAL SPECIFICATIONS Refrigerant Oil
RZQ71B8V3B
Type Charged Volume
2
Piping connections
Liquid (OD)
RZQ100B8V3B
l Quantity
0.8
1.0
1.0
1.0
1
1
1
1
9.52
9.52
1
1
Flare connection
Diameter (OD) Gas
mm
Quantity
9.52
9.52
1
1
Type
Flare connection
Diameter (OD) Drain
mm
Quantity Type
Piping Length
RZQ125B8V3B
Daphne FVC68D
Type
2
RZQ100B7W1B
Daphne FVC50K
15.9
15.9
15.9
15.9
3
3
3
3
26
26
26
Hole
Diameter (OD)
mm
26
Minimum
m
5
5
5
5
Maximum
m
50
75
75
75
Equivalent
m
70
95
95
95
Chargeless m
30
30
30
30
Additional Refrigerant Charge
kg/m
see installation manual 4PW21412-1
Installation Maximum height difference
m
30.0
30.0
Max. internunit level difference m
0.5
0.5
Heat Insulation
30.0
30.0
0.5
0.5
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Safety Devices
High pressure switch Fan motor thermal protector Fuse
Standard Accessories
Item
Tie-wraps
Quantity
2
2
Item Quantity
2-1 TECHNICAL SPECIFICATIONS Casing Dimensions
Colour Material Packing
Unit
Weight Heat Exchanger
Machine Weight Gross Weight Dimensions
Tube type Fin Fan
4
2
2
Installation manual
Height Width Depth Height Width Depth
mm mm mm mm mm mm kg kg mm
Length Nr of Rows Fin Pitch mm Nr of Passes Face Area m2 Nr of Stages Type Treatment
Type Discharge direction Quantity Air Flow Rate Cooling (nominal) Heating External static pressure (Max) Motor Quantity Model Position
m3/min m3/min
1
1
1
1
RZQ125B7W1B
RZQ140B7W1B
RZQ200B7W1B
RZQ250B7W1B
Daikin white Painted galvanized steel plate 1475 1475 1753 1753 980 980 1055 1055 420 420 860 860 1345 1345 1600 1600 900 900 930 930 320 320 765 765 106 106 225 226 111 111 236 237 857 857 1640 1640 2 2 2 2 1.40 1.40 2.00 2.00 5 5 16 16 1.131 1.131 1.948 1.948 60 60 54 54 Hi-XSS(8) WF fin Non-symmetric waffle louvre Anti-corrosion treatment (PE) Corrosion resistant Propeller Horizontal Vertical 2 2 1 1 99.0 99.0 175 175 100.0 100.0 175 175 60 Pa in high static pressure 2 2 1 1 KFD-325-70-8A Brushless DC Vertical
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
2-1 TECHNICAL SPECIFICATIONS Motor
Speed (nominal at Steps 230V) Cooling rpm Heating rpm Fan Motor Output W Drive Compressor Quantity Motor Model Type Speed rpm Motor W Output Starting Method Crankcase W Heater Motor Model Type Speed rpm Motor W Output Starting Method Crankcase W Heater Operation Range Cooling Min °CDB Max °CDB Heating Min °CWB Max °CWB Sound Level Cooling Sound dBA (nominal) Power Sound dBA Pressure Heating Sound dBA Power Sound dBA Pressure Sound Level Cooling Sound dBA (Night quiet) Pressure Refrigerant Type Charge kg Control Nr of Circuits Refrigerant Oil Type Charged Volume l Piping Liquid (OD) Quantity connections Type Diameter mm (OD) Gas Quantity Type Diameter mm (OD) Drain Quantity Type Diameter mm (OD) Piping Length Minimum m Maximum m Equivalent m Chargeless m Additional Refrigerant Charge kg/m Installation height Maximum m difference Max. internunit level difference m Heat Insulation Defrost Method Defrost Control Capacity Control Method
RZQ125B7W1B
RZQ140B7W1B
RZQ200B7W1B
RZQ250B7W1B
8 782 767 70
8 782 767 70
8 760 825 750
8 760 825 750
Direct drive 1 JT1G-VDYR@T
1 2 JT1G-VDYR@T Hermetically sealed scroll compressor 2200 2200
2200
2
2 2
Inverter 900~6480 2200
Direct on line 33
33
-
Hermetically sealed scroll compressor -
-
33
33 ON - OFF 2900 4500
Direct on line -
-
33
-15.0 50.0 -20.0 15.5 66.0
-15.0 50.0 -20.0 15.5 66.0
-5.0 46.0 -15.0 15.0 -
-5.0 46.0 -15.0 15.0 -
50.0
50.0
-
-
-
-
78.0
78.0
-
-
57.0
57.0
45.0
45.0
-
-
R-410A 4.30 8.00 Expansion valve (electronic type) 1 1 Daphne FVC68D 1.0 1.7 + 1.6 1 1 Flare connection 9.52 9.52
4.30 1 1.0 1 9.52 1
1
3
5 75 95 30
1.7 + 1.6 1 12.7 1 Braze connection
15.9
22.2
22.2
3
-
-
Hole 26
1
1
Flare connection 15.9
9.00
26
30.0
5 5 75 100 95 30 30 see installation manual 4PW21412-1 30.0 30.0
30.0
0.5
0.5
0.5
0.5
5 100 30
Both liquid and gas pipes Pressure equalising Sensor for outdoor heat exchanger temperature Inverter controlled
• Split Sky Air • Outdoor Units
Reversed cycle Sensor for outdoor heat exchanger temperature Inverter controlled
5
• Outdoor Units • R410A • RZQ-B
2-1 TECHNICAL SPECIFICATIONS
RZQ125B7W1B
Safety Devices
2 2
Standard Accessories
Item Quantity Item Quantity Item Quantity
2
RZQ200B7W1B
2
1
1 Installation manual
1
1
RZQ250B7W1B
High pressure switch Fan motor driver overload protector Inverter overload protector Overcurrent relay PC board fuse Installation manual 1 1 Additional refrigerant label 1 1 Connection pipes 4 4
Installation manual
2-2 ELECTRICAL SPECIFICATIONS Power Supply
RZQ140B7W1B
High pressure switch Fan motor thermal protector Fuse Tie-wraps
RZQ71B8V3B
RZQ100B8V3B
RZQ100B7W1B
RZQ125B8V3B
Name
V3
V3
W1B
V3
Phase
1
1
3N
1
Frequency
Hz
50
50
50
50 230
Voltage
V
230
230
400
Current
Recomended fuses
A
20
32
20
32
Voltage range
Minimum
V
207
207
360
207
Maximum
V
253
253
440
253
Wiring connections
For Power Supply Remark
see installation manual 4PW21412-1
For connection with indoor
see installation manual 4PW21412-1
Remark
Power Supply Intake
Outdoor unit only
2-2 ELECTRICAL SPECIFICATIONS Power Supply
Current
RZQ125B7W1B
RZQ140B7W1B
RZQ200B7W1B
Name
W1B
W1B
W1
W1
Phase
3N
3N
3N~
3N~
Frequency
Hz
50
50
50
50
Voltage
V
400
400
400
400
Nominal running current
Cooling
A
-
-
refer to electrical data indoor outdoor combination
Heating
A
-
-
refer to electrical data indoor outdoor combination
Starting current (cooling/heating)
Voltage range Wiring connections
RZQ250B7W1B
-
-
refer to electrical data indoor outdoor combination
Maximum running current
A
-
-
refer to electrical data indoor outdoor combination
Recomended fuses
A
20
20
32
32
Minimum
V
360
360
360
360
Maximum
V
440
440
440
440
For Power Supply Quantity Remark For connection with indoor
-
5
see installation manual 4PW21412-1
earth wire included
Quantity
-
4
Remark
see installation manual 4PW21412-1
earth wire included
Power Supply Intake
Outdoor unit only
Notes
See seperate drawings for electrical data Power supply to the FDQ indoor unit is separate
NOTES
6
1
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
2
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m.
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
3
Electrical data
2 RZQ71-125B7 Unit combination Indoor unit Outdoor unit
3 Power supply Voltage range MCA
Hz-volts
TOCA
MFA
Comp. MSC RLA
OFM kW
IFM FLA
kW
FLA
3D048637A
SYMBOLS MCA TOCA MFA MSC
RLA OFM IFM FLA kW
NOTES
: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (See note 7) (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)
1
2 3
4 5 6 7 8
RLA is based on the following conditions: Power supply: 50Hz 230V Heating Cooling Indoor temperature 20.0°CDB Indoor temperature 27°CDB/19°CWB Outdoor temperature 7.0°CDB/6.0°CWB Outdoor temperature 35°CDB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
7
• Outdoor Units • R410A • RZQ-B
3
Electrical data
2 3
RZQ71-125-140B7 Unit combination Indoor unit Outdoor unit
Hz-volts
Power supply Comp. Voltage range MCA TOCA MFA MSC RLA
OFM kW
IFM FLA
kW
FLA
3D048638A
SYMBOLS MCA TOCA MFA MSC
RLA OFM IFM FLA kW
NOTES
: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (See note 7) (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)
1
2 3
4 5 6 7 8
8
RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Heating Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
3
Electrical data
2 3
RZQ200-250B7 Indoor unit
Unit combination Outdoor unit
Power supply Voltage range
Hz-volts
MCA
TOCA
MFA
Comp. MSC RLA
OFM kW
IFM FLA
kW
FLA
Max. 50Hz 440V Min. 50Hz 360V
Max. 50Hz 440V Min. 50Hz 360V
3TW26561-4A
SYMBOLS MCA TOCA MFA MSC
RLA OFM IFM FLA kW
NOTES
: Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW)
1
2 3
4 5 6 7 8
RLA is based on the following conditions: Power supply: 50Hz - 400V Heating Cooling Indoor temperature 20.0°CDB Indoor temperature 27°CDB/19°CWB Outdoor temperature 7.0°CDB/6.0°CWB Outdoor temperature 35°CDB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
9
• Outdoor Units • R410A • RZQ-B
4
Options
2 4
RZQ71∼140B7V3B Kit name Name of option
RZQ71B7V3B
RZQ100B8V3B
RZQ125B8V3B
RZQ100B7W1B Central drain plug Refrigerant branch piping
RZQ125B7W1B
RZQ140B7W1B
KKPJ5F180 Twin
KHRQ22M20TA7
Triple
-
Double twin
-
Demand adapter kit
KHRQ127H7 -
KHRQ22M20TA7 (3x) KRP58M51 3TW26739-1
Available options for RZQ200,250B7W1B Name of option Central drain pan kit Refrigerant branch piping
Kit name RZQ200B7W1B
RZQ250B7W1B KWC26B280
Twin Triple Double twin
KHRQ22M20TA7 KHRQ250H7 KHRQ22M20TA7 (3x) 4TW26569-3
10
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-1
Combination table
2 5
Possible combinations and standard capacity for twin, triple and double twin application Possible indoor combination Simultaneous operation
Outdoor models
Twin
Triple
Out
Out
In
In
In
In
Double twin Out
In
In
In
In
RZQ71B8V3B
35-35 (KHRQ22M20TA7)
RZQ100B8V3B RZQ100B7W1B
50-50 (KHRQ22M20TA7)
35-35-35 (KHRQ127H7)
RZQ125B8V3B RZQ125B7W1B
60-60 (KHRQ22M20TA7)
50-50-50 (KHRQ127H7)
35-35-35-35 (3x KHRQ22M20TA7)
RZQ140B7W1B
71-71 (KHRQ22M20TA7)
50-50-50 (KHRQ127H7)
35-35-35-35 (3x KHRQ22M20TA7)
In
3TW26739-2
NOTES 1
Possible indoor units: FCQ35-71, FFQ35-60, FHQ35-71, FBQ35-71, FUQ71, FAQ71
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote control that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
Possible combinations and standard capacity for twin, triple and double twin operation Possible indoor combination Simultaneous operation
Outdoor models
Twin
Triple
Out
Out
In
In
In
In
Double twin Out
In
In
In
In
RZQ200B7W1B
100-100 (KHRQ22M20TA7)
60-60-60 71-71-71 (KHRQ250H7)
50-50-50-50 (3x KHRQ22M20TA7)
RZQ250B7W1B
125-125 (KHRQ22M20TA7)
---
60-60-60-60 (3x KHRQ22M20TA7)
In
3TW26569-2
NOTES 1
Possible indoor units: FCQ50-125, FFQ50-60, FHQ50-125, FBQ50-125, FAQ71-100, FUQ71-125, FDQ125
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
• Split Sky Air • Outdoor Units
11
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ71B8V3B
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity Cooling capacity
Indoor
EWB
230V [50Hz]
EDB
(°C)
(°C)
16.0 18.0 19.0 19.5 22.0 24.0
22 25 27 27 30 32
25 SHC (kW) 4.39 4.82 4.80 4.79 4.73 4.66
TC (kW) 6.47 7.43 7.58 7.66 8.05 8.37
CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85
TC (kW) 6.46 7.20 7.35 7.43 7.81 8.12
30 SHC (kW) 4.43 4.72 4.71 4.70 4.64 4.58
Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93
TC (kW) 6.66 6.95 7.10 7.17 7.55 7.85
35 SHC (kW) 4.62 4.61 4.60 4.59 4.54 4.48
CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02
TC (kW) 6.39 6.67 6.82 6.89 7.26 7.55
40 SHC (kW) 4.49 4.47 4.46 4.46 4.41 4.35
CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048602
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ71D 19 (0.10)
FCQ71B 18 (0.10)
FBQ71 19 (0.11)
FHQ71 17 (0.10)
FAQ71 19 (0.08)
FUQ71 19 (0.07)
Twin
Model AFR (BF)
FCQ35x2 14x2 (0.16x2)
FFQ35x2 10x2 (0.25x2)
FBQ35x2 11.5x2 (0.15x2)
FHQ35x2 13x2 (0.2x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ71D 1.98 1.97
FCQ71B 2.16 2.56
FBQ71 2.14 2.09
FHQ71 2.46 2.67
FAQ71 2.36 2.42
FUQ71 2.21 2.34
Twin
Model Cooling Heating
12
FCQ35x2 2.27 2.62
FFQ35x2 2.29 2.64
FBQ35x2 2.25 2.20
FHQ35x2 2.53 2.81
• Split Sky Air • Outdoor Units
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ100B8V3B (Pair + Twin/triple)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity Cooling capacity
Indoor
EWB
230V [50Hz]
EDB
(°C)
(°C)
16.0 18.0 19.0 19.5 22.0 24.0
22 25 27 27 30 32
25 SHC (kW) 6.19 6.78 6.76 6.75 6.66 6.57
TC (kW) 9.12 10.5 10.7 10.8 11.3 11.8
CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85
TC (kW) 9.10 10.1 10.4 10.5 11.0 11.4
30 SHC (kW) 6.25 6.65 6.63 6.62 6.54 6.45
Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93
TC (kW) 9.38 9.79 10.0 10.1 10.6 11.1
35 SHC (kW) 6.51 6.49 6.48 6.47 6.39 6.30
CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02
TC (kW) 9.00 9.40 9.60 9.71 10.2 10.6
40 SHC (kW) 6.32 6.30 6.29 6.28 6.21 6.13
CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048603
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ100D 30 (0.11)
FCQ100B 28 (0.16)
FBQ100 27 (0.20)
FHQ100 24 (0.14)
FAQ100 23 (0.10)
FUQ100 29 (0.07)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
(m3/min)
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ35Bx3 14x3 (0.16x3)
FFQ35x3 10x3 (0.25x3)
FBQ35x3 11.5x3 (0.15x3)
FHQ35x3 13x3 (0.2x3)
FCQ35Bx3 2.78 3.31
FFQ35x3 2.79 3.21
FBQ35x3 3.01 3.16
FHQ35x3 3.32 3.79
Twin
Model AFR (BF)
FCQ50Bx2 15x2 (0.16x2)
FFQ50x2 12x2 (0.16x2)
FBQ50x2 14x2 (0.15x2)
FHQ50x2 13x2 (0.1x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ100D 2.44 2.56
FCQ100B 2.64 3.14
FBQ100 2.86 3.00
FHQ100 3.15 3.60
Triple
FAQ100 2.78 3.39
FUQ100 3.12 3.28
Model Cooling Heating
Twin
Model Cooling Heating
FCQ50Bx2 2.78 3.31
FFQ50x2 2.79 3.21
FBQ50x2 3.01 3.16
FHQ50x2 3.32 3.79
• Split Sky Air • Outdoor Units
13
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ100B7W1B (Pair + Twin/triple)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity Cooling capacity
Indoor
EWB
400V [50Hz]
EDB
(°C)
(°C)
16.0 18.0 19.0 19.5 22.0 24.0
22 25 27 27 30 32
25 SHC (kW) 6.19 6.78 6.76 6.75 6.66 6.57
TC (kW) 9.12 10.5 10.7 10.8 11.3 11.8
CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85
TC (kW) 9.10 10.1 10.4 10.5 11.0 11.4
30 SHC (kW) 6.25 6.65 6.63 6.62 6.54 6.45
Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93
TC (kW) 9.38 9.79 10.0 10.1 10.6 11.1
35 SHC (kW) 6.51 6.49 6.48 6.47 6.39 6.30
CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02
TC (kW) 9.00 9.40 9.60 9.71 10.2 10.6
40 SHC (kW) 6.32 6.30 6.29 6.28 6.21 6.13
CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048605
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ100D 30 (0.11)
FCQ100B 28 (0.16)
FBQ100 27 (0.20)
FHQ100 24 (0.14)
FAQ100 23 (0.10)
FUQ100 29 (0.07)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
(m3/min)
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ35Bx3 14x3 (0.16x3)
FFQ35x3 10x3 (0.25x3)
FBQ35x3 11.5x3 (0.15x3)
FHQ35x3 13x3 (0.2x3)
FCQ35Bx3 2.78 3.31
FFQ35x3 2.79 3.21
FBQ35x3 3.01 3.16
FHQ35x3 3.32 3.79
Twin
Model AFR (BF)
FCQ50Bx2 15x2 (0.16x2)
FFQ50x2 12x2 (0.16x2)
FBQ50x2 14x2 (0.15x2)
FHQ50x2 13x2 (0.1x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ100D 2.44 2.56
FCQ100B 2.64 3.14
FBQ100 2.86 3.00
FHQ100 3.15 3.60
Triple
FAQ100 2.78 3.39
FUQ100 3.12 3.28
Twin
Model Cooling Heating
14
FCQ50Bx2 2.78 3.31
FFQ50x2 2.79 3.21
FBQ50x2 3.01 3.16
FHQ50x2 3.32 3.79
• Split Sky Air • Outdoor Units
Model Cooling Heating
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ125B8V3B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
16.0 18.0 19.0 19.5 22.0 24.0
22 25 27 27 30 32
230V [50Hz]
TC (kW) 11.4 13.1 13.3 13.5 14.2 14.7
25 SHC (kW) 7.73 8.48 8.45 8.44 8.33 8.21
CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85
TC (kW) 11.4 12.7 12.9 13.1 13.8 14.3
30 SHC (kW) 7.81 8.32 8.29 8.28 8.18 8.06
Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93
TC (kW) 11.7 12.2 12.5 12.6 13.3 13.8
35 SHC (kW) 8.14 8.12 8.09 8.08 7.99 7.88
CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02
TC (kW) 11.3 11.8 12.0 12.1 12.8 13.3
40 SHC (kW) 7.90 7.88 7.86 7.85 7.76 7.67
CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048604A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ125D 30 (0.13)
FCQ125B 31 (0.07)
FBQ125 35 (0.14)
FHQ125 30 (0.13)
Model AFR (BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125 32 (0.07)
FDQ125 45 (0.25)
Twin
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Model AFR (BF)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ125D 3.54 3.59
FCQ125B 3.88 4.36
FBQ125 3.98 3.99
Triple
FHQ125 4.45 4.50
FUQ125 4.05 4.36
FDQ125 4.15 3.69
Model Cooling Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
Double twin
Twin
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
• Split Sky Air • Outdoor Units
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
15
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ125B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
16.0 18.0 19.0 19.5 22.0 24.0
22 25 27 27 30 32
400V [50Hz]
TC (kW) 11.4 13.1 13.3 13.5 14.2 14.7
25 SHC (kW) 7.73 8.48 8.45 8.44 8.33 8.21
CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85
TC (kW) 11.4 12.7 12.9 13.1 13.8 14.3
30 SHC (kW) 7.81 8.32 8.29 8.28 8.18 8.06
Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93
TC (kW) 11.7 12.2 12.5 12.6 13.3 13.8
35 SHC (kW) 8.14 8.12 8.09 8.08 7.99 7.88
CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02
TC (kW) 11.3 11.8 12.0 12.1 12.8 13.3
40 SHC (kW) 7.90 7.88 7.86 7.85 7.76 7.67
CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048606A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ125D 30 (0.13)
FCQ125B 31 (0.07)
FBQ125 35 (0.14)
FHQ125 30 (0.13)
Model AFR (BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125 32 (0.07)
FDQ125 45 (0.25)
Twin
CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Model AFR (BF)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ125D 3.54 3.59
FCQ125B 3.88 4.36
FBQ125 3.98 3.99
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
FHQ125 4.45 4.50
FUQ125 4.05 4.36
FDQ125 4.15 3.69
Model Cooling Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
Double twin
Twin
16
AFR: BF: EWB: EDB: TC: SHC: PI:
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
• Split Sky Air • Outdoor Units
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ140B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
16.0 18.0 19.0 19.5 22.0 24.0
22 25 27 27 30 32
400V [50Hz]
TC (kW) 12.8 14.6 15.0 15.1 15.9 16.5
25 SHC (kW) 8.66 9.50 9.47 9.45 9.33 9.20
CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85
TC (kW) 12.7 14.2 14.5 14.7 15.4 16.0
30 SHC (kW) 8.74 9.31 9.29 9.27 9.16 9.03
Outdoor temp. (°CDB) CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93
TC (kW) 13.1 13.7 14.0 14.1 14.9 15.5
35 SHC (kW) 9.12 9.09 9.07 9.05 8.95 8.83
CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02
TC (kW) 12.6 13.2 13.4 13.6 14.3 14.9
40 SHC (kW) 8.84 8.82 8.80 8.79 8.69 8.59
CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D048607
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ140D 30 (0.07)
Model AFR (BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 18x2 19x2 17x2 19x2 19x2 (0.1x2) (0.11x2) (0.1x2) (0.07x2) (0.08x2)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
Twin
(m3/min)
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
Model Cooling Heating
FCQ140D 4.65 4.52
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69
Double twin
Twin
Model Cooling Heating
Model AFR (BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 4.81 4.95 4.99 4.99 4.92 5.52 5.06 5.69 5.05 5.22
• Split Sky Air • Outdoor Units
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69
17
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ200B7W1B (Pair / Twin / Triple / Double twin)
Coefficient of power input. (-)
Cooling
22.4
7.5
Cooling capacity (kW) Cooling capacity
Indoor TC (kW) 20.2 21.3 21.8 22.3 23.4 24.4
°CWB 16 18 19 20 22 24
400V [50Hz]
25 SHC (kW) 17.0 17.1 17.1 17.1 17.0 16.8
CPI (-) 0.82 0.83 0.84 0.84 0.85 0.86
TC (kW) 19.4 20.4 20.9 21.4 22.4 23.4
30 SHC (kW) 16.3 16.4 16.4 16.4 16.3 16.1
Outdoor temperature (°CDB) CPI (-) 0.90 0.91 0.92 0.92 0.94 0.95
TC (kW) 18.6 19.5 20.0 20.5 21.4 22.4
35 SHC (kW) 15.5 15.7 15.6 15.6 15.6 15.4
CPI (-) 0.98 0.99 1.00 1.01 1.02 1.03
TC (kW) 17.7 18.6 19.1 19.6 20.5 21.4
40 SHC (kW) 14.8 14.9 14.9 14.9 14.9 14.7
CPI (-) 1.06 1.07 1.08 1.09 1.10 1.12 3TW26561-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Pair
Model AFR (BF)
Triple
FDQ200 69 0.31
Model AFR (BF)
Twin
Model AFR (BF)
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 28x2 27x2 24x2 29x2 23x2 (0.16x2) (0.2x2) (0.14x2) (0.07x2) (0.1x2)
10. Rated power input of each model is tabulated below.
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 18x3 18x3 15x3 19x3 19x3 17x3 17x3 19x3 19x3 (0.1x3) (0.1x3) (0.11x3) (0.11x3) (0.11x3) (0.2x3) (0.1x3) (0.07x3) (0.08x3)
Double twin
Model AFR (BF)
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 15x4 12x4 14x4 13x4 (0.16x4) (0.16x4) (0.15x4) (0.1x4)
Pair
Model Cooling Heating
Triple
FDQ200 6.43 7.54
Model Cooling Heating
Twin
Model Cooling Heating
18
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 5.87 6.36 7.00 6.93 6.18 7.16 6.85 8.21 7.48 7.74
• Split Sky Air • Outdoor Units
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 6.18 6.18 6.20 6.69 6.69 7.37 7.37 7.30 6.50 7.54 7.54 7.32 7.21 7.21 8.65 8.65 7.88 8.14
Double twin
Model Cooling Heating
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 6.18 6.20 6.69 7.37 7.54 7.32 7.21 8.65
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2 5
RZQ250B7W1B (Pair / Twin / Double twin)
Coefficient of power input. (-)
Cooling
28
9.1
Cooling capacity (kW) Cooling capacity
Indoor TC (kW) 25.4 26.6 27.2 27.8 29.0 30.2
°CWB 16 18 19 20 22 24
400V [50Hz]
25 SHC (kW) 21.5 21.5 21.5 21.4 21.2 20.9
CPI (-) 0.79 0.80 0.80 0.81 0.81 0.82
TC (kW) 24.4 25.5 26.1 26.7 27.8 29.0
30 SHC (kW) 20.7 20.6 20.6 20.5 20.3 20.1
Outdoor temperature (°CDB) CPI (-) 0.88 0.89 0.90 0.91 0.92 0.93
TC (kW) 23.4 24.5 25.0 25.5 26.6 27.7
35 SHC (kW) 19.8 19.8 19.8 19.7 19.5 19.3
CPI (-) 0.98 0.99 1.00 1.01 1.02 1.03
TC (kW) 22.3 23.4 23.9 24.4 25.5 26.5
40 SHC (kW) 19.0 18.9 19.0 18.9 18.7 18.4
CPI (-) 1.08 1.09 1.10 1.11 1.12 1.13 3TW26571-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Pair
Model AFR (BF)
Double twin
FDQ250 89 0.34
Model AFR (BF)
Twin
Model AFR (BF)
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 18x4 15x4 19x4 17x4 (0.1x4) (0.11x4) (0.11x4) (0.2x4)
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 31x2 35x2 30x2 32x2 45x2 (0.07x2) (0.14x2) (0.13x2) (0.07x2) (0.25x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
Double twin
FDQ250 8.30 8.85
Model Cooling Heating
Twin
Model Cooling Heating
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 9.08 9.18 9.31 10.41 9.83 9.13 9.00 10.15
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 8.62 8.84 9.89 9.00 9.22 9.34 8.55 9.64 9.34 7.91
• Split Sky Air • Outdoor Units
19
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ71B8V3B (Pair + Twin)
Coefficient of power input. (-)
Heating
Rated point
Capacity range
Heating capacity Heating capacity
Indoor EDB (°C) 16.O 18.O 20.0 21.O 22.O 24.0
TC (kW) 5.14 5.14 5.13 5.13 5.12 5.12
230V [50Hz]
−15
CPI (-) 1.06 1.10 1.15 1.17 1.19 1.23
TC (kW) 5.68 5.67 5.67 5.66 5.66 5.65
−10
CPI (-) 1.12 1.16 1.21 1.23 1.25 1.30
TC (kW) 6.22 6.21 6.20 6.20 6.19 6.19
−5
Outdoor temp. (°CWB) CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36
TC (kW) 6.75 6.74 6.74 6.73 6.73 6.72
0
CPI (-) 1.23 1.28 1.33 1.35 1.38 1.43
TC (kW) 8.02 8.01 8.00 8.00 7.99 7.98
6
CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08
TC (kW) 8.64 8.62 8.61 8.61 8.60 8.59
10
CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048602
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ71D 19 (0.10)
FCQ71B 18 (0.10)
FBQ71 19 (0.11)
FHQ71 17 (0.10)
FAQ71 19 (0.08)
FUQ71 19 (0.07)
Twin
Model AFR (BF)
FCQ35x2 14x2 (0.16x2)
FFQ35x2 10x2 (0.25x2)
FBQ35x2 11.5x2 (0.15x2)
FHQ35x2 13x2 (0.2x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ71D 1.98 1.97
FCQ71B 2.16 2.56
FBQ71 2.14 2.09
FHQ71 2.46 2.67
FAQ71 2.36 2.42
FUQ71 2.21 2.34
Twin
Model Cooling Heating
20
FCQ35x2 2.27 2.62
FFQ35x2 2.29 2.64
FBQ35x2 2.25 2.20
FHQ35x2 2.53 2.81
• Split Sky Air • Outdoor Units
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ100B8V3B (Pair + Twin/triple)
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity Heating capacity
Indoor EDB
230V [50Hz]
−15
TC (kW) 7.16 7.15 7.15 7.14 7.14 7.13
(°C) 16.O 18.O 20.0 21.O 22.O 24.0
CPI (-) 1.01 1.05 1.09 1.12 1.14 1.18
TC (kW) 7.91 7.90 7.89 7.89 7.88 7.87
−10
CPI (-) 1.07 1.11 1.15 1.17 1.20 1.24
TC (kW) 8.66 8.65 8.64 8.63 8.63 8.62
−5
Outdoor temp. (°CWB) CPI (-) 1.12 1.16 1.21 1.23 1.26 1.30
TC (kW) 9.41 9.39 9.38 9.38 9.37 9.36
0
CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36
TC (kW) 11.2 11.2 11.2 11.2 11.2 11.2
6
CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08
TC (kW) 12.1 12.1 12.1 12.1 12.0 12.0
10
CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048603
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ100D 30 (0.11)
FCQ100B 28 (0.16)
FBQ100 27 (0.20)
FHQ100 24 (0.14)
FAQ100 23 (0.10)
FUQ100 29 (0.07)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
(m3/min)
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ35Bx3 14x3 (0.16x3)
FFQ35x3 10x3 (0.25x3)
FBQ35x3 11.5x3 (0.15x3)
FHQ35x3 13x3 (0.2x3)
FCQ35Bx3 2.78 3.31
FFQ35x3 2.79 3.21
FBQ35x3 3.01 3.16
FHQ35x3 3.32 3.79
Twin
Model AFR (BF)
FCQ50Bx2 15x2 (0.16x2)
FFQ50x2 12x2 (0.16x2)
FBQ50x2 14x2 (0.15x2)
FHQ50x2 13x2 (0.1x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ100D 2.44 2.56
FCQ100B 2.64 3.14
FBQ100 2.86 3.00
FHQ100 3.15 3.60
Triple
FAQ100 2.78 3.39
FUQ100 3.12 3.28
Model Cooling Heating
Twin
Model Cooling Heating
FCQ50Bx2 2.78 3.31
FFQ50x2 2.79 3.21
FBQ50x2 3.01 3.16
FHQ50x2 3.32 3.79
• Split Sky Air • Outdoor Units
21
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ100B7W1B (Pair + Twin/triple)
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity Heating capacity
Indoor EDB
400V [50Hz]
−15
TC (kW) 7.16 7.15 7.15 7.14 7.14 7.13
(°C) 16.O 18.O 20.0 21.O 22.O 24.0
CPI (-) 1.01 1.05 1.09 1.12 1.14 1.18
TC (kW) 7.91 7.90 7.89 7.89 7.88 7.87
−10
CPI (-) 1.07 1.11 1.15 1.17 1.20 1.24
TC (kW) 8.66 8.65 8.64 8.63 8.63 8.62
−5
Outdoor temp. (°CWB) CPI (-) 1.12 1.16 1.21 1.23 1.26 1.30
TC (kW) 9.41 9.39 9.38 9.38 9.37 9.36
0
CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36
TC (kW) 11.2 11.2 11.2 11.2 11.2 11.2
6
CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08
TC (kW) 12.1 12.1 12.1 12.1 12.0 12.0
10
CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048605
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ100D 30 (0.11)
FCQ100B 28 (0.16)
FBQ100 27 (0.20)
FHQ100 24 (0.14)
FAQ100 23 (0.10)
FUQ100 29 (0.07)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
(m3/min)
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ35Bx3 14x3 (0.16x3)
FFQ35x3 10x3 (0.25x3)
FBQ35x3 11.5x3 (0.15x3)
FHQ35x3 13x3 (0.2x3)
FCQ35Bx3 2.78 3.31
FFQ35x3 2.79 3.21
FBQ35x3 3.01 3.16
FHQ35x3 3.32 3.79
Twin
Model AFR (BF)
FCQ50Bx2 15x2 (0.16x2)
FFQ50x2 12x2 (0.16x2)
FBQ50x2 14x2 (0.15x2)
FHQ50x2 13x2 (0.1x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ100D 2.44 2.56
FCQ100B 2.64 3.14
FBQ100 2.86 3.00
FHQ100 3.15 3.60
Triple
FAQ100 2.78 3.39
FUQ100 3.12 3.28
Twin
Model Cooling Heating
22
FCQ50Bx2 2.78 3.31
FFQ50x2 2.79 3.21
FBQ50x2 3.01 3.16
FHQ50x2 3.32 3.79
• Split Sky Air • Outdoor Units
Model Cooling Heating
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ125B8V3B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Heating
Capacity range
Heating capacity
Heating capacity
Indoor EDB
TC (kW) 8.83 8.82 8.81 8.81 8.80 8.79
(°C) 16.O 18.O 20.0 21.O 22.O 24.0
Rated point
−15
CPI (-) 1.05 1.10 1.14 1.16 1.18 1.22
TC (kW) 9.76 9.74 9.73 9.73 9.72 9.71
−10
230V [50Hz]
CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29
TC (kW) 10.7 10.7 10.7 10.6 10.6 10.6
−5
Outdoor temp. (°CWB) CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35
TC (kW) 11.6 11.6 11.6 11.6 11.6 11.5
0
CPI (-) 1.22 1.27 1.32 1.34 1.37 1.42
TC (kW) 14.0 14.0 14.0 14.0 14.0 14.0
6
CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08
TC (kW) 15.1 15.1 15.1 15.1 15.1 15.0
10
CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13
3D048604A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ125D 30 (0.13)
FCQ125B 31 (0.07)
FBQ125 35 (0.14)
FHQ125 30 (0.13)
Model AFR (BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125 32 (0.07)
FDQ125 45 (0.25)
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Twin
Model AFR (BF)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ125D 3.54 3.59
FCQ125B 3.88 4.36
FBQ125 3.98 3.99
Triple
FHQ125 4.45 4.50
FUQ125 4.05 4.36
FDQ125 4.15 3.69
Model Cooling Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
Double twin
Twin
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
• Split Sky Air • Outdoor Units
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
23
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ125B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Heating
Capacity range
Heating capacity
Heating capacity
Indoor EDB
TC (kW) 8.83 8.82 8.81 8.81 8.80 8.79
(°C) 16.O 18.O 20.0 21.O 22.O 24.0
Rated point
−15
CPI (-) 1.05 1.10 1.14 1.16 1.18 1.22
TC (kW) 9.76 9.74 9.73 9.73 9.72 9.71
−10
400V [50Hz]
CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29
TC (kW) 10.7 10.7 10.7 10.6 10.6 10.6
−5
Outdoor temp. (°CWB) CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35
TC (kW) 11.6 11.6 11.6 11.6 11.6 11.5
0
CPI (-) 1.22 1.27 1.32 1.34 1.37 1.42
TC (kW) 14.0 14.0 14.0 14.0 14.0 14.0
6
CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08
TC (kW) 15.1 15.1 15.1 15.1 15.1 15.0
10
CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13
3D048606A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
Model AFR (BF)
FCQ125D 30 (0.13)
FCQ125B 31 (0.07)
FBQ125 35 (0.14)
FHQ125 30 (0.13)
Model AFR (BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 18x2 15x2 19x2 17x2 (0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125 32 (0.07)
FDQ125 45 (0.25)
CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Twin
Model AFR (BF)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ125D 3.54 3.59
FCQ125B 3.88 4.36
FBQ125 3.98 3.99
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
FHQ125 4.45 4.50
FUQ125 4.05 4.36
FDQ125 4.15 3.69
Model Cooling Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
Double twin
Twin
24
AFR: BF: EWB: EDB: TC: SHC: PI:
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
• Split Sky Air • Outdoor Units
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.08 4.13 4.19 4.45 4.59 4.26 4.20 4.74
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ140B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Heating
Rated point
Capacity range
Heating capacity
Heating capacity
Indoor EDB
TC (kW) 9.82 9.80 9.79 9.79 9.78 9.77
(°C) 16.O 18.O 20.0 21.O 22.O 24.0
−15
CPI (-) 1.05 1.10 1.14 1.16 1.18 1.22
TC (kW) 9.80 10.8 10.8 10.8 10.8 10.8
−10
400V [50Hz]
CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29
TC (kW) 11.9 11.8 11.8 11.8 11.8 11.8
−5
Outdoor temp. (°CWB) CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35
TC (kW) 12.9 12.9 12.9 12.8 12.8 12.8
0
CPI (-) 1.22 1.27 1.32 1.34 1.37 1.42
TC (kW) 16.0 16.0 16.0 16.0 16.0 16.0
6
CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08
TC (kW) 17.3 17.2 17.2 17.2 17.2 17.2
10
CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D048607
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. Pair
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
FCQ140D 30 (0.07)
Model AFR (BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 18x2 19x2 17x2 19x2 19x2 (0.1x2) (0.11x2) (0.1x2) (0.07x2) (0.08x2)
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Triple
Model AFR (BF)
Model AFR (BF)
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 15x3 12x3 14x3 13x3 (0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Twin
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 14x4 10x4 11.5x4 13x4 (0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
Model Cooling Heating
FCQ140D 4.65 4.52
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69
Double twin
Twin
Model Cooling Heating
Model AFR (BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2 4.81 4.95 4.99 4.99 4.92 5.52 5.06 5.69 5.05 5.22
• Split Sky Air • Outdoor Units
Model Cooling Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4 4.81 4.86 4.95 4.99 5.52 5.11 5.06 5.69
25
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ200B7W1B (Pair / Twin / Triple / Double twin)
Coefficient of power input. (-)
Heating
8.5
23
23.0 25
30
Heating capacity (kW) Heating capacity
Indoor TC (kW) 14.5 14.4 14.3 14.2 14.1
°CDB 16 18 20 22 24
400V [50Hz]
-15
CPI (-) 1.17 1.19 1.21 1.23 1.25
TC (kW) 17.3 17.2 17.1 17.0 16.8
-10
CPI (-) 1.22 1.25 1.27 1.29 1.31
TC (kW) 16.9 16.8 16.7 16.6 16.4
-5
Outdoor temperature (°CWB) CPI (-) 1.21 1.23 1.25 1.28 1.30
TC (kW) 18.1 18.0 17.9 17.8 17.6
0
CPI (-) 1.24 1.26 1.28 1.31 1.33
TC (kW) 23.3 23.2 23.0 22.8 22.7
6
CPI (-) 0.97 0.98 1.00 1.02 1.03
TC (kW) 25.4 25.3 25.1 24.9 24.7
10
CPI (-) 1.01 1.02 1.04 1.06 1.08
3TW26561-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Pair
Model AFR (BF)
Triple
FDQ200 69 0.31
Model AFR (BF)
Twin
Model AFR (BF)
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 28x2 27x2 24x2 29x2 23x2 (0.16x2) (0.2x2) (0.14x2) (0.07x2) (0.1x2)
10. Rated power input of each model is tabulated below.
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 18x3 18x3 15x3 19x3 19x3 17x3 17x3 19x3 19x3 (0.1x3) (0.1x3) (0.11x3) (0.11x3) (0.11x3) (0.2x3) (0.1x3) (0.07x3) (0.08x3)
Double twin
Model AFR (BF)
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 15x4 12x4 14x4 13x4 (0.16x4) (0.16x4) (0.15x4) (0.1x4)
Pair
Model Cooling Heating
Triple
FDQ200 6.43 7.54
Model Cooling Heating
Twin
Model Cooling Heating
26
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2 5.87 6.36 7.00 6.93 6.18 7.16 6.85 8.21 7.48 7.74
• Split Sky Air • Outdoor Units
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3 6.18 6.18 6.20 6.69 6.69 7.37 7.37 7.30 6.50 7.54 7.54 7.32 7.21 7.21 8.65 8.65 7.88 8.14
Double twin
Model Cooling Heating
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4 6.18 6.20 6.69 7.37 7.54 7.32 7.21 8.65
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2 5
RZQ250B7W1B (Pair / Twin / Double twin)
Coefficient of power input. (-)
Heating
9.1
31. 5
27.0
Heating capacity (kW) Heating capacity
Indoor TC (kW) 16.5 16.4 16.2 16.1 15.9
°CDB 16 18 20 22 24
400V [50Hz]
-15
CPI (-) 1.04 1.08 1.12 1.16 1.20
TC (kW) 19.4 19.2 19.0 18.8 18.7
-10
CPI (-) 1.09 1.14 1.18 1.23 1.27
TC (kW) 18.7 18.5 18.4 18.2 18.0
-5
Outdoor temperature (°CWB) CPI (-) 1.09 1.13 1.18 1.22 1.26
TC (kW) 19.9 19.7 19.5 19.3 19.2
0
CPI (-) 1.12 1.17 1.22 1.26 1.31
TC (kW) 27.5 27.2 27.0 26.8 26.5
6
CPI (-) 0.92 0.96 1.00 1.04 1.08
TC (kW) 29.9 29.6 29.3 29.1 28.8
10
CPI (-) 0.98 1.02 1.06 1.10 1.14
3TW26571-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark with * show the max. total capacity at standard conditions. On the figure the mark with show rated capacity and rated coefficient of power input. However, only rated capacity & CPI are guaranteed (maximal values NOT). 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. Rated values are guaranteed. Other values are accurate within an error of 5%. 8. Heating capacity includes capacity drop due to defrost operation. 9. Air flow rate and BF are tabulated below.
AFR: BF: EWB: EDB: TC: SHC: PI: CPI:
Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input.
(m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-)
Caution: TC and SHC are shown by kW
Pair
Model AFR (BF)
Double twin
FDQ250 89 0.34
Model AFR (BF)
Twin
Model AFR (BF)
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 18x4 15x4 19x4 17x4 (0.1x4) (0.11x4) (0.11x4) (0.2x4)
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 31x2 35x2 30x2 32x2 45x2 (0.07x2) (0.14x2) (0.13x2) (0.07x2) (0.25x2)
10. Rated power input of each model is tabulated below. Pair
Model Cooling Heating
Double twin
FDQ250 8.30 8.85
Model Cooling Heating
Twin
Model Cooling Heating
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4 9.08 9.18 9.31 10.41 9.83 9.13 9.00 10.15
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2 8.62 8.84 9.89 9.00 9.22 9.34 8.55 9.64 9.34 7.91
• Split Sky Air • Outdoor Units
27
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing
2 6
RZQ71B7V3B
unit (mm) Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8
Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock hole J34) Control wiring intake (knock hole J27) Drain outlet
3TW25144-1A
unit (mm)
RZQ100-125-140B7V3B Hole for anchor bolt 4-M12
1 2 3 4 5 6 7 8
Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) (2x) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock hole J34) Control wiring intake (knock hole J27) Drain outlet
3TW26071-1
28
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing
2 6 RZQ200B7
4 - 15 x 22.5 mm Oblong holes (foundation bolt hole) (Pitch of foundation bolt holes)
(Pitch of foundation bolt holes)
(Knock out hole)
(Knock out hole)
(for side-routed pipe)
Notes: 1 The dimensions marked with (a) are those with the installation of the provided pipes. 2 Refer to the installation instructions when the pipes are routed through the bottom of the unit.
1 2 3 4 5 6 7 8 9
(for front-routed pipe)
Liquid pipe connection port 9.52 flare connection Gas pipe connection port 22.2 braze connection Grounding terminal inside of switch box Power cord routing hole (side) - J 65 Power cord routing hole (front) - J 45 Power cord routing hole (bottom) - J 60 Power cord routing hole (front) - J 27 Pipe routing hole (front) Pipe routing hole (bottom) - see note 2
(Knock out hole)
(Knock out hole)
RZQ250B7
3TW26564-2
4 - 15 x 22.5 mm Oblong holes (foundation bolt hole) (Pitch of foundation bolt holes)
(Pitch of foundation bolt holes)
(Knock out hole)
(Knock out hole)
(for side-routed pipe)
Notes: 1 The dimensions marked with (a) are those with the installation of the provided pipes. 2 Refer to the installation instructions when the pipes are routed through the bottom of the unit.
1 2 3 4 5 6 7 8 9
(for front-routed pipe)
Liquid pipe connection port 12.7 flare connection Gas pipe connection port 22.2 braze connection Grounding terminal inside of switch box Power cord routing hole (side) - J 65 Power cord routing hole (front) - J 45 Power cord routing hole (bottom) - J 60 Power cord routing hole (front) - J 27 Pipe routing hole (front) Pipe routing hole (bottom) - see note 2
(Knock out hole)
(Knock out hole)
• Split Sky Air • Outdoor Units
3TW26574-2
29
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-2
Dimensional drawings and accessories
2 6 RZQ200-250B7
3D041017C
30
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-3
Centre of gravity
2 6 RZQ200-250B7
Center of foundation bolt hole
Center of foundation bolt hole (oblong hole)
• Split Sky Air • Outdoor Units
Center of foundation bolt hole
Center of foundation bolt hole (oblong hole)
4TW26569-1
31
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2 7
RZQ71B (Pair) Electronic expansion valve
One way valve
One way valve
Filter One way valve
Service port 5/16″
One way valve
Heat exchanger
Capillary tube Solenoid valve Receiver
Strainer Heat exchanger 4-way valve
Muffler Low pressure sensor
Muffler One way valve
Field piping J9.5 C1220T-0
Service port 5/16″
Filter Field piping J15.9 C1220T-0 Compressor
High pressure switch
Indoor unit
Outdoor unit
Heating Cooling
Stop valve (with service port 5/16’ flare)
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
3TW26735-1
RZQ100-125-140B (Pair) One way valve One way valve
One way valve
Heat exchanger
Filter Solenoid valve
One way valve
One way valve
Capillary tube
Electronic expansion valve
Capillary tube Receiver
Strainer
Capillary tube
Service port 5/16″ Heat exchanger 4-way valve
Filter
Low pressure switch
High pressure switch
Muffler
Field piping J9.5 C1220T-0
Service port 5/16″
Filter Field piping J15.9 C1220T-0 Compressor
Indoor unit
Outdoor unit Stop valve (with service port 5/16’ flare)
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
32
• Split Sky Air • Outdoor Units
Heating Cooling
3TW26745-1
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2 7
RZQ200-250B (Pair) Filter
Capillary tube
Receiver
Solenoid valve
Model RZQ200B RZQ250B
Check valve
Check valve
Filter
Fan
Check Check valve valve
Electronic expansion valve Electronic expansion valve
Filter
A 9.52 12.70
Heat exchanger pipe
Solenoid valve
Heat exchanger 4-way valve
High pressure sensor
Pressure regulating valve
Filter
Filter
Filter
Compressor
Field piping J A
Compressor
Filter
Capillary tube
Capillary tube
Indoor heat exchanger
High pressure switch
Oil separator
Oil separator
Filter
High pressure switch
Check valve
Low pressure sensor
Solenoid valve
Field piping J22.20
Fan
Stop valve (with service port on field piping side J 7.9mm flare connection)
Indoor unit
Outdoor unit Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.
3TW26565-1
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ71B (Twin) Electronic expansion valve
One way valve
One way valve
Heat exchanger Filter One way valve
Service port 5/16″
Heat exchanger
Capillary tube
Solenoid valve Field piping Filter
One way valve
Receiver
Field piping Strainer
Indoor unit 4-way valve
Muffler Low pressure sensor
Muffler
Heat exchanger
One way valve Field piping J9.5
Branch duct connection Option
Service port 5/16″
Field piping J15.9 Compressor
Outdoor unit
Field piping Filter
Indoor unit
Field piping
High pressure switch
Stop valve (with service port 5/16’ flare)
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Outdoor Units
Heating Cooling
3TW26735-2
33
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2 7
RZQ100-125-140B (Twin) One way valve One way valve
One way valve
One way valve
One way valve
Heat exchanger Filter Capillary tube
Solenoid valve
Electronic expansion valve
Capillary tube Receiver
Field piping Filter
Heat exchanger
Strainer
Capillary tube
Field piping Service port 5/16″
Indoor unit 4-way valve
Low pressure switch
Filter
High pressure switch
Muffler
Heat exchanger Field piping J9.5
Branch duct connection
Service port 5/16″
C1220T-0
Option
Field piping J15.9 Compressor
C1220T-0
Outdoor unit
Field piping Filter
Heating Cooling
Field piping
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
Stop valve (with service port 5/16’ flare)
Indoor unit
3TW26745-2
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ200-250B (Twin) Filter
Capillary tube
Receiver
Solenoid valve
Filter
Model RZQ200B RZQ250B
Check valve
Check valve
Fan
Check Check valve valve
Electronic expansion valve Electronic expansion valve
Filter
A 9.52 12.70
Heat exchanger pipe
Solenoid valve
Heat exchanger 4-way valve
High pressure sensor
Pressure regulating valve
Filter
Filter
Fan
Capillary tube
Field piping
Filter Capillary tube
Compressor
Field piping
High pressure switch
Oil separator
Filter
High pressure switch
Oil separator
Indoor heat exchanger
Check valve
Compressor
Option Indoor heat exchanger
Low pressure sensor
Field piping J22.20 Stop valve (with service port on field piping side J 7.9mm flare connection)
Filter
Field piping J A Branch pipe
Indoor unit
Solenoid valve
Outdoor unit
Field piping
Fan
Field piping
Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
34
• Split Sky Air • Outdoor Units
3TW26565-2
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2 7 RZQ100-125-140B (Triple) Indoor unit Heat exchanger One way valve One way valve
Stop valve (with service port 5/16’ flare)
Filter
Field piping Filter
Capillary tube
Solenoid valve
Field piping
One way valve
Heat exchanger
One way valve
One way valve
Electronic expansion valve
Capillary tube
Indoor unit
Receiver
Heat exchanger
Strainer Capillary tube
Service port 5/16″ 4-way valve Field piping J9.5 C1220T-0 Field piping Filter
Field piping
Indoor unit Heat exchanger
Filter
Low pressure switch
High pressure switch
Muffler
Field piping J15.9 C1220T-0
Service port 5/16″
Branch duct connection Option
Compressor
Outdoor unit Field piping Filter
Field piping
Heating Cooling
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
3TW26745-3
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ200-250B (Triple) Filter
Model RZQ200B RZQ250B
Filter
Heat exchanger pipe
Solenoid valve Check valve
Check valve
Fan
Check Check valve valve
Electronic expansion valve Electronic expansion valve
Indoor heat exchanger
Filter
A 9.52 12.70
Capillary tube
Receiver
Solenoid valve
Heat exchanger 4-way valve
Field piping
High pressure sensor
Pressure regulating valve
Check valve
Field piping J A Field piping
Fan
Field piping
Branch pipe
Indoor unit
Option Indoor heat exchanger
Compressor Capillary tube
Field piping J22.20 Stop valve (with service port on field piping side J 7.9mm flare connection)
Filter Capillary tube
Filter
High pressure switch
High pressure switch
Low pressure sensor
Compressor
Filter
Indoor heat exchanger
Oil separator
Indoor unit
Filter
Filter
Field piping
Oil separator
Fan
Solenoid valve
Outdoor unit Field piping
Fan
Field piping
Indoor unit
Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Outdoor Units
3TW26565-3
35
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2 7
RZQ100-125-140B (Double twin) Heat exchanger
Indoor unit
One way valve One way valve
One way valve
One way Capillary valve tube
One way valve
Field piping Field piping
Filter Heat exchanger
Indoor unit
Filter Solenoid valve
Field piping J9.5
Service port 5/16″
Field piping Filter
Electronic expansion valve Strainer Capillary tube
Capillary tube Receiver
Field piping J15.9
Heat exchanger
4-way valve
Field piping Heat exchanger
Indoor unit
Field piping J9.5
Branch duct connection
Filter
C1220T-0
Low pressure sensor
High pressure switch
Option Service port 5/16″
Field piping J15.9 Muffler
C1220T-0 Compressor Field piping Filter
Field piping
Heat exchanger
Outdoor unit Heating Cooling
Field piping J9.5 Stop valve (with service port 5/16’ flare)
Field piping J15.9
Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections.
Field piping Field piping
Filter
3TW26755-4
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ200-250B (Double twin) Filter Solenoid valve
Field piping
Filter
Check valve
Check valve
Fan
Check Check valve valve
Electronic expansion valve Electronic expansion valve
Indoor unit Field piping J 9.52
Indoor heat exchanger
Heat exchanger pipe
Solenoid valve
Filter
Field piping
Fan
Model RZQ200B RZQ250B
Capillary tube
A 9.52 12.70
Receiver
Indoor heat exchanger
Heat exchanger Field piping J15.90
4-way valve
Field piping
High pressure sensor
Pressure regulating valve
Field piping J A Compressor
Field piping
Fan
Field piping J22.20
Field piping
Indoor unit
Field piping J 9.52
Indoor heat exchanger
Field piping J15.90
Capillary tube
Capillary tube
Filter
Option
Low pressure sensor Stop valve (with service port on field piping side J 7.9mm flare connection)
Compressor
Filter
High pressure switch
Branch pipe
High pressure switch
Oil separator
Indoor heat exchanger
Oil separator
Indoor unit
Filter
Filter
Check valve
Filter
Field piping
Fan
Solenoid valve
Outdoor unit Field piping
Fan
Field piping
Note: The pipes between the branch and the indoor units should have the same size as the indoor connections.
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
36
• Split Sky Air • Outdoor Units
3TW26565-4A
• Outdoor Units • R410A • RZQ-B
8
Wiring diagram
2 8
RZQ71B8V3B Indoor
: Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector
NOTE 1.
L N
Outdoor
: Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green ON OFF
NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off. El. comp. assy front
A1P A2P BS1 C1-C2-C3 DS1 F1U HAP (A1P) HAP (A2P) H1P (A1P)
Printed circuit board Printed circuit board (INV) Push button switch (forced defrost / pump down) Capacitor Dip switch Fuse (T6, 3A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red)
K1M(A2P) K1R(A1P) K2R(A1P) K2R(A2P) L1R M1C M1F PS Q1DI R1-R2 R1T
Magnetic contactor Magnetic relay (Y1S) Magnetic relay (Y2S) Magnetic relay Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air)
R2T R3T R4T R5T S1PH S1NPL RC TC V1R
Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal receiver circuit Signal transmission circuit Power module
V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F
View A
Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter
2TW26736-1A
Noise filter (with surge absorber)
RZQ100-125B8V3B Indoor
: Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector
NOTE 1.
L N
Outdoor
: Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green
ON OFF
NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off.
A1P A2P BS1 C1-C2-C3 DS1 E1HC F1U F2U F3U HAP (A1P) HAP (A2P) H1P (A1P)
Printed circuit board Printed circuit board (INV) Push button switch (forced defrost / pump down) Capacitor Dip switch Crankcase heater Fuse (T 6,3A/250V) Fuse Fuse (B 5A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red)
K1M(A2P) K1R(A1P) K2R(A1P) K3R(A1P) K4R (A1P) L1R M1C M1F PS Q1DI R1-R2 R1T
El. comp. assy front
Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (E1HC) Magnetic relay (Y2S) Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air)
R2T R3T R4T R5T S1PH S1NPL TC V1R
Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal transmission circuit Power module
• Split Sky Air • Outdoor Units
V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F Z1F
View A
Reactor box
Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter Noise filter Noise filter (with surge absorber)
2TW26746-1
37
• Outdoor Units • R410A • RZQ-B
8
Wiring diagram
2 8 RZQ100-125-140B7W1B Indoor
: Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector
NOTE 1.
L N
Outdoor
: Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green
ON OFF
NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off.
A1P A2P BS1 C1-C2-C3 DS1 F1U (A2P) F2U F3U F4U HAP (A1P) HAP (A2P) H1P (A1P)
Printed circuit board Printed circuit board (INV) Push button switch (forced defrost / pump down) Capacitor Dip switch Fuse (T 6,3A/250V) Fuse (T 6,3A/250V) Fuse (B 10A/250V) Fuse (B 10A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red)
K1M(A2P) K1R(A1P) K2R(A1P) K3R(A1P) K4R, K5R L1R M1C M1F PS Q1DI R1-R2
RZQ200-250B7
Reactor box El. comp. assy front
Magnetic contactor Magnetic relay (Y1S) Magnetic relay (Y2S) Magnetic relay (E1HC) Magnetic relay Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor
Power supply
R1T R2T R3T R4T R5T S1PH S1NPL RC TC V1R
Thermistor (air) Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal receiver circuit Signal transmission circuit Power module
V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F Z1F
View A
Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter
2TW26766-1
Noise filter Noise filter (with surge absorber)
Indoor
400V 3N ∼50Hz
Printed circuit board Main Inverter Fan motor Noise filter current sensor Push button switch Mode, set, return, test, forced defrost C2-C5,C63,C65 Capacitor DS1 Dip switch E1HC, E2HC Crankcase heater B ) (A4P) F1U Fuse (250V, 5A j B ) (A1P) F1U, F2U Fuse (250V, 10Aj F5U Field fuse H1P-H7P Pilot lamp (Pilotlamp service monitor - orange) Prepare test--------Flickering [H2P] Malfunction detection---Light up HAP Pilot lamp (Pilotlamp service monitor - green) K1 Magnetic relay K2S Magnetic relay (M2C) K2 Magnetic contactor (M1C) K2M Magnetic contactor (M2C) K1R-K7R Magnetic relay K1R K2M (A1P) K2R Y1S K3R E1HC (A1P) K4R E2HC (A1P) K5R Y2S K6R Y3S K7R Y4S L1R Reactor M1C, M2C Motor compressor M1F Motor fan PS Power circuit Q1DI Earth leakage breaker (max. 30mA) Q1RP Phase reversal detect circuit R10 Resistor (current sensor) R50, R59 Resistor R95 Resistor (current limiting) R1T, R32T Thermistor R1T Air (A1P) R32T M2C Discharge R1T Fin type (A2P) R4T Coil-deicer R2T Suction R5T Coil-outlet R31T M1C Discharge S1NPH Pressure sensor (high)
(NOTE 4)
A1P-A5P A1P A2P A3P A4P A5P BS1-BS5
38
ON XXX = Color of PCB connector YYY = (Marked) color of wire connector ZZZ = Color of wire
OFF
(NOTE 4)
(NOTE 4)
Notes: 1. This wiring diagram only applies to the outdoor unit : Field wiring 2. 3. : Terminal strip : Connector : Terminal : Protective earth (screw) 4. For use of the option adaptor, how to use BS1 ∼ BS5 and DS1 switch and connection to X1M(A1P) or X3M refer to the installation manual. 5. Do not operate the unit by short-circuiting protection device S1PH, S2PH 6. BLK: Black / WHT: White / RED: Red / BLU: Blue GRY: Grey / BRN: brown / GRN: Green / YLW: Yellow / PNK: Pink
Detail of M1C, M2C
S1NPL S1PH, S2PH T1A T1R V1CP, V2CP V1R, V2R V1R X1M X2M X3M X4M
Pressure sensor (low) Pressure switch (high) current sensor Transformer(230V/20V) Safety devices input Power module (A2P) Power module (A3P) Terminal strip (Control) (A1P) Terminal (Power supply indoor) Terminal (Control) Terminal strip (Power supply)
Y1E Electronic expansion valve (Main) Y2E Electronic expansion valve (Subcool) Y1S-Y4S Solenoid valve Y1S 4-way valve Y2S Hot gas Y3S Receiver gas purge Y4S Liquid pipe Z1C, Z5C Noise filter (ferrite core) Z1F Noise filter (with surge absorber) Option connectors X36A Connector adaptor power supply
• Split Sky Air • Outdoor Units
Front layer
Rear layer Position in switch box
2TW26566-1
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-1
Sound pressure spectrum
2 RZQ71B8V3B - Cooling Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
3TW26737-1
3TW26737-2
Octave band center frequency (Hz)
NOTES 1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
1 2 3 4
Measuring location (discharge side)
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
Measuring location (discharge side)
RZQ100B8V3B - Heating RZQ100B7W1B Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
3TW26747-1
Octave band center frequency (Hz)
3TW26747-2
NOTES
4
Octave band center frequency (Hz)
NOTES
RZQ100B8V3B - Cooling RZQ100B7W1B
1 2 3
9
RZQ71B8V3B - Heating
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
1 2 3 Measuring location (discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side)
39
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-1
Sound pressure spectrum
2 9
RZQ125B8V3B - Heating RZQ125B7W1B Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
RZQ125B8V3B - Cooling RZQ125B7W1B
3TW26757-1
3TW26757-2
Octave band center frequency (Hz)
NOTES 1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
1 2 3 Measuring location (discharge side)
4
3TW26787-2
Octave band center frequency (Hz)
NOTES
40
Measuring location (discharge side)
Sound pressure level [dB(A)]
3TW26787-1
4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
RZQ140B8V3B - Heating
Sound pressure level [dB(A)]
RZQ140B8V3B - Cooling
1 2 3
Octave band center frequency (Hz)
NOTES
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
1 2 3 Measuring location (discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
Measuring location (discharge side)
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-1
Sound pressure spectrum
2 9 Sound pressure level [dB(A)]
RZQ250B7
Sound pressure level [dB(A)]
RZQ200B7
3TW26567-1
3TW26577-1
Octave band center frequency (Hz)
NOTES 1 2 3 4
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil
Microphone
1 2
Switchbox
Location of microphone
• Split Sky Air • Outdoor Units
3 4
Data is valid at free field condition (measured in a semi-anachoic room) dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.
Coil
Microphone
Switchbox
Location of microphone
41
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-2
Sound power spectrum
2 9
RZQ100B8V3B - Cooling RZQ100B7W1B Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
RZQ71B7V3B - Cooling
3TW26737-3
3TW26747-3
Octave band center frequency (Hz)
NOTES 1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
1 2 3 4
RZQ125B8V3B - Cooling RZQ125B7W1B Sound pressure level [dB(A)]
3TW26787-3
Octave band center frequency (Hz)
NOTES
42
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
RZQ140B8V3B - Cooling
Sound pressure level [dB(A)]
3TW26757-3
1 2 3 4
Octave band center frequency (Hz)
NOTES
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
• Split Sky Air • Outdoor Units
1 2 3 4
Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-2
Sound power spectrum
2 Sound power level (dB)
3TW26567-2
3TW26577-2
Octave band center frequency (Hz)
NOTES 1 2 3
9
RZQ250B7
Sound power level (dB)
RZQ200B7
Octave band center frequency (Hz)
NOTES
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2. Measured according to ISO 3744
• Split Sky Air • Outdoor Units
1 2 3
dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2. Measured according to ISO 3744
43
Liquid side junction Suction gas side junction
Liquid side header
Discharge gas side header
10
44 1TW25799-1E
Liquid side junction
10
Closed pipes
Discharge gas side junction
• Outdoor Units • R410A • RZQ-B
Installation
10 - 1 Refnet pipe systems
2
• Split Sky Air • Outdoor Units Reducers - Expanders
• Outdoor Units • R410A • RZQ-B
10
Installation
10 - 2 Service space
2 10
RZQ71∼140B A. Non stacked installation
Legend Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present
In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models.
B. Stacked installation 2. Obstacles exist in front of the air inlet
1. Obstacles exist in front of the outlet side
Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation 1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral connection per row
Relation of dimensions of H, A, and L are shown in the table below. L≤H H