SIPART DR Ergänzungsblatt / Supplement sheet “Beschaltung und Einstellung der Optionskarten zu SIPART DR Reglern” - 6DR2800-8P Pt100 Eingang (RTD) - 6DR2800-8T Thermoelement Eingang (TC)
“Wiring and setting of option cards for SIPART DR controllers” - 6DR2800-8P Pt100 Input (RTD) - 6DR2800-8T Thermocouple input (TC)
The options cards 6DR2800-8P and 6DR2800-8T have been replaced with the controllers SIPART DR19 and SIPART DR21 as well as the modification of the controllers SIPART DR2210 and SIPART DR2410 by the UNI module 6DR2800-8V. Therefore the wiring of these options cards and the necessary setting on the cards have not been taken into account in the manuals of these devices. Regardless of this, these options can still be used in the SIPART DR19 til SIPART DR24 controllers. Please note: -
The measuring range for these inputs is set by plug-in jumpers and adjusting potentiometers on the options!
-
The tables for setting the jumpers contain data in ohms or mV. Basic value tables for RTD and TC are therefore absolutely essential.
-
The menus CAE1 and CAE2 or CAE4 and CAE5 are not active for these options.
Possible slots and necessary basic settings: Basic setting - Structure switch DR19/DR21/DR22) - hdEF (DR24
Input
Slot
SIPART DR19 6DR190x-4/-5
AI2 AI3
Slot 2 Slot 1
S8 = 0/1 S9 = 0/1
SIPART DR21 6DR210x-4/-5
AI3 AI4
Slot 1 Slot 2
S6 = 0/1 S7 = 0/1
SIPART DR22 6DR2210-4/-5
AI4 AI5
Slot 2 Slot 3
S8 = 0/1 S9 = 0/1
SIPART DR24 6DR2410-4/-5
AI4 AI5
Slot 2 Slot 3
hdEF: AI4 = 0 MA hdEF: AI5 = 0 MA
Ergänzungsblatt/Supplement sheet A5E00097041-01
7 von/of 12
6DR2800-8P •
Pt100 Input
Wiring
Figure 1 Wiring of Pt100 module 6DR2800-8P •
Jumper settings
Figure 2 Jumper settings for Pt100 module 6DR2800-8P 1. Set Pt100 switching mode to 2L, 3L or 4L. 2. Get RtA and RtE from Pt100 table (DIN/IEC 751 Oct 85). 3. Calculate R0 according to wiring configuration (see above). 4. Set R0 jumpers according to Table 1. 5. Calculate ∆R = RtE-RtA. 6. Set jumpers for ∆R according to Table 1. Factory setting: 4L
BC, EF
R0
1 GH
2 GH
3 GH
4 GH
5 GH
∆R
1 KL
2 LM
3 LM
4 LM
5 LM
Ergänzungsblatt/Supplement sheet A5E00097041-01
6 GH
7 GH
R0 = 80.31 Ω RtA = -50 °C ∆R = 309.95 Ω RtE = -850 °C
8 von/of 12
•
Calibration 1. Simulate RtA (with resistances in the case of 2L) using "0!display, or set analog output (depending on the configuration) to start-of-scale value. 2. Simulate RtE (with resistances in the case of 2L) using value.
display, or set analog output to full-scale
A single character means that only one jumper pole should be attached.
Table 1 Jumper settings for start-of-scale value R0 and measuring range ∆R of Pt100 module
Ergänzungsblatt/Supplement sheet A5E00097041-01
9 von/of 12
6DR2800-8T •
Thermocouple input and mV transmitter
Wiring
Figure 3 Wiring of thermocouple module All common types of thermocouple and mV sources can be connected to this module. The low drift input amplifier possesses a common mode rejection of up to 10 V. This means that if two SIPART are fittet with thermocouple inputs, and the controllers are connected to one another via the reference line, unisolated (surface welded, undefined earth) thermocouples can also be connected. If this is not the case, we recommend that in order to prevent undefined common mode voltages, pin 3 be connected to reference line M on the standard controller. Electrical isolation is then achieved via the power supply. Trimming with an mV transmitter can also be performed using this circuit. •
Jumper settings
Figure 4 Jumper settings for thermocouples module 6DR2800-8T Factory setting:
Ergänzungsblatt/Supplement sheet A5E00097041-01
10 von/of 12
1. Set jumpers for internal cold junction according to type of thermocouple (DIN 43710 or IEC 584). With types B and E, mV transmitters and an external cold junction: attach one jumper pole to E. 2. Determine response in event of thermocouple breakage „+ „ indicates that x G 100 %
: „ - I I “ indicates that x G 0 %;
3. Refer to thermocouple table (DIN 43710 or DIN IEC 584) for values of UtA and UtE. 4. Calculate U0 according to location of cold junction:
5. Set appropriate jumpers to value of U0, 0,5 + 1 + 2 + 4 + 8 + 16 + 32 mV. If a voltage is not required, only attach one jumper pole. Set jumpers for U0 polarity: U0 9 0, jumper 0 = P; U0 < 0, jumper 0 = N 6. Calculate ∆U = UtE – UtA. 7. Set jumpers for ∆U according to table 2. 8. If actual physical values are to be displayed, parameterise the lineariser in the controller. •
Calibration 1. Set jumper to TEST position. 2. Supply U0 from mV transmitter using "0! display, or set analog output (depending on the configuration) to start-of-scale value or 4 mA. 3. Supply U0 and ∆U from mV transmitter using 20 mA
•
display, or set analog output to full-scale value or
Operation Set jumper to NORM position for thermocouples using an internal cold junction Leave jumper on TEST for thermocouples using external compensation and mV transmitters.
Ergänzungsblatt/Supplement sheet A5E00097041-01
11 von/of 12
A single character means that only one jumper pole should be attached.
Table 2 Jumper settings for measuring span ∆U of thermocouples modules
1.5.4.11 S1 = 10: Fixed setpoint controller with 1 setpoint (control system coupling). 84 ..... signal or as a three-position step controller for controlling electric motor drives .... The microcontroller used has integrated AD- and DA converters and
The correction computer is used to calculate the flow of gases from the active ...... prox. 5 s). Release tA5. +. --. Online parameters, see chapter 3.3.1, page 136.
Mar 2, 2015 - Contents of status register and process variables. 22 ..... via the SES. Bit. ST2. 7. 0. Process operation level is quit. 6. 0. --. 5. 0. MEM Err. 4.
power still applied. When opening covers or ... Overview. Description. This manual provides instructions for installation of the Maxum edition ..... If a forklift or dolly is used, make sure the Maxum II is strapped to it se- curely. Add padding ..
The HydroRanger 200 is a single-point, six relay device that offers both level and volume ... è Wall Mount: suitable for outdoors (Type / Nema 4x, IP65 Enclosure).
24, ost SA locking cevice. 27, Air evoCuction CDrtoiner ... Note the side clistance oetween or evacuation CDntainer and probe, ca, 500mm. Datur 2, 2,96. Bedro ...
be construed as a commitment, representation, warranty, or guarantee of any method, ...... Once your PC is set up, as described in Configuring Your PC, you are.
Description. In the methanator CO and CO2 are ... Methanator Operation. Ni. CO + 3 H2. â. CH4 + H2O. Ni ... Operational Note. File: Filament.DOC. Removal ...
This device/system may only be set up and operated in conjunction with this manual. ... Under Weighing Technology, select Continuous Weighing Systems and then go to the manual ...... The distance calculation is dependent upon the ambient sound. .....
Neopren. Rubber bushing. EPDM 50. Packaging. Bio-degradable cardboard. 3K. âÎ. 2K. âÎ ... However, the data in this manual are reviewed regularly and any.
92+0.8 mm x 45+0.6 mm. ⢠Upright version. 45+0.6 ... Electric connection. Tab connector 6.3 x 0.8 or ..... 62.5 mm at BV 3340 of Federal. Navy (Order No. N98).
Heater LED - ON when the PIC is requesting the heater to be turned ON and the ... Over Temperature Shutdown active, the corresponding heater output was ...
values of several measuring chan- nels, of status informations as well as diagnosis signals for preventive maintenance.The limited dynamics of 4-20 mA signals ...
GENERAL. This instruction manual contains information essential to successful CompuScale III operation. ... PROGRAMMING CHART, provides a space to record programmed parameter values for future reference. ...... POS B L/C (A + B) (V).
longest cycletime in the Maxum's method table for an application, even ..... 3051 162. 1. 3. SEL. 0. 1. 38. B. 3052 162. 2. 3. SEL. 0. 1. 39. B. 3101 162. 1. 3. CUR.
high degree of isolation from mains supply as the MASS 6000 (Class 2 transformer or Class 1). Electrical connection. Electrical connection for. Ex application. 81.
specifically designed for process gas chromatography. It uses pressure-on-diaphragm activation with no other moving parts. The valve can inject vapor samples ...
Red LED. ON no communication between bus and module / Bus error ..... Positive values indicate that the decimal place shifts to the left, and negative values ...
Feb 10, 2000 - edit database tables, configure hardware, application IO, and other related ...... (suitable for MS Excel) for ADH; type 3 indicates a TCP printer ...
Floating double-throw contacts, maximum contact load rating. 1 A at 30 V. ... NEMA 3, IP54 (outdoor with weather protection) ... No instrument air for airless oven.
Device Response after Switching on the Power Supply. 22 . . . . . . . 7.3 ... the signal converter can be found in the handbooks for the SIPART DR22 and. SIPART ...