Simple automation control modules
Automation control modules
Simplicity itself ! A concentrated solution Ideal for your small automation control applications, millenium can manage : – Time delays – Counters, relays – Clock programming – Analogue control – Threshold monitoring – Console and associated logic processing
Integrated operator console Edit your messages in plain text, define your setpoints.
A range with several versions : 6 - 10 and 20 inputs/outputs, in 24 VDC or 100-240 VAC-50-60 Hz. Powerful relay outputs : 8 to 10 A depending on the model. Up to 8 inputs on 24 VDC units used as digital OR analogue (0-10 VDC, 8 bits). Special control functions are available for domestic or simple industrial applications.
When setting up your project, choose : "Simplicity" : Enter parameters directly using the buttons and the screen on the "front" panel. "Performance" : Program your PC using the Crouzet Software CLS software workshop for design, simulation, testing and direct transfer.
A Year 2000 compatible realtime calendar clock as standard on the whole range, with 350 programmable ON/OFF cycles! When setting the date, the day of the week is calibrated automatically, plus automatic changeover between winter/summer time!
➾ replace expensive programming clocks.
Temperature management
Lighting control with clock
Mounting in cabinets or consumer units Power supply
Irrigation, pump control
Inputs
Cycle and counter management
Interface for programming via the PC Interface for memory cartridges
The millenium range is suitable for both domestic electrical applications and industrial requirements such as controlling small machines.
Outputs 8 buttons and LCD screen for programming on the unit
CLS software makes it easy to define and check your wiring diagrams millenium offers you programs with 64
Toolbox selector – Inputs, outputs, functions
function blocks, stored on EEPROM. Moreover, an optional removable EEPROM cartridge is available for remote transfer of modifications, for example. Data is stored in self-protected RAM (no battery required) for 20 days in the event of mains failure.
Toolbox – Inputs
Performance
Simplicity Programmed directly on the unit. An LCD screen (4 lines of 10 characters) with display function (messages and values) and operator console. Program, edit, modify - all using the 8 buttons on the front. System builders and software integrators alike can easily create any type of automation system.
– Direct programming of boolean functions – Online help specifies whether or not millenium is connected during simulation – Program password-protected with 3 security levels. – Buttons on front can be assigned to programmed functions. – Complete program listing
Use the mouse for fingertip control of your project
– Select the icon for the function, input or output. – Place it on the screen. – Define the setpoints. – Draw the connections. – Test your wiring diagram. – Supervise the installation from the "SKETCH system" screen. – Transfer your program to
millenium (EEPROM).
– Print your program listing.
Your function toolbox Function blocks
Description
AND (up to 4 digital inputs)
AND. Output ON when all inputs present are ON.
OR (up to 4 digital inputs)
OR. Output ON when at least one input present is ON.
XOR (2 digital inputs)
OR. EXCLUSIVE. Output ON when only one input is ON.
NOT (1 digital input)
NOT. Reverses the signal. Output ON if input OFF, and OFF if input ON.
NAND (up to 4 digital inputs)
NOT AND. Output ON when at least one input present is OFF.
NOR (up to 4 digital inputs)
NOT OR. Output ON when all inputs present are OFF.
BOOLEAN (up to 4 digital inputs)
Can be used to create logic equations between the connected variables. Option of testing the equation.
SET/RESET
Bistable memory. Priority assigned to either SET or RESET.
DELAY
Delays a (digital) signal from a rising edge, falling edge, or both at once. Option of using RESET (Functions A.C. Ac).
ONE SHOT
Sends an adjustable pulse signal. Conditions for clearing the digital output : end of time delay or RESET (function B).
PULSE
Sends a pulse from a rising edge, a falling edge, or both at once.
ALT
Alternates the digital output signal on each rising edge of the digital input. Option of using RESET.
COUNTER
Counter incremented on each rising edge of the digital input. Option of using RESET. Preset value can be assigned by a digital value.
UP/DW COUNTER
Counter incremented (digital input), decremented (digital input) on each rising edge. Preset value can be assigned by a digital value (parameter) or by an analogue input. 1 digital input for accessing the preset value directly. Option of using RESET.
FLICKER
Sends a pulse train (ON, OFF) according to several different modes: counting ON/OFF cycles (preselection), counting the time (preselection), continuous (advanced Di function).
COMPARE
Compares two analogue or digital values. Activates the digital output if the equation is verified.
TIMES SWITCH
Program clock. Uses the module internal time and date to activate or deactivate the digital output. 24-hour, 7-day and calendar time bases. Year 2000 compliant. Summer time function. Up to 350 ON/OFF cycles per program.
GAIN
Can be used to convert an analogue value by changing the scale and offset. Parameters : gain numerator, gain denominator, offset, lower and upper conversion limits.
SCHMITT
Defines an activation zone with hysteresis (On values, off values) for the digital output.
ZONE COMPARE
Defines a range (analogue or digital values) in which activation (or deactivation depending on which option is checked) of the digital output depends on the value being used.
DISPLAY
Display of digital and analogue data, character strings, date, time, messages for the man-machine interface.
HOUR METER
Counts the time (preselected in hours or minutes) during each activation of the digital input. Memorisation of elapsed time. Option of using RESET.
Characteristics Power Maximum consumption micro-cut 3 4 3 8 6
VA VA W VA W
10 ms 10 ms 5 ms 10 ms 5 ms
Maximum inrush current
Relay outputs
Power supply
Part numbers
0.7 A - 1.5 A 0.7 A - 1.5 A 7A 0.7 A - 1.5 A 7A
4 in - 2 out 6 in - 4 out 6 in - 4 out 12 in - 8 out 12 in - 8 out
100-240 VAC + 10 % – 15 % 50/60 Hz 100-240 VAC + 10 % – 15 % 50/60 Hz 24 VDC + 20 % – 15 % 100-240 VAC + 10 % – 15 % 50/60 Hz 24 VDC + 20 % – 15 %
89 89 89 89 89
750 750 750 750 750
001 002 003 004 005
89 89 89 89
750 750 750 750
100 101 102 103
Accessories Millenium programming software - CD-ROM PC-module interface, length 3 m EEPROM memory module Faceplate for mounting on front panel AC INPUT CHARACTERISTICS Input voltage Input impedance Pull-in voltage at logic state 1 Drop-out voltage at logic state 0 Response time Status indicator
RELAY OUTPUT CHARACTERISTICS
100-240 VAC + 10 %-15 %, 50-60 Hz > or = 800 kOhms
Max. breaking voltage Breaking voltage Service life
≥ 80 V ≤ 40 V 50 ms YES on LCD screen
Minimum load Response time Status indicator
250 VAC - 30 VDC 8 A (10 A for 110 VAC outputs) 100,000 operations at 8 A / 240 VAC or 24 VDC 30,000 operations at 10 A / 110 VAC 50 mW (10 mA at 5 VDC) 10 ms YES on LCD screen
DC INPUT CHARACTERISTICS Input voltage Input current Pull-in voltage at logic state 1 Drop-out voltage at logic state 0 Response time Status indicator Sensor type
24 VDC + 20 %-15 % 5 mA
ELECTRICAL - ENVIRONMENTAL SPECIFICATIONS Insulation
≥ 18 V
Safety class Earthing Protection Certifications Conformity with
≤4V 15 ms YES on LCD screen NPN or PNP 2 or 3-wire
ANALOGUE INPUT CHARACTERISTICS MAS 10 MAS 20 Measurement range Resolution Conversion time Input voltage Input impedance Precision Temp. dependent derating
6 inputs from l01 to l06 8 inputs from l01 to l08 0-255 8 bits - 10 000 / 256 mV 10 ms 0-10 VDC 150 kOhms min. +/- 5 % (0.5 VDC) +/- 3 LSB
Programming method Program size Program memory Removable memory Data memory Operating temperature Storage temperature Humidity Dimensions (l x h x d)
Mounting on front panel with faceplate
90
Dimensions
6/10 E/S: 71,2 20 E/S: 124,6
7 MOhms at 500 VDC between connectors according to EN 60730-1 II None IP 20 CE, UL/cUL UL 508 EN 60730-1 EN 61010-1 EN 50081-1 EN 50082-1 EN 50082-2 Function blocks 64 function blocks or 1,500 bytes EEPROM built-in as standard YES - optional EEPROM cartridge Backed up for 20 days 0-55 °C - 30 to + 70 °C 35 - 85 % relative humidity without condensation 6-10 : 71.2 x 90 x 55 mm 20 : 124.6 x 90 x 55 mm
55