Operating range. 0.85 â1.15 Un. Power consumption at Un. 3 VA AC. 1 W DC. Immunity from micro power cuts. 10 ms. Inputs and measuring circuit. Frequency ...
››Current transformer fitted by passing a cable through the front ››AC current treshold adjustable from 1 to 20 A AC (30 Hz to 400 Hz) via button on front ››Relay output 5 A - 250 V AC - 1 N/O contact ››Multivoltage power supply : 100 to 230 V AC 5060 Hz ››24 V AC / DC
Specifications Measurement range
Supply voltage
Code
2 →500 mA
24 V DC
84871020
2 →500 mA
24 V AC
84871021
2 →500 mA
48 V AC
84871022
2 →500 mA
120 V AC
84871023
2 →500 mA
230 V AC
84871024
Supply Supply voltage Un
24 VDC / 24 VAC / 48 VAC / 120 VAC / 220 VAC
Voltage supply tolerance
-15 % / +15 % limited to -15 % / +10 % if products are mounted without space between them
Operating range
0.85 →1.15 Un
Power consumption at Un
3 VA AC 1 W DC
Immunity from micro power cuts
10 ms
Inputs and measuring circuit Frequency of measured signal
40 →500 Hz
Threshold adjustment
10 →100 % of the measurement range
Adjustable hysteresis
5 →50 % of the displayed threshold
Display precision
± 10 %
Repetition accuracy with constant parameters
± 0.1 %
Measuring error with voltage drift
± 0,1 % (± 10 % Un)
Measuring error with temperature drift
± 0,02 %
Timing Delays on power up (Ti)
0.1 s →20 s ± 10 %
Delay on thresold crossing Tt
0.1 s →3 s ± 10 %
Repetition accuracy with constant parameters
± 0.1 %
Reset time
500 ms
Delay on pick-up
500 ms
I Monitoring Relays
I 02
I www.crouzet-control.com
Output Type of output
1 changeover AgNi, 8A AC max
Type of contacts
No cadmium
Maximum breaking voltage
250 V AC/DC
Max. breaking current
8 AAC max.
Min. breaking current
100 mA AC/DC
Electrical life (number of operations)
AC 12 : 2000 VA - 10⁵ AC 15 : Cos φ = 0,3 - 6 000 DC 13 : L/R = 300 ms - 6 000