G 24 q-3. Type N-EVG ... 158 CG-S. 136 CG-S. 126 CG-S. Lamp load. 58 W. 36 W ... 0.35 kg. Enclosure colour white. Type of mounting. For installation inside ...
Electronic Ballasts to be Built into Luminaires of Insulation class I and II N-EVG 126 CG-S, N-EVG 136 CG-S and N-EVG 158 CG-S Technical data
30% - 100 % adjustable in 10% steps Flame retardant plastic 0.35 kg white For installation inside luminaires 28.5 x 270 x 30 Loop terminals 2.5 mm2 230 V 50/60 Hz, 220 V DC +25/-20 % see table -20°C to + 50°C 1) see table IP 20 II
2
Ordering details Type/Marking
Luminous flux during battery operation
Order No.
N-EVG 136 CG-S N-EVG 158 CG-S N-EVG 126 CG-S
30 - 100% adjustable in 10% steps
4 0071 348 239 4 0071 348 238 on request
Power consumption N-EVG CG-S for mains and battery operation International term
T 26
Lamp cap
TC-TEL
G 13
Type N-EVG ...
TC-DEL
GX 24 q-3
G 24 q-3
158 CG-S
136 CG-S
Lamp load
58 W
36 W
26 W
26 W
Current consumption in A at battery operation in switch position (Luminous flux ⌽E/⌽N in %) 0 (100%) 1 ( 90%) 2 ( 80%) 3 ( 70%) 4 ( 60%) 5 ( 50%) 6 ( 40%) 7 ( 30%)
0.264 0.241 0.228 0.198 0.164 0.154 0.132 0.100
0.176 0.159 0.141 0.127 0.100 0.092 0.085 0.080
0.134 0.124 0.117 0.103 0.097 0.089 0.083 0.078
0.134 0.124 0.117 0.103 0.097 0.089 0.083 0.078
62.7
38.7
34.2
34.2
10
10
10
10
Power consumption in VA Inrush current [A/ms]
126 CG-S
The drawn battery current depends on the luminous flux ratio (30 % ... 100 %) and has to be used for calculating the total current required for a central battery system. Dimensions (mm) 270 260
4.4 30
28.5
6.3
21.5
N-EVG 136 CG-S
N-EVG ... CG-S Luminous flux ⌽E at the end of rated operating time Enclosure material Weight Enclosure colour Type of mounting Dimensions (mm) (H x L x B) Connection terminals Voltage ranges Max. rated load Permissible temperature range Lamp Degree of protection Insulation class 1) max. Tc = 70°C