S Time Actuator to Manage Work Cycles - Frigoristes.fr

toggle. Through the “dxc” parameters it is possible to set a constant delay ... in “free running” mode with switch times ..... performances related to EMC electro-.
473KB taille 135 téléchargements 225 vues
EWTS 330/S Time Actuator to Manage Work Cycles Technical Data Sheet EWTS 330/S

M1 version: time actuator with digital inputs and alarm relays • M2 version: outputs manual commands or from dgital inputs EWTS 330/S includes an internal clock to control timings. An internal back-up device permits time count for about one hour in case of power failure. A range of alphanumeric parameters allows configuring EWTS 330/S according to requirements. EWTS 330/S and EWTS SLAVE are supplied in the 70x85 mm format (4 modules) for Din rail (Omega 3) or wall mount. •

OUTPUT CONTROL GENERAL DESCRIPTION EWTS 330/S is a microprocessor-based digital instrument designed to operate as time actuator to manage time cycles. This instrument controls three relays that are included in the EWTS SLAVE Din module, that also powers the instrument to which it is connected through a special MULTIPLE WIRE cable. This cable is provided with disconnectable polarised telephone connectors on both ends and conveys all the input and control signals to the module relays, and the power supply voltage to the EWTS 330/S master. EWTS 330/S includes a 4 digit led display and four configuration keys for the manual operation of users, a 12 Vc /20 mA voltage output to drive a fourth relay for the management of operation alarms (e.g. recovery after a power failure), and 3 inputs for the users remote control. It is also provided with an RS-485 port (doubled to ease cabling) for the connection to the TELEVIS system. The Instrument is available in 2 different versions suitable for different applications:

The control of the outputs are 4: Automatic, Manual, Output Programming, Remote. -Automatic: the instrument manages a range of 40 events that can be configured through the keyboard or the TELEVIS SYSTEM. An event is identified by settings in the “Exx” type user menus, which are accessible from parameters programming. The structure of each event menu is described in Tab.2. The relay status will be updated in correspondence with the operation time of each set event. Manual operation of outputs has a higher priority on event operation. This is in force until the following event. Weekly events have higher priority on daily events according to the order in Tab.2. In this way an event programmed for all weekdays can be cancelled by a different weekly event (for instance on Mondays). Not vice-versa. Parameter “CUSt”, in detail, allows to set a custom sequence of days of the week for which it will be executed the events related to the Custom period. Range of

this parameter is 0 (no days) to 127 (all days). Intermediate values show all the list of possible days. To calculate the value proceeed as follows: Calculate the decimal number corresponding to the binary number LMMGVSD where you set to 1 the days of the week taht you consider, and at 0 the others (See Example in Tab. 3) On every event, each output can be set to five different modes: unchanged, active, inactive, pulse, free-running and toggle. Through the “dxc” parameters it is possible to set a constant delay time for each output that on each event allows to “freeze” the output status and delay its status change. The operation times for each output in the bistable and pulse cycles can be set through parameters “tx1” and “tx2”. Parameter “PrEn” can be used to disable event management while keeping the program stored. In this case outputs can only be operated manually or through digital input. -Manual: by operating on keys Out 1, Out 2 and Out 3 the three connected users can be manually enabled or disabled. -Output programming: the logical status of the outputs can be modified through the keyboard. The setting modes allow to generate an asynchronous event from the keyboard, which is similar to events automatically actuated by the chronometer (see Automatic Mode). -Remote: digital inputs can be configured to remote activate the connected users through special contacts.

Tab. 1 Summary of Mode and Functions Automatic

Manual

Output Programming

Remote

Unchanged X Active Inactive Pulse FreeRunning Toggle Stand-by

Tab.2

X

X X X X

X X

X

X X

X X

COMMANDS ON FRONT PANEL

User menù Structure

Campo Enb

Meaning Enable Event

Hour DAyS

Hour Day

Values On Off hh:mm Mond tueS Wed Thur Frid Satu Sund Cust Shor Jobd Alld noCh Act InAc PUL ASt ToL

(Priority)

Out

X X X X

Outputs State

Meaning Enabled Event Disabled Event Event Hour and Minute Monday Tuesday Wednesday Thursday Friday Saturday Sunday Custom Short Week (5) (Job) Work Days (6) All Days (7) Unchanged Active Inactive Pulse Free Running (Astable) Toggle

Tab. 3 Example Monday

Tuesday

1 1 64 (1x64) 32 (1x32)

Wednesday

0 0 (0x16)

-Free running: the output is controlled in “free running” mode with switch times set through parameters “tx1” and “tx2”. It is initially enabled for the “tx1” time, then turned off for the “tx2” time, then cyclically restarted until the following event, save the occurrence of other functions. A delay set through parameter “dxc” will postpone the first activation of the output. Indicated by label “b”. -Toggle: output is switched. A delay set through parameter “dxc” will postpone the first activation of the output. Indicated by label “t”.

Thursday

1 8 (1x8) 64+32+8+4+2

Outputs can be performed in the following ways: Unchanged, Active, Inactive, Pulse, Free Running, Toggle, Stand-by (see Tab. 1) -Unchanged: the output status is not modified. Indicated by label “n”. -Active: the output is enabled till the following event, save the occurrence of other functions (stand-by or manual operation). A delay set through parameter “dxc” will postpone the output activation. If no status change is programmed between the two events, such delay has no effect. Indicated by label “A”.

Friday

Saturday

Sunday

1 4 (1x4)

1 2 (1x2)

0 0 (0x1)

Parameter CUSt value 110 110

-Inactive: the output is disabled till the following event, save the occurrence of other functions. This function is similar to active mode. Indicated by label “I”. -Pulse: the output is pulse enabled for the time set through parameter “tx1” only, save the occurrence of other functions. A delay set through parameter “dxc” will postpone the output activation. The following event programming has priority over the output status in case the pulse is not yet terminated. In this case parameter “tx2” is not considered. Indicated by label “P”.

EWTS 330/S front panel includes 4 keys, 3 signal leds and a 4 digit display. Out 1 Key Multi function key; it allows to: • manually enable user N. 1; • enter parameters programming mode when held pressed with key St-by for more than 7 sec; • confirm the password or parameter during programming; enable the parameter or event field • change during programming; • enable the data fields change during time programming; • enable the change in the logical status of outputs during their programming. Out 2 Key Multi function key; it allows to: • manually enable user N. 2; • increase the value of the password, parameter or event field during programming; • switch to the following parameter or field during programming; • enter real time programming mode when held pressed with key St-by for more than 7 sec; • increase the date field during time programming; • increase the output status during output programming. Out 3 Key Multi function key; it allows to: • manually enable user N. 3; • decrease the value of the password, parameter or event field during programming; • switch to the previous parameter or field during programming; • enter outputs status manual programming mode when held pressed with key St-by for more than 7 sec; EWTS 330/S 2/8

decrease the date field during time programming; • decrease the output status during output programming. St-by key • Multi function key; it allows to: • enter parameters programming mode when held pressed with key 1 for more than 7 sec; • enter real time programming mode when held pressed with key 2 for more than 7 sec; • enter real output status manual programming mode when held pressed with key 3 for more than 7 sec; • enable the event setting menu; • exit parameters programming mode; • exit real time programming mode. • exit output status manual programming mode; • exit event setting menu; • display current time – current day – output status. Out 1 Led On when relay Out 1 is active. Out 2 Led On when relay Out 2 is active. Out 3 Led On when relay Out 3 is active. Display The display shows: • time in the hh.mm format during normal operation or the status of outputs and instrument according to parameter “dro”; • the error code in case of error; • the parameter value or label during parameters programming. •

REAL TIME PROGRAMMING EWTS 330/S is provided with an internal clock. To change the set time, hold keys “St-by” and “Out 2” pressed for more than 7 seconds. The current time with the blinking minute digits will be displayed. The “UP” and “DOWN” keys can be used to set the required value, key “Out 1” switches to the following field setting (time – day – minutes in sequence). The field being modified blinks. To exit time programming and confirm the set value press key “St-by”. EWTS 330/S is provided with an internal back-up device that allows continuing time count in case of power failure. Autonomy is about 1 hour; then the real time is cancelled from the instrument memory and shall be re-

programmed (in fact the count is set to “h00”-“00'” at start-up). OUTPUT PROGRAMMING To change the logical status of outputs, hold keys “St-by” and “Out 3” pressed for more than 7 seconds. This enters output status programming mode, indicated by the blinking “P” on the first display. The other three displays show the logical status of outputs which is initially set to “nnn”. This programming mode allows actuating users according to a logical sequence in the same way as an event of the automatic event programming would do. Use keys “UP” and “DOWN” to change the status of output indicated by the blinking display and key “Out 1” to confirm setting and activate the following output setting. At the end of selection confirm the last change through the “Out 1” key and press “Stby” to operate. EMERGENCY CYCLE The device provides the management of an emergency cycle that can be enabled through parameters “bAE”,“diAx” and “PoAE”. During the emergency cycle the three users are enabled according to settings made through parameters “SO1E”, “SO2E” and “SO3E”. The alarm signal Emergency user is operated during the emergency cycle according to the mode set through parameters “SOE”, “tE1”,“tE2” and “dEc”. The length of the emergency cycle is determined by parameter “ECd”. At the end of the emergency cycle due to time-out the Emergency user is turned off. Parameter “EcP” can be used to assign the emergency cycle a higher priority on programming. If the emergency cycle is active, letter “E” is displayed on the first display . Black-Out In case of power failure for less than the backup-capacity (about 60 minutes), if the “PoAE” parameter is set to value “n”, when recovering from the black-out the users shall be initially turned off and the display will show Short Black Out error until the first time event or key pressure. By setting parameter PoAE to “y” the emergency cycle can be activated in case of Short Black Out. The alarm is reset by pressing any key or on the first time event.

Long Black Out. In case of power failure for more than the backup capacity, the time count will be locked to “00” of day “1” (Monday) and the outputs disabled. Initially users shall be turned off and the display indicates the Long Black Out error. Parameter bAE can be used to enable the emergency cycle even in case of Long Black Out. Setting the time resets alarm. Digital Input Emergency cycle is activated through a digital input if parameter “diAx” is enabled. If parameter “did” (detect digital input) is set to LEL (LEveL) the digital input related to emergency handled on the level as follows: • presence of digital input (see also polarity) = Active emergency status (if it was not terminated by timeout); • absence of digital input (see also polarity) = Disabled emergency status. If parameter “did” (detect digital input) is set to EdE (EdgE) digital inputs are handled on the front as follows: • positive front (see also polarity) = emergency status toggle. STAND-BY FUNCTION The stand-by function allows to “freeze” the status of outputs by inhibiting the actions of programming and emergency cycle. It can be performed through a digital input or the instrument keyboard (manual). For both modes two parameters (“dSE” and “hSE”) are available to enable the function. Both the digital input, whose polarity is set through parameter “diPx”, and the keyboard activation sequence have the same effect on all outputs. The maximum function time can be set through parameter “Sbt”. When set to 0, there is no limit to duration. The standby function also affects the emergency cycle. In case of manual stand by the first display shows letter “S”. In case of digital input stand by the first display shows a blinking “S”. Digital Input If parameter “did” (detect digital input) is set to LEL (LEveL) the digital input related to stand-by is handled on the level as follows:

EWTS 330/S 3/8

presence of digital input (see also polarity) = Active stand-by status (if it was not terminated by time-out); • absence of digital input (see also polarity) = Disabled stand-by status. If parameter “did” (detect digital input) is set to EdE (EdgE) digital inputs are handled on the front as follows: • positive front (see also polarity) = stand-by status toggle. •

OPERATING USERS FROM DIGITAL INPUTS Users can also be controlled by the related digital inputs: keys di1(OUT1), di2(OUT2) and di3(OUT3). The polarity of digital inputs is controlled by “dPx” parameters –an active state involves the activation of the related user. Digital Input on level If parameter “did” (detect digital input) is set to LEL (LEveL) the digital inputs are handled on level as follows: • presence of digital input (see also polarity) = forced activation of the connected user. The display shows letter d to indicate the output is forced to high value by digital input. The digital input action has no effect on output programming. When the digital input is disabled the output takes the programming value, as if no d.i. event had occurred. Digital Input on front If parameter “did” (detect digital input) is set to EdE (EdgE) the digital inputs are handled on front as follows: • positive front (see also polarity) = toggle of the connected user. This operation also affects programming as the output status is permanently changed until the following event. DIAGNOSTIC The ELbo blinking label indicates the instrument has lost the time memory due to a prolonged electrical black out. Set the time to cancel the signal. The ESbo blinking label indicates the instrument was turned on and no event is active. In this case the time memory has been kept. Press any key to cancel the signal. The fourth display is used to indicate the instrument status during the user status display. Acceptable values are: • “ ”: normal operation; • “S”: stand-by from digital input (blinking);

• • •

“S”: stand-by from keyboard; “P”: output programming; “E”: Active emergency.

PARAMETERS Parameters are visible in two different tables (Parameter description table) which describes the parameter function and while the second table (Parameter features table) provides for a list of the specific features of each parameter. PARAMETERS – EVENTS PROGRAMMING Holding keys “St-by” and “Out 1” pressed for more than 7 seconds enters programming mode. The first user parameter label is displayed. Press the “UP” or “DOWN” key (“Out 2”and “Out 3”) to skip to the other user parameters’ label. To display the value of a user parameter indicated by the label press key “Out 1”. To change it press key “UP” or “DOWN”; to exit parameter setting press key “Out 1” again. The newly set values are automatically stored when programming mode is exited, either when no key is pressed for 10 seconds or by pressing the key during parameters label display. The instrument allows setting a password to access parameters programming mode. To set (or change) the password access parameter “PAS” and introduce a value between 1 and 120 (setting value 0 disables the password). The password will be enabled when exiting parameters programming mode. In case the password is enabled label “PASS” is displayed as access to the parameters programming mode is requested. Press key “Out 1” to access password setting, it can be modified through keys “UP” and “DOWN”. If the password is correct, pressing the “Out 1” key will permit to access programming mode, otherwise it will automatically exit. Parameter “Menu” is used to enter event setting mode. When key “Out 1” is pressed while displaying label “Menu”, the label of the first event, “E00”, will be displayed (if the label is preceded by the minus sign “-” it means the current event is not used). The “UP” and “DOWN” keys can be used to browse the list of events (from 0 to 39). Pressing the "St-by" key in correspondence with the required event can access the event programming sub menu.

The event programming submenus are composed by a series of 6 labels through which all the event variables can be set, in the same modes as in the parameters programming menu. ELECTRICAL CONNECTIONS The instrument is provided with a telephone connector for the connection to the EWTS SLAVE Din module, and with a screw terminal block for the connection of electrical cables with a 2.5 mm2 section (one wire only per terminal according to VDE regulations). EWTS SLAVE is provided with a telephone connector for the connection to the master module, two screw terminal blocks for the connection of electrical cables with a 2.5 mm2 section (one wire only per terminal for power connections). Check the power supply voltage of EWTS SLAVE complies with the instrument requirements. Relay outputs are free from voltage. Do not exceed the maximum allowed current; in case of heavier loads use a suitable power contactor. The connection cables for digital inputs can be lengthened by a common bipolar cable (please remember that too long cables decrease the instrument performances related to EMC electromagnetic compatibility). Outputs for the connection to the TELEVIS system require compliance to indicated polarity. Cables for digital inputs, the connection cable between the two modules and the TELEVIS serial port shall be kept far from relay cables both for EMC and safety reasons. The European coordinated regulations require that relay contact wires (and generally speaking all parts subject to dangerous voltage) shall be separate from very low safety voltage sections (probes and Televis serial) through insulation and distances to ensure at least a double or reinforced insulation. EMC requirements for correct operation suggest / impose to take more care in such separation by using separated insulating raceways and special cable fixing fittings.

EWTS 330/S 4/8

Tab. 4 Parameter Description Table Par. MEnu PrEn CUSt Out 1 Out 2 Out 3 Out A d1c t11 t12 d2c t21 t22 d3c t31 t32 So1E So2E So3E SoE

dEc tE1

tE2 bAE PoAE ECP ECd did diP1 diP2 diP5 diA1 diA2 diA5

hSE dSE Sbto Unt dro dEA FAA CLOF PASS reL tAb

Description Event Programming Menu. 40 Menus for event programming. Event program enable - Program Enable. Allows enabling the management of events programmed through the events menu. Custom week - Custom. OUT 1 user programming. Allows indicating which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) is used to control user OUT1. OUT 2 user programming. Allows indicating which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) is used to control user OUT2. OUT 3 user programming. Allows indicating which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) is used to control user OUT3. Emergency cycle programming - Alarm. Allows indicating on which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) the system alarm is signalled. Out 1 user operation delay - Delay output 1 to change. Operation delay for user Out 1. Every event, both automatic and manual, is delayed by this time. During this period the output is “frozen” to the previous status. Time 1 User 1 - Astable time for out 1 number 1. First operation time for user Out 1. In the pulse or bistable cycle it is the time period during which the user is active. Time 1 User 2. Second operation time for user. Out 1: In the bistable cycle it is the time period during which the user is inactive. Out 2 user operation delay. Operation delay for user Out 2: Every event, both automatic and manual, is delayed by this time. During this period the output is “frozen” to the previous status. Time 1 User 2. First operation time for user Out 2. In the pulse or bistable cycle it is the time period during which the user is active. Time 2 User 2. Second operation time for user. Out 3 user operation delay . Operation delay for user Out 3: Every event, both automatic and manual, is delayed by this time. During this period the output is “frozen” to the previous status. Time 1 User 3. First operation time for user Out 3. In the pulse or bistable cycle it is the time period during which the user is active. Time 2 User 3. Second operation time for user Out 3. In the bistable cycle it is the time period during which the user is inactive. Out 1 status in Emergency. Status of user OUT 1 in the emergency cycle. If the parameter is set to value noCH it has no effect. See also parameter “ECP”. Out 2 status in Emergency. Status of user OUT 2 in the emergency cycle. If the parameter is set to value noCH it has no effect. See also parameter “ECP”. Out 3 status in Emergency. Status of user OUT 3 in the emergency cycle. If the parameter is set to value noCH it has no effect. See also parameter “ECP”. Emergency Output status. Status of the Alarm output in the emergency cycle. If the parameter is set to value noCH it has no effect. For the operation of this output refer to parameters OUtA, dEc, tE1, tE2 and ECd. Emergency cycle delay - Delay Emergency cycle. Delay time for the Alarm user operation. During this period the output is “frozen” to the previous state. Emergency Cycle output Time 1. Astable time for Emergency cycle number 1. First operation time for user Alarm. In the pulse or bistable cycle it is the time period during which the user is active. Emergency Cycle output Time 1. Second operation time for user Alarm. In the bistable cycle it is the time period during which the user is inactive. BlackOut Alarm Enable. Allows enabling or disabling the emergency cycle in case of Black out with consequent loss of the programmed time. Power-On Alarm Enable. Allows enabling or disabling the activation of the emergency cycle in case of Power on with or without loss of the programmed time. Emergency cycle Priority. Allows setting the priority of the emergency cycle on the programmed operation of users OUT1, OUT2 and OUT3. NOTE: The alarm condition shall be present! Emergency cycle duration. Duration of the emergency cycle. When it expires parameter ECP has no longer effect, and output OUT3 is disabled. Digital input sensitivity - detect digital input. Allows setting the sensitivity of the digital inputs, on level or front. Allows setting the polarity for digital input.

Allows assigning a meaning to digital input . Out1: digital input with actuation functionality for user n.1 Out2: digital input with actuation functionality for user n.2 Out3: digital input with actuation functionality for user n.3 EMEr: digital input with actuation functionality for emercency cycle Stby: digital input with actuation functionality of standby-by DiSA: digital input disabled Allows enabling manual StandBy by key. Allows enabling manual StandBy by digital input. See also parameter diAx Stand-By Timeout. Timeout after which the stand-by status is cancelled. Value 0 corresponds to time-out disable. Permits to select the mesaure unit for delay timing and output actutations. default read out. TELEVIS remote control address. TELEVIS SYSTEM remote control address TELEVIS remote control family. TELEVIS SYSTEM remote control family. Frequency synchronism. Read Out of the measured mains frequency. Parameters programming Password. Password to access parameters programming mode. Value 0 disables the password Release firmware. Firmware Release read out. tAble of parameters. Programming Table.

EWTS 330/S 5/8

Tab. 5 Parameter features table Par. MEnu PrEn CUSt Out 1

Description Event Programming Menu. Program Enable. Allows enabling the management of events programmed through the events menu. Custom week - Custom. OUT 1 user programming. Allows indicating which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) is used to control user OUT1.

Model M1 M1

Range / n/y

Default / y

U.M. / Flag

M1 M1

0 rEL1

Num Flag

rEL2

Flag

rEL3

Flag

rEL4

Flag

0

Num

Out 2

OUT 2 user programming. Allows indicating which one of the four physical outputs (rEL1, rEL2, M1 rEL3, rEL4) is used to control user OUT2.

Out 3

OUT 3 user programming. Allows indicating which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) is used to control user OUT3.

M1

Out A

Emergency cycle programming - Alarm. Allows indicating on which one of the four physical outputs (rEL1, rEL2, rEL3, rEL4) the system alarm is signalled.

M1

d1c

M1, M2

M1, M2

0…250

30

Num

M1, M2

0…250

30

Num

M1, M2

0…250

0

Num

M1, M2

0…250

30

Num

M1, M2 M1, M2

0…250 0…250

30 0

Num Num

M1, M2

0…250

30

Num

M1, M2

0…250

30

Num

M1

Flag

noCh

Flag

noCh

Flag

Ast

Flag

dEc tE1 tE2 bAE

Emergency cycle delay - Delay Emergency cycle. Emergency Cycle output Time 1. Emergency Cycle output Time 1. BlackOut Alarm Enable.

M1 M1 M1 M1

noCh, Acti, InAC, PULS, Ast, toL noCh, Acti, InAC, PULS, Ast, toL noCh, Acti, InAC, PULS, Ast, toL noCh, Acti, InAC, PULS, Ast, toL 0…250 0…250 0…250 n/y

noCh

SoE

Out 1 user operation delay - Delay output 1 to change. Operation delay for user Out 1. Every event, both automatic and manual, is delayed by this time. During this period the output is “frozen” to the previous status. Time 1 User 1 - Astable time for out 1 number 1. First operation time for user Out 1. In the pulse or bistable cycle it is the time period during which the user is active. Time 1 User 2. Second operation time for user. Out 1: In the bistable cycle it is the time period during which the user is inactive. Out 2 user operation delay. Operation delay for user Out 2: Every event, both automatic and manual, is delayed by this time. During this period the output is “frozen” to the previous status. Time 1 User 2. First operation time for user Out 2. In the pulse or bistable cycle it is the time period during which the user is active. Time 2 User 2. Second operation time for user. Out 3 user operation delay . Operation delay for user Out 3: Every event, both automatic and manual, is delayed by this time. During this period the output is “frozen” to the previous status. Time 1 User 3. First operation time for user Out 3. In the pulse or bistable cycle it is the time period during which the user is active. Time 2 User 3. Second operation time for user Out 3. In the bistable cycle it is the time period during which the user is inactive. Out 1 status in Emergency. Status of user OUT 1 in the emergency cycle. If the parameter is set to value noCH it has no effect. See also parameter “ECP”. Out 2 status in Emergency. Status of user OUT 2 in the emergency cycle. If the parameter is set to value noCH it has no effect. See also parameter “ECP”. Out 3 status in Emergency. Status of user OUT 3 in the emergency cycle. If the parameter is set to value noCH it has no effect. See also parameter “ECP”. Emergency Output status.

0…127 rEL1, rEL2, rEL3, rEL4, dISA rEL1, rEL2, rEL3, rEL4, dISA rEL1, rEL2, rEL3, rEL4, dISA rEL1, rEL2, rEL3, rEL4, dISA 0…250

Num Num Num Flag

PoAE ECP

Power-On Alarm Enable. Emergency cycle Priority. Allows setting the priority of the emergency cycle on the programmed operation of users OUT1, OUT2 and OUT3. NOTE: The alarm condition shall be present! Emergency cycle duration. Digital input sensitivity - detect digital input. Allows setting the sensitivity of the digital inputs, on level or front. Allows setting the polarity for digital input.

M1 M1

n/y n/y

0 30 30 Secondo modello y y

M1 M1, M2

0…250 EdE/LEL

60 LEL

Num Flag

M1, M2

OPEn/CLOS

OPEn

Flag

diA1: Digital input 1 meaning . Allows assigning a meaning to digital input 1. diA2: Digital input 2 meaning. Allows assigning a meaning to digital input 2. diA5: Digital input 5 meaning. Allows assigning a meaning to digital input 5.

M1, M2

OUt1, OUt2, Out3, EmEr, StbY, dISA

OUt1, OUt2, Out3,

Flag

t11 t12 d2c t21 t22 d3c t31 t32

So1E

So2E

So3E

ECd did diP1 diP2 diP5 diA1 diA2 diA5

M1

M1

M1

Flag Flag

EWTS 330/S 6/8

Tab. 5 (continue)

hSE

Unt dro

hSE: Manual Stand-By Enable - Handle Stand-By. Allows enabling manual StandBy by key. dSE: Digital Input Stand-By Enable. Allows enabling manual StandBy by digital input. See also parameter diAx Sbto: Stand-By Timeout. Timeout after which the stand-by status is cancelled. Value 0 corresponds to time-out disable. Permits to select the mesaure unit for delay timing and output actutations. dro: default read out.

dEA FAA CLOF PASS reL tAb

TELEVIS remote control address. TELEVIS remote control family. Frequency synchronism. Parameters programming Password. Release firmware. tAble of parameters.

dSE Sbto

M1

n/y

n

Flag

M1

n/y

n

Flag

M1

0…250

15

M1, M2 M1, M3

S/P/H Rtc, Out, ALt

M1, M2 M1, M2 M1, M2 M1, M2 M1, M2 M1, M2

0…14 0…14 / 0…120 / /

P Rtc (M1) Out (M2) 0 0 / 0 / /

CONDITIONS OF USE

RESPONSIBILITY AND RESIDUAL RISKS

Permitted Use For safety compliance the control device shall be installed and used according to instructions supplied and parts subject to dangerous shall not be accessible in normal conditions. The device shall be properly protected against water and dust and shall be accessible by using a tool only. The device is suitable to be incorporated in a household appliance and/or similar device in the field of refrigeration / conditioning. According to the reference regulations it is classified: - according to construction as automatic electronic control device to be incorporated with independent mount; - according to automatic operation features as type 1 action control device, with reference to manufacturing tolerances and drifts; - as class 2 device according to protection against electrical shock; - as class A device according to the software structure and class. Forbidden Use Any use different from allowed is forbidden.

Invensy Controls Italy s.r.l. cannot be held responsible for damages due to: - installation/use different from those recommended and from safety prescriptions imposed by regulations; - use on devices that do not guarantee enough protection against electrical shocks, water and dust in the mount conditions; - use on devices that permit access to dangerous part without the use of tools; - product alteration and tampering. - installation and use in devices not complying with legal rules and regulations in force.

Flag Flag Num Num Hz Num Num Num

DISCLAIMER This manual and its contents remain the sole property of Invensys Controls Italy s.r.l. and shall not be reproduced or distributed without authorization. Although great care has been exercised in the preparation of this document, Invensys Controls Italy s.r.l., its employees or its vendors, cannot accept any liability whatsoever connected with its use Invensys Controls Italy s.r.l. reserves the right to make any changes or improvements without prior notice.

EWTS 330/S 7/8

EWTS 330/S Connections

DI1 DI 2

ALARM OUT 12 VC 20 mA



10 11 12

+

1 2 3 4

EWTS SLAVE (330 ver.)

14 15 16 17

19 20 21 22 23 24

EWTS 330/S

13 14 15 16 17 18 gnd



RS-485 Out 2

Out 1

DI5

+

gnd



+

RS-485

Out 3

ALIMENTAZIONE POWER SUPPLY

EWTS 330/S TECHNICAL DATA

EWTS SLAVE TECHNICAL DATA

Housing: plastic 4 Din modules 70x85 mm. Depth: 61 mm. Mounting: Din rail (Omega 3) or wall. Protection grade: IP50 (on front panel). Connections: one telephone connector for the connection to the EWTS SLAVE Din module (version 330) and two screw terminal blocks for wires ≤ 2.5 mm2 (one wire only per terminal for power connections) for other connections. Display: on 4-digit display, digit height 13 mm. Parameters data storage: on non-volatile memory (EEPROM). Operating temperature: –5…55 °C (23… °F). Operating humidity: 10…90% R.H. Storage temperature: –30…75 °C (–22…167 °F). Outputs: three 12 Vc /30 mA outputs to control auxiliary relays in the EWTS SLAVE Din module. Alarm Out Output:12 Vc /20 mA voltage output to control external alarms. Digital inputs: 1 ON/OFF input free from voltage. Serial connection: double RS–485 port for the connection to the TELEVIS system. Consumption: 8 VA. Power supply: from the EWTS SLAVE module.

Housing: plastic 4 Din modules 70x85 mm. Depth: 61 mm. Mounting: Din rail (Omega 3) or wall. Connections: one telephone connector for the connection to EWTS 330/S and two screw terminal blocks for wires ≤ 2.5 mm2 (one wire only per terminal for power connections) for other connections. Operating temperature: –5…55 °C (23… °F). Operating humidity: 10…90% R.H. Storage temperature: –30…75 °C (–22…167 °F). Outputs: 1 15(6) A 250V~ SPDT relay output and 2 8(3) A 250V~ relay outputs. Digital inputs: 2 ON/OFF inputs. Power supply: depending on the model.

EWTS 330/S 2001/8 EWTS 330/S Cod: 9IS22025

8/8